www.glendimplex.de
452172.66.01-EN · FD 0204
EN-27
LIA 0608HWCF M - LIA 0911HWCF M English
9.5 Characteristic curve
temperature sensor indoor unit
9.5.1 Sensor characteristic curves
The temperature sensors to be connected to the heat pump
manager must correspond to the sensor characteristic curve il-
lustrated in Fig. 9.1 on page 27. The only exception is the out-
side temperature sensor included in the scope of supply of the
heat pump (see Fig. 9.2 on page 27)
Fig. 9.1: Sensor characteristic curve NTC-10
Fig. 9.2: Sensor characteristic curve NTC-2 according to DIN 44574 Out-
side temperature sensor
9.5.2 Mounting the outside temperature
sensor
The outside temperature is measured via the heat source inlet
sensor on the outdoor unit. Optionally, a separate outdoor tem-
perature sensor can be mounted.
The temperature sensor must be mounted in such a way that all
weather conditions are taken into consideration and the meas-
ured value is not falsified.
Install on the external wall of a heated room, if possible on the
north or north-west side of the building
Do not install in a "sheltered position" (e.g. in a wall niche or
under a balcony)
Not in the vicinity of windows, doors, exhaust air vents, ex-
ternal lighting or heat pumps
Not to be exposed to direct sunlight at any time of year
-
Temperature in °C
-20
-15
-10
-5
0
5
10
NTC-2 in k
14.6
11.4
8.9
7.1
5.6
4.5
3.7
NTC-10 in k
67.7
53.4
42.3
33.9
27.3
22.1
18.0
5
20
25
30
35
40
45
50
55
60
2.9
2.4
2.0
1.7
1.4
1.1
1.0
0.8
0.7
0.6
14.9
12.1
10.0
8.4
7.0
5.9
5.0
4.2
3.6
3.1
0
10
20
30
40
50
60
70
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
External temperature in [°C]
Resistance value in
[kOhm]
0
2
4
6
8
10
12
14
16
18
20
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
External temperature in [°C]
Resistance value in
[kOhm]
Dimensioning parameters sensor cable
Conductor material
Cu
Cable length
50 m
Ambient temperature
35 °C
Routing type
B2 (DIN VDE 0298-4 /
IEC 60364-5-52)
External diameter
4-8 mm