7 Installation and electrical connection

The installation and the electrical connection must be carried out
by specialists and in compliance with the local regulations!

ATTENTION!

!!

WARNING! Danger of personal injury
The regulation module cannot be dismantled. If the regulation module
has been separated from the pump by force, there is danger of personal
injury:

 When the pump is in generator operation (with the rotor driven by the

booster pump) a dangerous voltage is present at the motor terminals
which are not protected against accidental contact.

 Due to the remaining electrical connection on the regulation module

ATTENTION!

!!

WARNING! Danger of personal injury!
Observe the valid accident prevention regulations.

ATTENTION!

!!

WARNING! Danger of electric shock
It must be ensured that there are no risks resulting from electrical energy.
Instructions resulting from local or general regulations (e.g. IEC, VDE
etc.) and from local utility companies must be observed.

7.1 Installation

The system/pump must be installed in a dry, well-ventilated
room protected from frost.

The system/pump must not be installed until all welding and
soldering  work  is  completed;  the  pipe  system  must  be
flushed if necessary. 

ATTENTION!

!!

CAUTION! Danger of damage to property!
Any impurities in the pipe system can destroy the pump during operation.
Flush the pipe system before the pump is installed.

The  installation  of  shutoff  devices  upstream  and  down-
stream from the pump is recommended. This means that it
is  not  necessary  to  drain  and  re-fill  the  system  when  the
pump is replaced.

Carry  out  tension-free  installation.  The  pipes  must  be
mounted such that the pump does not bear the weight of the
pipes.

The flow direction of the medium must correspond to the di-
rection triangle on the pump casing.

Mounting  positions  according  to  Abb  1.1  Anhang  Seite II
only. The pump shaft must be horizontal.
Under  special  installation  conditions,  the  motor  can  be  ro-
tated to bring the regulation module into a horizontal posi-
tion. (Kap. 7.1.1 auf S. 7)

The pump must be installed in an easily accessible position
in order to facilitate subsequent service work.

The pump must be installed such that no water can drip onto
the pump motor and/or the terminal box.

7.1.1 Module position changes

The motor does not need be completely removed from the pump
casing in order to change the position of the regulation module.
The  motor  can  be  rotated  into  the  desired  position  within  the
pump casing, if there is enough space. (Kap. 1 auf S. II)

ATTENTION!

!!

In the event of condensate formation and during cooling applications, the
electrical connection must always be on the right-hand side of the pump
body (“3 o'clock” position).

ATTENTION!

!!

WARNING! Danger of personal injury
The motor screws can only be loosened and the module position
changed when the system is without pressure/empty.

4 M6 hexagon socket screws must be loosened to release the
motor. 

ATTENTION!

!!

CAUTION! Danger of damage to the pump
Excessive application of force on the pump module must be avoided.

ATTENTION!

!!

WARNING! Danger of personal injury
The shaft is inseparably connected to the wheel, the end plate and the
rotor. If the rotor with its strong magnets is not inserted into the motor
casing, there is a high potential for danger e.g. through the sudden
attraction of items made of iron/steel, interference with the operation of
electrical devices (danger to personnel wearing pacemakers), destruction
of magnetic cards etc.

ATTENTION!

!!

WARNING! Danger of personal injury
The regulation module cannot be dismantled. If the regulation module
has been separated from the pump by force, there is danger of personal
injury:
When the pump is in generator operation (with the rotor driven by the
booster pump) a dangerous voltage is present at the motor terminals
which are not protected against accidental contact.
Due to the remaining electrical connection on the regulation module

7.1.2 Insulation of the pump in systems with condensate formation

The UP series is suitable for use in refrigerating, air conditioning
and similar systems where the temperature of the medium to be
pumped  is  as  low  as  2 °C.  Condensate  can  form  on  medium-
bearing components, e.g. pipework or pump casings, if the ambi-
ent temperature is higher than the temperature of the medium to

be pumped. Intermittent pump operation is still permissible even
in these cases.
For use in systems like these, a diffusion-tight insulation must be
fitted  on-site  or  a  cold  insulation  shell  suitable  for  the  relevant
pump size.

Summary of Contents for UP 75-25PK

Page 1: ...UP 75 32PK Montage und Gebrauchsanweisung Installation and Operating Instruction Instruction d installation et d utilisation Umw lzpumpe mitautomatischer Leistungs anpassung Circulating pump with auto...

Page 2: ......

Page 3: ...1 2 Einstellansicht DE 5 6 2 Navigation DE 6 6 3 Einstellmodus DE 6 7 Installation und elektrischer Anschluss DE 7 7 1 Installation DE 7 7 1 1 nderung der Modulposition DE 7 7 1 2 Isolierung der Pump...

