background image

 

 

6/14 

 

 

Figure 19.  Manual Override. 

Dual Auxiliary Switch Setting 

For  DA-044N024FX2XP,  DA-044N024PA2XP,  DA-044N024PX2XP 
only. 

Factory setting:  

A = 5° 

B = 85° 

Use a flat-blade screwdriver to adjust the A switch. The long arm of the 

 points to the setting. Manually turn the red ring of the B switch. The 

narrower tab on the ring points to the setting. See Figure 20.  

The auxiliary switch setting shafts rotate with the actuator.  

The  scale  is  valid  only  when  the  actuator  is  in  the  "0"  position  on 
clockwise motion. 

 

Figure 20.  Auxiliary Switch Setting Dial. 

Mechanical Range Adjustment 

1.  Loosen the stop set screw.  
2.  Move  it  along  the  track  to  the  desired  position,  and  fasten  it  in 

place. 

 

 

Figure 21.  Moving the Mechanical Range Stop. 

To  use  the  entire  0  to  10V  input  signal  to  control  the  mechanically 
limited range, see Figure 16 for setting self-adaptive features. 

Example: 

Stop set screw at 70° 

Self-adapt switch ON 

Input signal Y = 5 Vdc 

The damper will be at 35° (50% of the adjusted range.) 

Note:   

On  versions  with  the  slope  and  offset  features,  this  example 

assumes 

Offset Uo = 0 Vdc 

Slope 

U = 10 Vdc 

 

Mechanical Range Limitation and  
Self

–Adapt Feature 

1.  To use the entire 0 to 10V input signal to control the adjusted range, 

raise the tab located on the lower left-hand side of the actuator and 
locate the DIP switches. See Figure 22. 

2.  Set the self-adapt DIP switch to 

 (ON). 

3.  Close the tab over the DIP switches.  

For example, if you set the locking screw at 70° and turn the self-adapt 
switch  ON,  a  5V  input  signal  will  drive  the  damper  to  35°  (50%  of  its 
adjusted range). 

 

Factory setting 0 (OFF) 

Figure 22.  Self-adapt Switch in the On Position. 

 

When  turning  the  self-adaptive  feature  on,  or  after  software 
reset with the feature on, the actuator will enter a five-minute 
calibration cycle as the actuator adjusts to the rotation limits 
of  the  system.  The  software  reset  happens  after  power  on, 
or may be caused by electrostatic discharge (ESD) at levels 
of 2 kV and above. 

1

 

2

 

Summary of Contents for DA-044N Series

Page 1: ...Avoid areas where corroding deteriorating or explosive vapors fumes or gases may be present Ensure that all equipment is installed according to local regional and national regulations Personal injury...

Page 2: ...5 32 inch drill bit and drill Small flat blade screwdriver Marker or pencil Do not open the actuator Place the actuator on the damper shaft so that the front of the actuator is accessible The label i...

Page 3: ...For all damper shafts with the exception of the 1 2 inch round shaft Remove 1 2 inch guide before installation When using a 3 8 inch shaft Remove factory installed 1 2 inch guide See Figure 6 Figure 6...

Page 4: ...r to set the slope span between 2 to 30 Vdc The Y input is limited to a maximum of 10 Vdc If the sum of the offset and slope setting is greater than 10V the angle of rotation is reduced providing the...

Page 5: ...ch When turning the self adaptive feature on or after the software reset with the feature on the actuator will enter a five minute calibration cycle as the actuator adjusts to the rotation limits of t...

Page 6: ...at 70 Self adapt switch ON Input signal Y 5 Vdc The damper will be at 35 50 of the adjusted range Note On versions with the slope and offset features this example assumes Offset Uo 0 Vdc Slope U 10 Vd...

Page 7: ...ust only be connected to Class 2 voltage UL CSA Separated Extra Low Voltage SELV or Protective Extra Low Voltage PELV according to HD384 4 41 for installations requiring conformance Installations requ...

Page 8: ...24 Black pink P1 Feedback Potentiometer 0 to 100 P1 P2 a White red P2 Feedback Potentiometer Common b White blue P3 Feedback Potentiometer 100 to 0 P3 P2 c White pink Each wire has the standard symbol...

Page 9: ...nstallations requiring Conformance All wiring for CE rated actuators must only be separated extra low voltage SELV or protective extra low voltage PELV per HD384 4 41 Use safety isolating transformers...

Page 10: ...8 gray The reading at the DMM should increase 4 Remove the signal from wire 8 gray The reading at the DMM should decrease and the actuator shaft coupling returns to the 0 position Check the Auxiliary...

Page 11: ...able precabled Numbers listed associate with terminal positions M9109 Series is not available precabled Numbers listed associate with terminal positions Floating Control Distech Controls DA 044N Serie...

Page 12: ...12 14 Dimensions Figure 34 Dimensions of the DA ASK75 7U Weather Shield in Inches Millimeters...

Page 13: ...13 14 Dimensions cont d Figure 35 Dimensions of the DA 044N Actuator and Mounting Bracket in Inches mm...

Page 14: ...wiring procedures and maintaining safe working conditions with fail safe environments Distech Controls reserves the right to change delete or add to the information in this manual at any time without...

Reviews: