1. Press the button
[OK]
to access the basic menu. Use the same button to select the item "BASIC
ADJUSTEMENT". Then use the button
[
↑
↓
]
and
[OK]
to select the item "MANUAL MIN" or
"MANUAL MAX".
2. Now the item "MANUAL MIN" or "MANUAL MAX" is displayed (as selected). Using the buttons
[OK]
and
[
↑
↓
]
, set the output current "OUTPUT" and distance for the de
fi
ned current "LEVEL",
display of the value on the display "DISP" and unit selection "U".
3. After the setting is completed, save the data using the button
[OK]
. By repeated pressing the
button
[ESC]
, you leave the menu and the display of the level meter and return back to the
measurement mode.
1. Fill up the tank up to the required level.
2. Press the button
[OK]
to access the basic menu. Use the same button to select the item "BASIC
ADJUSTMENT" and then use
[
↑
↓
]
and
[OK]
to select the item “AUTO MAX”.
3. Now the item "AUTO MAX" is displayed. The level meter assigns the 20mA value for the measured
value automatically.
4. Using the buttons
[OK]
and
[
↑
↓
]
, set the values to display on the display "DISP" and select the
units "U".
5. After the setting is completed, save the data using the button
[OK]
. By repeated pressing the
button
[ESC]
, you leave the menu and the display of the level meter and return back to the
measurement mode.
"MANUAL MIN and MANUAL MAX" (Manual setting of limits)
In these items, you can de
fi
ne min. or max. level, to which you can assign an optional output current in
the range of 4 ÷ 20mA. This is recommended to carry out if the
fi
nal value of the min. and max. level is
known but it is not possible to
fl
ood the tank up to these limits.
For convenience, it is suitable to assign 4mA cur-
rent to the min. value and 20mA current to the
max. value.
OUTPUT: Setting of output current (4 ÷ 20mA)
LEVEL: Setting of distance of the level from the
front of the level meter in mm
DISP: Display of measured values on the display
U: Unit selection (mm, cm, m, l, m
3
,mA, %)
www.jetec.com.tw
久德電子
TEL:
+886-4-23729418
FAX:
+886-4-23724011
(40349)