Page 4: ...ge haben 2 3 Sicherheitshinweise f r den Betreiber Die bestehenden Vorschriften zur Unfallverh tung sind zu be achten Gef hrdungen durch elektrische Energie sind auszuschlie en Weisungen lokaler oder...

Page 5: ...kwasser Zirkulationssystemen zugelassen sind Pumpen sind nicht zugelassen in reinem Trinkwassersystemen 4 1 F rdermedien Reine d nnfl ssige nicht aggressive und nicht explosive Me dien ohne feste oder...

Page 6: ...rh ltnis zu korrigieren thylen Propylenglykole mit Korrosionsschutzinhibitoren Handels bliche Sauerstoffbindemittel1 Handels bliche Korrosionsschutzmittel1 Handels bliche Kombinationsprodukte1 Handels...

Page 7: ...Die Priorit t ist aus der nachfolgenden Tabelle ersichtlich Liegt kein Alarm mehr an wechselt das Display in den Betriebs status zur ck 6 1 2 Einstellansicht Auf Tastendruck wechselt das Display von d...

Page 8: ...ng ndern der Einstellungen bei der UP 75 25 32 PK Wird die Pumpe eingeschaltet l uft sie zun chst mit der Werks voreinstellung Im Display wird der aktuelle Betriebsstatus ange zeigt 1 Die Taste dr cke...

Page 9: ...er auf den Pumpenmotor bzw Klemmenkasten tropfen kann 7 1 1 nderung der Modulposition Soll das Regelmodul in eine andere Position gebracht werden so braucht der Motor nicht komplett aus dem Pumpengeh...

Page 10: ...Signaleingang gegebenenfalls mit einem Stecker verschlossen der beim Anschluss einer Signalleitung entfernt werden muss ACHTUNG Warnung Gefahr durch Stromschlag Sollte durch Gewalteinwirkung das Kabel...

Page 11: ...glichen Stromwert einzu stellen Die Pumpe darf mit einem RCD Schutzschalter abgesichert werden Kennzeichnung RCD oder Stromart und Spannung des Netzanschlusses m ssen den Angaben auf dem Typenschild e...

Page 12: ...dus 8 2 2 Einstellung der Pumpenleistung durch Signal PWM Bei der Drehzahlverstellung durch PWM Signal wird der f r eine Regelung erforderliche Soll Istwertvergleich von einem exter nen Regler bernomm...

Page 13: ...runreinigungen blockiert Die Verunreinigungen entfernen Die Pumpe vorn an der Elktronikeinheit mithilfe eines Schraubendrehers deblockieren Die Pumpe ist defekt Die Pumpe austauschen Die Pumpe l uft m...

Page 14: ...DE 12 452115 66 53 FD 9712 Deutsch UP 75 25PK UP 75 32PK...

Page 15: ...N 5 6 1 2 Settings view EN 5 6 2 Navigation EN 6 6 3 Settings mode EN 6 7 Installation and electrical connection EN 7 7 1 Installation EN 7 7 1 1 Module position changes EN 7 7 1 2 Insulation of the p...

Page 16: ...Safety notes for the operator Observe the valid accident prevention regulations It must be ensured that there are no risks resulting from electrical energy Instructions resulting from local or general...

Page 17: ...are not approved for use in pure domestic water systems 4 1 Media to be pumped Pure thin liquid non aggressive and non explosive media with no solid or long fibre components and free from admixtures o...

Page 18: ...roportional mixing ratio Ethylene propylene glycols with corrosion protection inhibitor Standard oxygen binder1 Standard anticorrosive1 Standard combination products1 Standard cooling brines1 Permissi...

Page 19: ...Ds indicate the fault with the highest priority The priority is shown in the following table If an alarm is no longer active the display switches back to the operating status 6 1 2 Settings view The d...

Page 20: ...75 25 32 PK If the pump is switched on it initially runs with the factory presets The current operating status is shown in the display 1 Press the key to switch to the settings view The LEDs indi cate...

Page 21: ...ork The pump must be installed such that no water can drip onto the pump motor and or the terminal box 7 1 1 Module position changes The motor does not need be completely removed from the pump casing...

Page 22: ...te the signal input may be sealed with a connector which must be removed when connecting a signal line ATTENTION Warning Danger of electric shock If the cable has been disconnected from the pump by fo...

Page 23: ...e current value The pump can be protected using a RCD circuit breaker Labelling RCD or Current type and voltage of the mains connection must be in accordance with the specifications on the type plate...

Page 24: ...gnal When the speed is adjusted using a PWM signal the setpoint ac tual value comparison required for the regulation is carried out by an external controller A signal PWM is sent to the pumps from the...

Page 25: ...blocked with dirt Remove the dirt Unblock the pump at the front of the electrical unit using a screwdriver The pump is faulty Replace the pump The pump is running at maxi mum speed and the speed can n...

Page 26: ...EN 12 452115 66 53 FD 9712 English UP 75 25PK UP 75 32PK...

Page 27: ...6 1 2 Affichage du mode de r glage FR 5 6 2 Navigation FR 6 6 3 Mode de r glage FR 6 7 Installation et branchements lectriques FR 7 7 1 Installation FR 7 7 1 1 Changement de place du module FR 7 7 1...

Page 28: ...Consignes de s curit l attention de l exploitant Respecter les prescriptions existantes concernant la pr vention des accidents carter tous les risques li s l nergie lectrique Respecter les prescriptio...

Page 29: ...s de circulation d eau potable Les pompes ne sont pas autoris es dans les syst mes r serv s la circulation d eau potable 4 1 Fluides d alimentation Les fluides purs tr s liquides non agressifs et non...

Page 30: ...ne glycol avec inhibiteurs de corrosion Liant d oxyg ne disponible dans le commerce1 Produits anticorrosion disponibles dans le commerce1 Produits de combinaison disponibles dans le commerce1 Eaux gl...

Page 31: ...leau suivant Lorsqu il n y a plus d alarme l cran repasse en mode de ser vice 6 1 2 Affichage du mode de r glage L cran passe de l affichage du mode de r glage celui du mode de service sur pression de...

Page 32: ...rrespondant Profil PWM A chauffage Modification des r glages sur la UP 75 25 32 PK Lorsque la pompe est mise en service elle fonctionne tout d abord avec les pr r glages d usine L cran affiche le mode...

Page 33: ...mpe doit tre l ho rizontale En cas de conditions de montage sp ciales il est possible en tournant le moteur de positionner le module de r glage l horizontale Kap 7 1 1 auf S 7 Monter la pompe dans un...

Page 34: ...chements lectriques ATTENTION AVERTISSEMENT Risque de d charge lectrique Les branchements lectriques doivent tre r alis s par un installateur sp cialis en lectricit autoris par la soci t d lectricit l...

Page 35: ...ourant La pompe peut tre prot g e par un disjoncteur RCD Marquage RCD ou Le type de courant et la tension du branchement secteur doivent correspondre aux donn es de la plaque signal tique Tension de r...

Page 36: ...ignal PWM Lors du r glage de la vitesse via un signal PWM la comparaison requise entre la valeur de consigne et la valeur r elle est prise en charge par un r gulateur externe En guise de grandeur de r...

Page 37: ...r la pompe l avant au niveau de l unit lectronique l aide d un tournevis La pompe est d fectueuse Remplacer la pompe La pompe tourne la vitesse de rotation maximale et la vitesse de rotation ne peut p...

Page 38: ...FR 12 452115 66 53 FD 9712 Fran ais UP 75 25PK UP 75 32PK...

Page 39: ...c curve Courbe caract ristique UP 75 25PK UP 75 32PK A III 3 Stromlaufpl ne Circuit diagrams Sch mas lectriques A IV 3 1 Aderbelegung Pin configuration Brin occupation A IV 3 2 Anschluss Koppelrelais...

Page 40: ...A II 452115 66 53 FD 9712 Anhang Appendix Annexes UP 75 25PK UP 75 32PK 1 Einbaulage Mounting position Emplacement de montage Abb Fig Fig 1 1 IPX4D...

Page 41: ...2 5 3 0 3 5 4 0 PWM 1 Maximum 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 0 0 0 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 1 1 1 max 2 3 0 10 20 30 40 50 60 70 0 0 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 P 1 W Maximum F rderh...

Page 42: ...age ACHTUNG Je nach W rmepumpentyp wird der Pumpendraht direkt am W rmepumpenmanager oder auf der daf r vorgesehenen 3 Stockklemme aufgelegt ATTENTION The pump wire is either placed directly on the he...

Page 43: ...sch mas lectriques Jx Stecker von Nx Plug from Nx Connecteur de Nx K5 Sch tz Prim rpumpe Contactor primary pump Contacteur pompe primaire KMx Koppelrelais Pumpe Pump coupling relay Relais de couplage...

Page 44: ...ales service addres ses please refer to the Installation and Operating Instructions for Heat Pumps Pour les conditions de garantie et les adresses SAV se r f rer aux instructions de montage et d tilis...

Reviews: