7.5 Electrical connection 

7.5.1 General

All  electrical  installation  work  must  be  carried  out  by  a  trained
electrician  or  a  specialist  for  the  specified  tasks  in  accordance
with the 

installation and operating instructions, 

country-specific installation regulations (e.g. VDE 0100),

technical connection conditions of the energy suppliers and
supply grid operators (e.g. TAB) and

local conditions. 

To  ensure  that  the  frost  protection  function  of  the  heat  pump
works properly, the heat pump manager must remain connected
to the power supply and the flow must be maintained through the
heat pump at all times.
The switching contacts of the output relay are interference-sup-
pressed. Therefore, depending on the internal resistance of the
measuring instrument, a voltage can also be measured when the
contacts are open. However, this will be much lower than the line
voltage.
Extra-low  voltage  is  connected  to  controller  terminals  N1-J1  to
N1-J11; N1-J19 to N1-J20; N1-J23 to N1-J26 and the terminal
strips X3. If, due to a wiring error, the line voltage is mistakenly
connected to these terminals, the heat pump manager will be de-
stroyed.

NOTE

º

For installation work on the switch box, ensure that the mains cable and
signal cables are inserted separately into the switch box. The specially
arranged switch box inlets must be used for this purpose (see Fig.7.4 on
pag. 8). 
The mains cables and signal cables must also always be laid separately
in the switch box during wiring work.

Fig. 7.4:Cable inlet switch box

7.5.2 Electrical connection

1)

The  four-core  electrical  supply  cable  for  the  heat  pump
power part is fed from the heat pump electricity meter into
the heat pump via the utility company blocking contactor (if
required) (for supply voltage, see heat pump manual).
The  mains  cable  is  connected  to  the  heat  pump  contact
plate via terminals X1: L1/L2/L3/PE.

ATTENTION!

!!

Ensure that there is a clockwise rotating field: With incorrect wiring the
starting of the heat pump is prevented. A corresponding warning is
indicated on the display of the heat pump manager (adjust wiring).

An  all-pole  disconnecting  device  with  a  contact  gap  of  at  least
3 mm (e.g. utility company blocking contactor or power contac-
tor) and an all-pole circuit breaker with common tripping for all
external conductors must be installed in the power supply for the
heat pump (tripping current and characteristic in compliance with
the device information).
2)

The  three-core  supply  cable  for  the  heat  pump  manager
(heating controller N1) is fed into the heat pump. Connection
of the control cable to the contact plate of the heat pump via
terminal X2: L/N/PE.
The (L/N/PE~230 V, 50 Hz) supply cable for the heat pump
manager must have a continuous voltage. For this reason, it
should be tapped upstream from the utility company block-
ing contactor or be connected to the household current, as
important protection functions could otherwise be lost during
a utility block.

3)

The utility company blocking contactor (K22) with main con-
tacts  and  an  auxiliary  contact  must  be  designed  and  pro-
vided  by  the  customer  in  accordance  with  the  heat  pump
output.
The NO contact of the utility company blocking contactor is
looped  from the terminal  strip X3/G  to the plug-in  terminal
X3/A1. 

CAUTION! Extra-low voltage

!

4)

The contactor (K20) for the immersion heater (E10) of mono
energy systems (HG2) should be dimensioned according to
the radiator output and must be supplied by the customer. It
is controlled (230 V AC) by the heat pump manager via ter-
minals X2/N and X2/K20.

5)

The contactor (K21) for the flange heater (E9) in the domes-
tic  hot  water  cylinder  should  be  dimensioned  according  to
the radiator output and must be supplied by the customer. It
is controlled (230 V AC) by the heat pump manager via ter-
minals X2/N and X2/K21.

6)

The contactors mentioned above in points 3, 4 and 5 are in-
stalled in the electrical distribution system. 

7)

All installed electric cables must have permanent wiring.

8)

The heat circulating pump (M13) is activated via the contact
N1-J13/NO5.  The  connection  points  for  the  pump  are  X2/
M13 and X2/N. When using pumps where the switching ca-
pacity  exceeds  the  output,  a  coupling  relay  must  be  inter-
posed.

9)

The auxiliary circulating pump (M16) is activated via the con-
tact  N1-J16/NO9.  The  connection  points  for  the  pump  are
X2/M16 and X2/N. A coupling relay is already integrated in
this output.

10) The domestic hot water circulating pump (M18) is activated

via the contact N1-J13/NO6. The connection points for the
pump are X2/M18 and X2/N. When using pumps where the
switching capacity exceeds the output, a coupling relay must
be interposed.

A

A

Supply mains cable 
line voltage

Supply signal cable 
extra-low voltage

Summary of Contents for WI 65TU

Page 1: ...TU WI 95TU Montage und Gebrauchsanweisung Installation and Operating Instruction Instruction d installation et d utilisation Wasser Wasser W rmepumpe f r Innenaufstellung Water to Water Heat Pump for...

