- 35 -
0DT869 2019-01-30
FUSES
ID
Value
Size
Circuit
F1 - F2
12A - 500V
10.3 x 38
Single phase line
COMMAND
NOTES
Opening position
at 200 mm from the crosspiece
Partial opening position
at ¾ of total opening
Closing position
on
floor
POSITION ADJUSTMENT
TROUBLESHOOTING
Display message
Problem
Check
Current limit exceeded
Requested motor torque
exceeds available torque.
• Reduce opening speed.
• Check power supply.
• Check power supply wiring.
Encoder battery
Absolute encoder battery flat or
position read error
• Switch off the control panel, wait 3 minutes and
reconnect the power supply.
If the problem is not resolved, try again.
• If the encoder battery message remains displayed,
replace the encoder.
Insert brake resistance
Voltage on BUS exceeds
threshold
• Switch off the control panel, wait 3 minutes and
reconnect the power supply.
• If the error reoccurs, check that the voltage on the
BUS is lower than 360 V.
Max. BUS voltage
BUS voltage exceeds threshold • Switch off the control panel, wait 3 minutes and
reconnect the power supply.
• Check the control panel power supply voltage.
52E
P5
P3
P4
P1
P2
41 40 20 9 8 4 3 2 1 1 0 LAMP
1 11 12 13
ON
OFF 1 2 3 4 5 6 7 8
DL
2 3 4 5 6 7
DL
M7
M4A
M5
M6
M3
BACK
M4
1 IN NC C NO
M2
J4
15
S3 S4
S5
S2
SAFETY
OPEN
F2
F1
230 V
50/60 Hz
GND
L
N
+F -F U V W
ON
EN
Summary of Contents for 0DT869
Page 22: ...22 0DT869 2019 01 30...
Page 24: ...DESSINS INSTALLATION M CANIQUE X Y 4 D C 3...
Page 25: ...MECHANICAL INSTALLATION DRAWINGS 90 9 STOP C NO DS V W U M4x8 7 5 6 E F...
Page 27: ...27 0DT869 2019 01 30...
Page 46: ...46 0DT869 2019 01 30 3 5 1 1 4 2 STOP 6 A B C 1 m EMERGENCY EXIT RESTORE CURTAIN INSTRUCTION...