3 / 16
Device Mounting
Security
Screw
Wall
Anchors
Figure 3: Mounting an Allure EC-Smart-Vue Sensor
Connector and Jumper Location, Identification and Configuration
Allure EC-Smart-Vue sensors have the following onsite configurable jumpers.
ON
EOL
OFF
Front Cover, Interior View
BAC
LON
Local Area Network Type
Jumper
BACnet
L
ON
W
ORKS
3.5 mm (1/8”) Local
Area Network
Access Jack
Pass-Through Subnetwork RJ-45 Connectors
D
E
J11
J6
J
1
8
PIR
LED
PIR LED
Motion Detection
Models Only
Disabled
Enabled
Subnetwork End of Line
Enabled
Disabled
Figure 4: Connector and Jumper Locations
About an Allure EC-Smart-Vue Sensor Equipped with a CO₂ Sensor
The Allure EC-Smart-Vue C/-CM/-CH/-CHM sensors are factory calibrated to accurately read CO
2
concentration levels at sea level. When these Allure
EC-Smart-Vue sensors are used in locations where the elevation is greater than 500ft (152m) above sea level, you must set the Elevation input of the
corresponding ComSensor block in EC-
gfx
Program to the current location’s elevation to obtain the most accurate readings.
For more information, refer to the ComSensor block section in the EC-
gfx
Program User Guide
Under normal conditions, an Allure EC-Smart-Vue sensor with CO
2
sensor will typically reach its operational
accuracy after 25 hours of continuous operation on the condition that it was exposed to ambient air reference levels
of 400 ppm ±10 ppm CO
2
.