Page 2: ......

Page 3: ...tiger Anschluss DE 6 7 4 Temperaturf hler DE 6 7 5 Elektrischer Anschluss DE 8 8 Inbetriebnahme DE 9 8 1 Allgemeine Hinweise DE 9 8 2 Vorbereitung DE 9 8 3 Vorgehensweise bei Inbetriebnahme DE 9 9 Pfl...

Page 4: ...m er Gebrauch Dieses Ger t ist nur f r den vom Hersteller vorgesehenen Ver wendungszweck freigegeben Ein anderer oder dar ber hinaus gehender Gebrauch gilt als nicht bestimmungsgem Dazu z hlt auch die...

Page 5: ...om elektrisch angetriebenen Verdichter an gesaugt verdichtet und auf ein h heres Temperaturniveau ge pumpt Die bei diesem Vorgang zugef hrte elektrische Antriebs leistung geht nicht verloren sondern w...

Page 6: ...st ein Durchflussschalter vorzusehen der das Einschalten des Verdichters bei fehlendem Volumenstrom verhindert 5 Transport Zum Transport auf ebenem Untergrund eignet sich ein Hubwa gen Muss die W rmep...

Page 7: ...zungsseitiger Installation ist die Heizungsan lage zu f llen zu entl ften und abzudr cken ACHTUNG Der maximale Pr fdruck betr gt heiz und prim rseitig 6 0 bar Dieser Wert darf nicht berschritten werde...

Page 8: ...sschalter ist zwingend im Vorlauf Austritt der W rmequelle einzubauen Dabei ist das hydraulische Einbindungsschema zu beachten 7 4 Temperaturf hler Folgende Temperaturf hler sind bereits eingebaut bzw...

Page 9: ...Schlauchschelle befestigen gut festziehen lose F hler f hren zu Fehlfunktionen und thermisch isolieren 7 4 4 Verteilsystem Hydraulik Kompaktverteiler und doppelt differenzdruckloser Verteiler fun gie...

Page 10: ...ffnungsabstand z B EVU Sperrsch tz Leistungssch tz sowie ein allpoliger Si cherungsautomat mit gemeinsamer Ausl sung aller Au enlei ter vorzusehen Ausl sestrom und Charakteristik gem Ger teinformation...

Page 11: ...on 2 A und ein maximaler Anlaufstrom von 12 A der elektronisch geregelten Umw lzpumpe nicht ber schritten wird oder es liegt eine ausdr ckliche Freigabe des Pumpenherstellers vor ACHTUNG Es ist nicht...

Page 12: ...nde Schmutzf nger zu montieren um den Verdampfer gegen Verunreinigungen zu sch tzen Im W rmequelleneintritt der W rmepumpe ist ein Schmutzf n ger montiert um den Verdampfer gegen Verunreinigungen zu s...

Page 13: ...digen Kundendienst ACHTUNG Arbeiten an der W rmepumpe d rfen nur vom autorisierten und sachkundigen Kundendienst durchgef hrt werden ACHTUNG Vor ffnen des Ger tes sind alle Stromkreise spannungsfrei z...

Page 14: ...ach EN 12102 dB A 61 62 4 4 Schalldruck Pegel in 1 m Entfernung1 dB A 45 46 5 Abmessungen Gewicht und F llmenge 5 1 Ger teabmessungen2 H x B x L mm 1665 x 1000 x 805 1900 x 1350 x 805 5 2 Gewicht der...

Page 15: ...stellt den Freifeldpegel dar Je nach Aufstellungsort kann der Messwert um bis zu 16 dB A abweichen 2 Beachten Sie dass der Platzbedarf f r Rohranschluss Bedienung und Wartung gr er ist 3 Diese Angaben...

Page 16: ...h auf das Ger t und vom Lieferer bezogene Teile Nicht vom Lieferer bezogene Teile und Ger te Anlagenm ngel die auf nicht vom Lieferer bezogene Teile zur ckzuf hren sind fallen nicht unter den Garantie...

Page 17: ...5 7 3 Heat source connection EN 6 7 4 Temperature sensor EN 6 7 5 Electrical connection EN 8 8 Commissioning EN 9 8 1 General Information EN 9 8 2 Preparation EN 9 8 3 Commissioning procedure EN 9 9 C...

Page 18: ...electrical circuits from the power source prior to opening the device 1 2 Intended use This device is only intended for use as specified by the manufac turer Any other use beyond that intended by the...

Page 19: ...ressed and pumped to a higher temperature level The electrical power needed to run the compressor is not lost in this process Most of it is absorbed by the refrigerant The refrigerant subsequently pas...

