For controllers embedding a pre-loaded application, commissioning can be used to perform application selection if needed. Pre-loaded applications are
factory-loaded programs that enable the controller to control a typical equipment. See the Pre-Loaded Application User Guide for more information.

For ECB Series controllers only, during commissioning, the Allure EC-Smart-Vue sensor is used to set the controller’s BACnet

®

 MAC Address. Set the

connected ECB Series controller’s MAC Address as follows:

Set the connected controller’s MAC Address as follows:

1. Connect an Allure EC-Smart-Vue Series Communicating Sensor to the controller with a Cat 5e patch cable. Wait for the display to show the room

temperature.

2. Press and hold the Menu button 

 for 5 seconds to enter the password menu. 10000 is shown on the display.

OR

Screen Timeout: 15 seconds

3. Use the down button 

 to set the number to 9995 (this is the default password).

OR

Screen Timeout: 15 seconds

4. Press the Menu button 

 to submit the password. Upon submitting the password, the GEN CFG menu appears on the display.

OR

Screen Timeout: 30 seconds

5. Press the down button 

 once to enter the GEN CFG submenu. The MAC ADDRESS menu is shown with the current controller’s BACnet MAC Ad-

dress.

OR

Screen Timeout: 30 seconds

6. Use the up and down buttons 

 

 to set the controller’s MAC Address. Only addresses from 1 to 127 are recommended to be used.

7. Press the Menu button 

 once to apply the value.

8. Press and hold the Menu button 

 for 5 seconds to exit the configuration menu.

Once the controller’s network is operational, the controller can be programmed with EC-

gfx

Program. For each Allure EC-Smart-Vue Series Communicat-

ing Sensor, set its Subnet ID number to the block number of its associated ComSensor block in EC-

gfx

Program. This is done in the sensor’s GEN CFG

menu under SUBNET ID.

Summary of Contents for Allure EC-Smart-Vue Series

Page 1: ...Allow for proper clearance around the device s enclosure and wiring terminals to provide easy access for hardware configuration and maintenance Orient the device with the ventilation slots towards the...

Page 2: ...Mounting pg 3 2 Open the device by pressing in the two 2 tabs on the bottom of the device and pulling the bottom side of the front plate out 3 Set any jumpers see Connector and Jumper Location Identif...

Page 3: ...Smart Vue Sensor Equipped with a CO Sensor The Allure EC Smart Vue C CM CH CHM sensors are factory calibrated to accurately read CO2 concentration levels at sea level When these Allure EC Smart Vue se...

Page 4: ...U 4 1 to 4 ECB 300 ECL 300 ECB 400 Series ECL 400 Series ECB 600 Series ECL 600 Series ECY S1000 Series 12 1 to 12 Table 1 Number of Allure EC Smart Vue sensors supported by controller model 1 A contr...

Page 5: ...ECx 400 Series Subnetwork Bus A controller can support a maximum of two Allure EC Smart Vue sensor models equipped with a CO2 sensor the remaining connected models must be without a CO2 sensor See Tab...

Page 6: ...us ON EOL OFF Controller Series ECB VAV O ECB VAVS ECB VVTS ECB VAV N ECB 103 ECB 203 Series ECB 300 Series ECB 400 Series Back of Allure EC Smart Vue ECL VAV O ECL VAVS ECL VVTS ECL VAV N ECL 103 ECL...

Page 7: ...OFF ON EOL OFF EOL ON Typical Compatible Controller I O Extension Modules ECx 4xx ECx 4xx I O Extension Modules 2 Wire Shielded Last daisy chained I O Extension Module EOL Jumper is ON All other I O E...

Page 8: ...the GEN CFG menu appears on the display OR Screen Timeout 30 seconds 5 Press the down button once to enter the GEN CFG submenu 6 Press the Menu button several times until SUBNET ID appears on the disp...

Page 9: ...lay OR Screen Timeout 15 seconds 3 Use the down button to set the number to 9995 this is the default password OR Screen Timeout 15 seconds 4 Press the Menu button to submit the password Upon submittin...

Page 10: ...r s BAUD rate as follows 1 Connect an Allure EC Smart Vue Series Communicating Sensor sensor to the controller with a Cat 5e patch cable Wait for the display to show the room temperature 2 Press and h...

Page 11: ...rt Vue sensor equipped with a motion sensor to the controller with a Cat 5e patch cable 2 After a 30 second warm up period if movement is detected the motion sensor light will turn on 3 To test the se...

Page 12: ...the indicator PIR LED jumper is enabled If you wish to disable it set jumper J18 to Disabled See Connector and Jumper Location Identification and Configuration pg 3 BACnet Network Access from the Sens...

Page 13: ...work segment should have their Net to Subnet Port Settings jumpers enabled Enabling too many Allure EC Smart Vue sensors with network access may cause network communication issues If there are any net...

Page 14: ...bled Figure 16 LONWORKS Network Bus Topology To temporarily access the LONWORKS LAN for commissioning and maintenance purposes connect a LONWORKS USB network interface to the audio plug port located o...

Page 15: ...ve Allure EC Smart Vue sensor firmware that supports the motion sensor When the Allure EC Smart Vue sensor is connected to a controller its firmware is loaded from the controller In this case the cont...

Page 16: ...sible for using the correct wiring procedures and maintaining safe working conditions with fail safe environ ments Distech Controls reserves the right to change delete or add to the information in thi...

Reviews: