9/14
Terminal Strip - DA-044N024PXXXT
Maximum wire size for the DA-044N024PXXXT is 14
AWG.
Figure 26. DA-044N024PXXXT Terminal Strip.
Figure 27. DA-044N024PXXXT Wiring Diagram.
Strain Relief
Securing the wires/cabling will prevent breakage and ensure strong
signals to and from the DA-044N024PXXXT model.
The following is recommended:
1. The open bracket to the right of the actuator terminal strip is the
strain relief for the customer provided control wires.
2. Secure the wires to the actuator bracket with a cable tie as shown
in Figure 28.
Figure 28.
Post Header AMP - DA-044N024PXXXA
The DA-044N024PXXXA Post Header AMP has two sets of identical
contacts as shown in Figure 29.
-
All wiring must conform to NEC and local codes and regulations.
-
Use earth ground isolating step-down Class 2 transformers. Do
not use autotransformers.
Determine the supply transformer rating by summing the total VA of all
actuators used. It is recommended that one transformer power no
more than 12 actuators.
Installations requiring
Conformance
-
All wiring for CE rated actuators must only be
separated extra low voltage (SELV) or protective extra
low voltage (PELV) per HD384-4-41.
-
Use safety-isolating transformers (Class III transformer)
per EN 61558. They must be rated for 100% duty cycle.
-
Over current protection for supply lines is maximum
10A.
It is necessary that the output current properly sustain and
operate all DA-044N024PXXXA actuators in a daisy chain
configuration.
Figure 29. DA-044N024PXXXA Post Header AMP.
Figure 30. DA-044N024PXXXA - 0 to 10 Vdc Modulating Control
Wiring Diagram.
The input cable (purchased separately) brings power and a control
signal to the first actuator in a daisy chain configuration. See Figure 32
and Figure 33.
Insert the plug into the DA-044N024PXXXA from the left to
prevent damage to the cable wires. (See Figure 29)
1. The open bracket to the right of the actuator (See Figure
27) is used for strain relief of the customer purchased
cabling (See Required Tools).
2. Secure the cabling to the actuator bracket with a cable
tie. (See Figure 30.)
Modulating Control Input Cable
DA-985-133
3 ft
12 pk
Note:
You
must
select either the top
3 contacts or the
bottom 3 contacts.