Page 20: ...olled externally a flow rate switch is required to prevent the compressor from being switched on when there is no volume flow 5 Transport A lift truck is suited for transporting the unit on a level su...

Page 21: ...illed de aerated and pressure tested ATTENTION The maximum test pressure in the heating circuit and the primary circuit is 6 0 bar This value must not be exceeded The following points must be observed...

Page 22: ...ed in the flow outlet of the heat source The hydraulic integration diagram must be adhered to 7 4 Temperature sensor The following temperature sensors are already installed or must be installed additi...

Page 23: ...th a hose clip tighten firmly as loose sensors can cause malfunctions and thermally insulate 7 4 4 Hydraulic distribution system The compact manifold and the dual differential pressureless manifold fu...

Page 24: ...pole circuit breaker with common tripping for all external conductors must be installed in the power supply for the heat pump tripping current and characteristic in compliance with the device informat...

Page 25: ...nt of 2 A and a maximum starting current of 12 A are not exceeded in the electronically regulated circulating pump or if express approval has been issued by the pump manufacturer ATTENTION It is not p...

Page 26: ...served 9 3 Cleaning the heat source system ATTENTION The supplied dirt trap must be inserted in the heat source inlet of the heat pump to protect the evaporator against the ingress of impurities The f...

Page 27: ...ician ATTENTION Work on the heat pump must only be performed by authorised and qualified after sales service technicians ATTENTION Disconnect all electrical circuits from the power source prior to ope...

Page 28: ...el at a distance of 1m1 dB A 45 46 5 Dimensions weight and filling quantity 5 1 Device dimensions 2 H x W x L mm 1665 x 1000 x 805 1900 x 1350x 805 5 2 Weight of the transportable unit s incl packagin...

Page 29: ...d value can deviate by up to 16 dB A depending on the installation location 2 Note that additional space is required for pipe connections operation and maintenance 3 These data indicate the size and c...

Page 30: ...EN 14 452237 66 11 FD 9908 www gdts one English WI 65TU WI 95TU...

Page 31: ...Raccordement c t source de chaleur FR 6 7 4 Sonde de temp rature FR 6 7 5 Branchements lectriques FR 8 8 Mise en service FR 9 8 1 Remarques d ordre g n ral FR 9 8 2 Pr paratifs FR 9 8 3 Proc dures su...

Page 32: ...appareil ne doit tre employ que pour l affectation pr vue par le fabricant Toute autre utilisation est consid r e comme non conforme La documentation accompagnant les projets doit galement tre prise...

Page 33: ...d livr e au fluide frigorig ne du circuit frigorifique Le fluide frigorig ne est aspir par le compresseur commande lectrique compress et pomp un niveau de temp rature plus lev L nergie lectrique mise...

Page 34: ...as de commande externe de la pompe chaleur ou des circulateurs pr voir un commutateur de d bit servant emp cher la mise en marche du compresseur en cas d absence de flux volumique 5 Transport Le trans...

Page 35: ...ouv e la pression ATTENTION La pression d preuve maximale s l ve c t chauffage et circuit primaire 6 0 bars de surpession Cette valeur ne doit pas tre d pass e Respecter les consignes suivantes lors d...

Page 36: ...part sortie de la source de chaleur Suivre pour cela les indications du sch ma d int gration hydrau lique 7 4 Sonde de temp rature Les sondes de temp rature suivantes sont d j mont es ou doivent tre...

Page 37: ...ouche La sonde doit tre fix e avec un collier serrer fond des sondes mal fix es engendrent des d fauts et isol e thermi quement 7 4 4 Syst me de distribution hydraulique Le distributeur compact et la...

Page 38: ...leur changer le c blage Sur l alimentation de puissance de la pompe chaleur pr voir une coupure omnipolaire avec au moins 3 mm d cartement d ouverture de contact p ex contacteur de blocage de la so ci...

Page 39: ...tall doit tre install entre la sortie du gestionnaire de pompe chaleur et le circulateur r gulation lectronique Cette disposi tion n est pas n cessaire si le circulateur r gulation lectro nique ne d...

Page 40: ...d ventuels restes de produit de nettoyage dans le syst me Les acides doivent tre utilis s avec pr caution et les prescrip tions des caisses de pr voyance des accidents doivent tre res pect es Observer...

Page 41: ...vannes Le d montage de la pompe chaleur doit tre effectu par du personnel sp cialis Il faut se conformer aux exigences relatives l environnement quant la r cup ration la r utilisation et l limination...

Page 42: ...dB A 45 46 5 Dimensions poids et capacit 5 1 Dimensions de l appareil2 H x l x L mm 1665 x 1000 x 805 1900 x 1650 x 805 5 2 Poids de l unit ou des unit s de transport emballage compris kg 465 565 5 3...

