10
discoverbattery.com
6.4 Discharging
• Set the battery to ON
• Set the load to ON
• Recommended low voltage cut off: 24 V | 36 V | 48 V
▲
NOTE!
Do not discharge battery below recommended minimum
operating voltages.
▲
NOTE!
Do not discharge battery at rates greater than
recommended operating currents.
6.5 Storage
Systems should be stored out of direct sunlight under the following temperature conditions:
Minimum Storage Temperature
-20°C / -4°F
Maximum Storage Temperature
45°C / 113°F
Systems should be put into storage at 80% SOC and checked monthly to ensure SOC does not fall below 20%.
At 20% SOC the battery will self discharge in approximately 2 months.
▲
CAUTION!
Do not store a discharged battery. Recharge battery after
every use. Batteries that have self-discharged to a severely
discharge state are not recoverable.
7. Service & Maintenance
7.1 Warranty Registration
To register your product you will need the serial number of the battery. Visit discoverbattery.com for registration details.
7.2 Inspection
Batteries should be carefully inspected on a regular basis in order to detect and correct potential problems before they do harm.
This routine should be started when the batteries are first received.
• Inspect for cracks in the battery casing
• Check battery terminals and connections to make sure they are clean, free of dirt, fluids and corrosion
• All battery cables and their connections should be tight, intact, and NOT broken or frayed
• Replace any damaged batteries
• Replace any damaged cables
• Ensure correct torque is used for the terminal bolts
7.3 Battery Firmware
Consult the Discoverbattery.com website for the latest battery firmware versions. If a battery firmware update is require, ensure
this is done by a qualified and authorized person using the AES Dashboard software tool.
8. Recycling and Disposal