www.dimplex.de 452162.66.14 · FD 9607
EN-19
English
LAK 6IMR-TP - LAK 14ITR-TP
8
Additional model features
8.1
Type of defrosting
Reverse circulation
Reverse circulation
Reverse circulation
8.2
Condensate tray frost protection /
Water in device is protected from freezing
9
No / Yes
No / Yes
Yes/ Yes
8.3
Max. operating overpressure (heat source/heat sink)
bar
3.0
3.0
3.0
9
Heat output / coefficients of performance (COP)
9.1
Heat output / COP
EN 14511
EN 14511
EN 14511
at A-7 / W35
kW / ---
10
4.2 / 2.8
6.3 / 2.4
13.9 / 2.9
kW / ---
4.2 / 2.8
6.3 / 2.4
13.9 / 2.9
at A2 / W35
kW / ---
4.8 / 3.4
5.3 / 3.6
10.5 / 3.6
kW / ---
4.8 / 3.4
6.2 / 3.2
11.0 / 3.2
at A7 / W35
kW / ---
5.6 / 4.8
5.6 / 4.8
10.6 / 4.1
kW / ---
5.6 / 4.8
9.0 / 4.3
14.7 / 4.3
at A7 / W45
kW / ---
5.4 / 3.4
5.4 / 3.4
9.8 / 3.7
kW / ---
5.4 / 3.4
8.3 / 3.3
13.9 / 3.3
at A10 / W35
kW / ---
6.0 / 5.1
6.0 / 5.1
11.3 / 4.5
kW / ---
6.0 / 5.1
9.6 / 4.5
15.7 / 4.3
9.2
Cooling capacity / COP
at A27 / W7
kW / ---
6.5 / 3.3
6.5 / 3.3
12.9 / 3.0
at A27 / W18
kW / ---
8.7 / 4.2
8.7 / 4.2
17.1 / 3.7
at A35 / W7
kW / ---
6.2 / 2.6
6.2 / 2.6
12.3 / 2.5
at A35 / W18
kW / ---
9.0 / 3.4
9.0 / 3.4
15.5 / 3.3
1. The specified sound levels apply if the supporting feet (available as an option) are not used. If the supporting feet are used, the level can increase by up to 3 dB (A).
2. The specified sound pressure level corresponds to the operating noise of the heat pump in heating operation at 35°C flow temperature.
The specified sound pressure level is the free sound area level. The measured value can deviate by up to 16 dB(A) depending on the installation location.
3. Please note that additional space is required for pipe connections, operation and maintenance.
4. Factory default 6 kW
5. These data indicate the size and capacity of the system according to EN 14511. For an analysis of the economic and energy efficiency of the system, the bivalence point and the
regulation should be taken into consideration. These figures are only achieved with clean heat exchangers. Instructions for care, commissioning and operation can be found in
the relevant sections of the installation and operation instructions. The specified values have the following meaning, e.g. A7 / W35: Heat source temperature 7 °C and heating
water flow temperature 35 °C.
6. Maximum heating/cooling output
7. Max. intake incl. pipe heating and immersion heater (state of supply)
8. See CE declaration of conformity
9. The heat circulating pump and the heat pump controller must always be ready for operation.
10.COP-optimised operation
Summary of Contents for LAK 14ITR-TP
Page 2: ......
Page 22: ...TR 20 452162 66 14 FD 9607 www dimplex de Türkçe LAK 6IMR TP LAK 14ITR TP ...
Page 42: ...EN 20 452162 66 14 FD 9607 www dimplex de English LAK 6IMR TP LAK 14ITR TP ...
Page 62: ...PL 20 452162 66 14 FD 9607 www dimplex de Polski LAK 6IMR TP LAK 14ITR TP ...
Page 79: ...www dimplex de 452162 66 14 FD 9607 A XVII Ek Appendix Załącznik LAK 6IMR TP LAK 14ITR TP ...