Page 43: ...ropagation en champ libre La valeur mesur e peut varier selon l emplacement de 16 dB A max 2 Tenir compte de la place n cessaire plus importante pour le raccordement de tuyau la commande et l entretie...

Page 44: ...FR 14 452237 66 11 FD 9908 www gdts one Fran ais WI 65TU WI 95TU...

Page 45: ...III 3 3 Last Load Charge A IX 3 4 Anschlussplan Connection Plan Sch ma de connexion A X 3 5 Anschlussplan Connection Plan Sch ma de connexion A XI 3 6 Legende Legend L gende A XII 4 Hydraulisches Einb...

Page 46: ...voltage Alimentation ligne de signalisation faible tension 1 1 Heizungsvorlauf Ausgang aus W rmepumpe Rp 1 1 2 1 2 Heizungsr cklauf Eingang in W rmepumpe Rp 1 1 2 1 5 W rmequellenvorlauf Eingang in W...

Page 47: ...limentation ligne de signalisation faible tension 1 1 Heizungsvorlauf Ausgang aus W rmepumpe Rp 2 1 2 Heizungsr cklauf Eingang in W rmepumpe Rp 2 1 5 W rmequellenvorlauf Eingang in W rmepumpe Rp 2 1 2...

Page 48: ...auffage Leistungsaufnahme in kW incl Pumpenleistungsanteil Power consumption in kW incl power input to pump Consommation de puissance en kW y compris part de consommation de la pompe Druckverlust in P...

Page 49: ...n in kW incl power input to pump Consommation de puissance en kW y compris part de consommation de la pompe Druckverlust in Pa Pressure loss in Pa Perte de pression en Pa Leistungszahl incl Pumpenleis...

Page 50: ...0 35 40 45 50 55 60 65 0 5 10 15 20 25 30 Heizwassertemperatur C Heating water temperatur e C Temp rature d eau chauffage C W rmequelleneintrittstemperatur C Heat source inlet temperature C Temp ratur...

Page 51: ...www gdts one 452237 66 11 FD 9908 A VII WI 65TU WI 95TU Anhang Appendix Annexes 3 Stromlaufpl ne Circuit Diagrams Sch mas lectriques 3 1 Steuerung Control Commande...

Page 52: ...A VIII 452237 66 11 FD 9908 www gdts one Anhang Appendix Annexes WI 65TU WI 95TU 3 2 Steuerung Control Commande...

Page 53: ...www gdts one 452237 66 11 FD 9908 A IX WI 65TU WI 95TU Anhang Appendix Annexes 3 3 Last Load Charge...

Page 54: ...A X 452237 66 11 FD 9908 www gdts one Anhang Appendix Annexes WI 65TU WI 95TU 3 4 Anschlussplan Connection Plan Sch ma de connexion...

Page 55: ...www gdts one 452237 66 11 FD 9908 A XI WI 65TU WI 95TU Anhang Appendix Annexes 3 5 Anschlussplan Connection Plan Sch ma de connexion...

Page 56: ...rmostat gaz chaud F10 1 Durchflussschalter Prim rkreis Flow rate switch for primary circuit Commutateur de d bit circuit primaire F10 2 Durchflussschalter Sekund rkreis Flow rate switch for secondary...

Page 57: ...ng circuit low pressure pO Capteur de pression circuit r frig rant basse pression pO R26 Drucksensor K ltekreis Hochdruck pc Pressure sensor for refrigerating circuit high pressure pc Capteur de press...

Page 58: ...c integration diagram Sch ma d int gration hydraulique 4 1 Monovalente W rmepumpenanlage mit einem Heizkreis Monovalent heat pump system with one heating circuits Installation monovalente de pompe cha...

Page 59: ...rmwasserbereitung Monovalent heat pump system with one heating circuits and domestic hot water preparation Installation monovalente de pompe chaleur avec une circuits de chauffage et production d eau...

Page 60: ...nschlussschlauch Flexible connection hose Tuyau de raccord flexible R ckschlagklappe Check valve Clapet anti retour Wasser Wasser W rmepumpe Water to water heat pump Pompe chaleur eau eau Reihen Puffe...

Page 61: ...g Declaration of Conformity D claration de conformit Die aktuelle CE Konformit tserkl rung finden sie als Download unter You can find and download the current CE conformity declaration at Vous pouvez...

Page 62: ...A XVIII 452237 66 11 FD 9908 www gdts one Anhang Appendix Annexes WI 65TU WI 95TU...

Page 63: ...www gdts one 452237 66 11 FD 9908 A XIX WI 65TU WI 95TU Anhang Appendix Annexes...

Page 64: ...tschland GmbH Gesch ftsbereich GDTS Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 9245...

Reviews: