452115.66.53 · FD 9712
EN-3
UP 75-25PK - UP 75-32PK
English
4 Intended use
This device must not be operated by persons (including children)
with limited physical, sensory or mental abilities or lacking the
necessary experience and/or knowledge.
Children must be supervised to ensure that they do not play with
the device.
These high-efficiency pumps from the series are intended for the
circulation of liquids (no oils, liquids containing oil, no foodstuff)
in:
Domestic hot water heating systems
Air conditioning, cooling and cold water circuits
Heat pumps, brine circuits up to +2 °C
Closed industrial circulating systems
Approved media to be pumped are heating water in accordance
with VDI 2035, water/glycol mixtures in a ratio of 1:1.
When glycol is added, the output data of the pump must be ad-
justed based on the higher viscosity.
ATTENTION!
!!
Danger of damage to health!
The materials used in the series can cause damage to health as they are
not approved for use in domestic water circulating systems.
Pumps are not approved for use in pure domestic water systems.
4.1 Media to be pumped
Pure, thin liquid, non-aggressive and non-explosive media with
no solid or long fibre components and free from admixtures of
mineral oils.
In heating systems, the water should fulfil the requirements of
current valid standards, which apply for the water quality in heat-
ing systems (e.g. VDI 2035).
ATTENTION!
!!
The pump must not be used to convey inflammable media, such as diesel
oil and petrol.
5 Information on the product
5.1 Model code
Tab. 5.1:
5.2 Technical data
Example: UP 75-25PK
UP
=
High efficiency pump
=
Electronically regulated
25
=
Screw connection
25 C (Rp 1½“), 30 (Rp 2“)
70
=
max. delivery height in (dm)
PK
=
P = PWM input signal
K = constant controller
Max. discharge rate
Depends on the pump type, see characteristic curve
Max. delivery height
Depends on the pump type, see characteristic curve
Line voltage
1~230 V ±10 % according to DIN IEC 60038
Nominal current
See type plate
Frequency
50/60 Hz
Insulation class
F
Degree of protection
IP X4D
Power consumption P1
See type plate
Nominal widths
siehe Kap. 5.1 Model code
Connecting flange
siehe Kap. 5.1 Model code
Permissible
ambient temperature
Tab. 5.2 auf S. 4
Max. relative humidity
*
95 %