background image

 

 

10/14 

 

 

Figure 31.  Always Insert the Cable From the Left. 

 

 

Figure 32.  Input Cable Installed in Bottom Three Contacts. 

Daisy Chain Cables 

DA-985-134 

12 ft 

12 pk 

DA-985-135 

25 ft 

12 pk 

 

Daisy Chain Configuration 

 

Figure 33.  

Note:   

You  must  select  either  the  top  3  contacts  or  the  bottom  3 

contacts. 

 

Do not configure more than 12 actuators in a daisy chain at 
any time. 

Start-Up / Commissioning 

1.  Check that the wires are connected correctly. 

2.  Check that offset and slope are set correctly, if used.  

3.  Check  that  the  direction  of  rotation  switch/cable  matches  the 

rotation of the damper shaft. 

4.  Connect  wires  1  (red)  and  2  (black)  to  a  Digital  Multimeter  (DMM) 

with the dial set at AC V to verify that the operating voltage is within 
range. 

 

Check operation: 

1.  Connect wires 1 (red) and 2 (black) to the actuator.  

2.  Set the DMM dial to Vdc. 

3.  Connect wires 2 (black) and 8 (gray) to the DMM. 

4.  Apply a full-scale input signal (10 Vdc) to wire 8 (gray).  

5.  Allow the actuator shaft coupling to rotate from 0 to 90°. 

6. 

Disconnect  wire  8  (gray)  and  the  shaft  coupling  returns  to  the  “0” 
position. 

 

Check Feedback: 

1.  Set the DMM dial to Vdc. 

2.  Attach wires 2 (black) and 9 (pink) to the DMM. 

3.  Apply  a  full-scale  input  signal  to  wire  8  (gray).  The  reading  at  the 

DMM should increase. 

4. 

Remove  the  signal  from  wire  8  (gray).  The  reading  at  the  DMM 
should decrease and the actuator shaft coupling returns to the “0” 
position.

 

 

Check the Auxiliary Switch A:  

1.  Set the DMM dial to ohms (resistance) or continuity check. 

2.  Connect 

wires 

S1 

and 

S3 

to 

the 

DMM.  

The DMM should indicate open circuit or no resistance. 

3.  Apply  a  full-scale  input  signal  to  wire  8  (gray).  The  DMM  should 

indicate contact closure as the actuator shaft coupling reaches the 
setting of switch A. 

4.  Connect  wires  S1  and  S2  to  the  DMM.  The  DMM  should  indicate 

open circuit or no resistance. 

5. 

Stop  the  signal  to wire 8 (gray). The DMM should indicate contact 
closure as the actuator shaft coupling reaches the setting of switch 
A.

 

 

Check the Auxiliary Switch B: 

1.  Set the DMM dial to ohms (resistance) or continuity check. 

2.  Connect  wires  S4  and  S6  to  the  DMM.  The  DMM  should  indicate 

open circuit or no resistance. 

3.  Apply  a  full-scale  input  signal  to  wire  8  (gray).  The  DMM  should 

indicate contact closure as the actuator shaft coupling reaches the 
setting of switch B. 

4.  Connect  wires  S4  and  S5  to  the  DMM.  The  DMM  should  indicate 

open circuit or no resistance. 

5.  Stop  the  signal  to wire 8 (gray). The DMM should indicate contact 

closure as the actuator shaft coupling reaches the setting of switch 
B. 

 

Note:   

You  must 

select  either  the  top 
3  contacts  or  the 
bottom 3 contacts. 

Summary of Contents for DA-044N Series

Page 1: ...Avoid areas where corroding deteriorating or explosive vapors fumes or gases may be present Ensure that all equipment is installed according to local regional and national regulations Personal injury...

Page 2: ...5 32 inch drill bit and drill Small flat blade screwdriver Marker or pencil Do not open the actuator Place the actuator on the damper shaft so that the front of the actuator is accessible The label i...

Page 3: ...For all damper shafts with the exception of the 1 2 inch round shaft Remove 1 2 inch guide before installation When using a 3 8 inch shaft Remove factory installed 1 2 inch guide See Figure 6 Figure 6...

Page 4: ...r to set the slope span between 2 to 30 Vdc The Y input is limited to a maximum of 10 Vdc If the sum of the offset and slope setting is greater than 10V the angle of rotation is reduced providing the...

Page 5: ...ch When turning the self adaptive feature on or after the software reset with the feature on the actuator will enter a five minute calibration cycle as the actuator adjusts to the rotation limits of t...

Page 6: ...at 70 Self adapt switch ON Input signal Y 5 Vdc The damper will be at 35 50 of the adjusted range Note On versions with the slope and offset features this example assumes Offset Uo 0 Vdc Slope U 10 Vd...

Page 7: ...ust only be connected to Class 2 voltage UL CSA Separated Extra Low Voltage SELV or Protective Extra Low Voltage PELV according to HD384 4 41 for installations requiring conformance Installations requ...

Page 8: ...24 Black pink P1 Feedback Potentiometer 0 to 100 P1 P2 a White red P2 Feedback Potentiometer Common b White blue P3 Feedback Potentiometer 100 to 0 P3 P2 c White pink Each wire has the standard symbol...

Page 9: ...nstallations requiring Conformance All wiring for CE rated actuators must only be separated extra low voltage SELV or protective extra low voltage PELV per HD384 4 41 Use safety isolating transformers...

Page 10: ...8 gray The reading at the DMM should increase 4 Remove the signal from wire 8 gray The reading at the DMM should decrease and the actuator shaft coupling returns to the 0 position Check the Auxiliary...

Page 11: ...able precabled Numbers listed associate with terminal positions M9109 Series is not available precabled Numbers listed associate with terminal positions Floating Control Distech Controls DA 044N Serie...

Page 12: ...12 14 Dimensions Figure 34 Dimensions of the DA ASK75 7U Weather Shield in Inches Millimeters...

Page 13: ...13 14 Dimensions cont d Figure 35 Dimensions of the DA 044N Actuator and Mounting Bracket in Inches mm...

Page 14: ...wiring procedures and maintaining safe working conditions with fail safe environments Distech Controls reserves the right to change delete or add to the information in this manual at any time without...

Reviews: