background image

Fig. 2: Level meter dead zone

m – Dead zone

  

I

NSTALLATION

 

INSTRUCTIONS

Install the level meter in the 

• 

vertical position

 into the upper lid of the tank or reservoir using 

a welding 

fl

 ange, a fastening nut or a 

fl

 ange so that the level meter axis can be perpendicular to 

the surface level of the measured liquid (Fig. 1).

  The  min. 

• 

dimensional parameters

 to install the 

level meter into a lid or a ceiling of a tank are given 
in Fig. 3.

When installing in an 

• 

open channel

 (reservoir, drain 

etc.), install the level meter onto a bracket as close as 
possible to the expected max. level.

In connection with the measurement principle, no 

• 

signals 

re

fl

 ected

 in the area immediately under the 

level meter can be evaluated (dead zone). 

The dead 

zone

 (Fig. 2) determines the min. distance possible 

between the level meter and the highest surface lev-
el. The min. distances to the medium are given in the 
chapter "Technical speci

fi

 cations" (p. 24).

It is necessary to install the level meter so that the 

• 

bin level cannot 

interfere

 with the dead zone when 

fi

 lled up to the maximum. If the measured level in-

terferes with the dead zone, the level meter will not 
work properly.

Fig. 1: Recommended installation

in the tank

Fig. 4: Possible installation of the installation neck

a – Neck height
b – Neck width
m – Dead zone

ULM–70–02 ; 06

a < 3 b
b > 100 mm

ULM–70–10

a < 1,5 b
b > 100 mm 

ULM–70–20

a < 1,5 b
b > 150 mm

Fig. 3: Installation distance from the tank wall

ULM–70–02 ; 10

d > 1/12 c 

(min. 200 mm)

ULM–70–06

d > 1/8 c 

(min. 200 mm)

ULM–70–20

d > 1/10 c

(min. 200 mm)

d – Distance from
      the tank wall 

c – Measurement 
      range of the level 
      meter

If the maximum surface level in the tank interferes with the dead zone, the level meter has 

• 

to be mounted into a higher 

installation neck

. In this way, the tank can be 

fi

 lled nearly up to 

the maximum volume. The inner neck surface has to be even and smooth (without edges and 
welded joints); the inner edge should be rounded where the ultrasonic wave leaves the pipe. 
The neck diameter should be as large as possible but the neck height should be as low as 
possible. Recommended dimensions of the input neck are given in Fig. 4.

www.jetec.com.tw

久德電子      

TEL:

+886-4-23729418     

FAX:

+886-4-23724011   

(40349)

台中市西區福人街11號

Summary of Contents for ULM -70 Series

Page 1: ...ully the instructions published in this manual before the first use of the level meters Keep the manual at a safe place The manufacturer reserves the right to implement changes without prior notice UL...

Page 2: ...Operation 10 Basic settings 10 Advanced settings 13 Additional functions 15 HART communication protocol 18 Order code 18 Accessories 18 Safety protection compatibility and explosion proof 19 Use mani...

Page 3: ...he individual pulses spread towards the surface level and back and based on the measured temperature in the tank the instant distance to the surface level is calculated According to the level height t...

Page 4: ...ENSIONAL DRAWINGS ULM 70_ 02 I ULM 70_ 06 I ULM 70N 10 I ULM 70_ 20 I ULM 70Xi 10 I Al alloy Al alloy HDPE Pg11 cable gland Ground terminal www jetec com tw TEL 886 4 23729418 FAX 886 4 23724011 40349...

Page 5: ...level cannot interfere with the dead zone when filled up to the maximum If the measured level in terferes with the dead zone the level meter will not work properly Fig 1 Recommended installation in th...

Page 6: ...sary to map false reflections by activating the mode TEACHING see p 14 In case of in stalled mixers it is necessary to put the mixers to position under the level meter direct the mixer blade to the ul...

Page 7: ...hu midity To lower the minimum distance to the measured medium a reflection board made from solid even and smooth material can be installed to the level meter Then the tank can be filled nearly up to...

Page 8: ...use from several sides to slightly lift the module Release the cable bushing and thread the 4 stripped supply cable in Connectthecableintotheboltedclipsaccording 5 to the diagram in Fig 14 Assemble t...

Page 9: ...unction NO ECHO Lighting intermittently the level meter is not able to receive echo for a long time Incorrect installation of the level meter DEAD ZONE Lighting intermittently the measured level is in...

Page 10: ...that have not been confirmed using the button OK will not be saved After the meter is locked you cannot change the setting When you attempt to edit the words NO PASSWORD will appear on the display Ho...

Page 11: ...er assigns the 20mA value for the measured value automatically 4 Using the buttons OK and set the values to display on the display DISP and select the units U 5 After the setting is completed save the...

Page 12: ...damping time can be set in the interval from 0 to 99 sec 1 Press the button OK to access the basic menu Use the same button to select the item BASIC ADJUSTEMENT Then use the button and OK to select th...

Page 13: ...m roughnesses on walls of the tank various partitions mixers or other obstacles The sensor starting this mode detects false reflections and save them in the memory Then these false reflections will no...

Page 14: ...s it is necessary to position the mixers under the level me ter direct the mixer blade to the ultrasonic signal beam Note If there are significant obstacles in the upper half of the tank multiple fals...

Page 15: ...as also a short time interruption of the supply voltage To enable the resetting press the button OK During the restart process RUNNING will be displayed Then the level meter will be automati cally tur...

Page 16: ...Lock the level meter You can set any digital combination to lock the level meter and prevent an unauthorised person from setting 1 Use the buttons OK and in the menu PASSWORD to select the mode ENTER...

Page 17: ...pe data Information about the type serial number and production date of the level meter ST Level meter type SN Serial number SW Firmware version www jetec com tw TEL 886 4 23729418 FAX 886 4 23724011...

Page 18: ...nicator ULM 70 PC 250R Voltage supply unit ORDER CODE ACCESSORIES Standard included in the price of the level meter Optional for extra charge 1x Seal only for ULM 70_ 02 I 06 I Stainless fixing nut UM...

Page 19: ...operation Maintenance of this equipment consists in verification of integrity of the level meter and of the supply cable Depending on the character of the substance measured we recommend to verify at...

Page 20: ...iance mark Electro waste take back system mark Level meters label data ULM 70Xi 02 I and ULM 70Xi 06 I Symbol of producer logo Dinel Level meter type ULM 70Xi 02 I ULM 70Xi 06 I Serial number Ser No x...

Page 21: ...person examining control of system quality 1026 Electro waste take back system mark Level meters label data ULM 70Xi 20 I Symbol of producer logo Dinel Level meter type ULM 70Xi 20 I Serial number Se...

Page 22: ...M ENU STRUCTURE www jetec com tw TEL 886 4 23729418 FAX 886 4 23724011 40349 11...

Page 23: ...data 2 only for variant Xi Max internal values Ui 30VDC Ii 132mA Pi 0 99W Ci 370nF Li 0 9mH Failure indication echo loss level in dead zone internal failure Adjustable in modes 3 75mA 22mA last measu...

Page 24: ...le level meter zone 1 front head part zone 0 ULM 70Xi 20 I Explosive proof suitable for explosive areas combustible gases or vapours II 2G Ex ia IIA T5 with isolating repeater IRU 420 the whole level...

Reviews: