7.3.3 Mounting the external temperature 

sensor

The temperature sensor must be mounted in such a way that all
weather conditions are taken into consideration and the meas-
ured value is not falsified.

Mount on the external wall on the north or north-west side
where possible

Do not install in a “sheltered position” (e.g. in a wall niche or
under a balcony)

Not in the vicinity of windows, doors, exhaust air vents, ex-
ternal lighting or heat pumps

Not to be exposed to direct sunlight at any time of year

Sensor  lead:

  Max.  length  40 m;  min.  core  cross-section

0.75 mm²; external diameter of the cable 4-8 mm.

7.3.4 Installing the strap-on sensor

It is only necessary to mount the strap-on sensors if they are in-
cluded in the scope of supply of the heat pump but have not yet
been installed. 
The strap-on sensors can be fitted as pipe-mounted sensors or
installed in the immersion sleeve of the compact manifold.
Mounting as a pipe-mounted sensor

Remove paint, rust and scale from heating pipe.

Coat  the  cleaned  surface  with  heat  transfer  compound
(apply sparingly).

Attach the sensor with a hose clip (tighten firmly, as loose
sensors can cause malfunctions) and thermally insulate.

7.3.5 Hydraulic distribution system

The  compact  manifold  and  the  dual  differential  pressureless
manifold  function  as  an  interface  between  the  heat  pump,  the
heating distribution system, the buffer tank and, in some cases,
even the hot water cylinder. A compact system is used to simplify
the installation process, so that a lot of different components do
not have to be installed individually. Further information can be
found in the relevant installation instructions.

Compact manifold

The return sensor can remain in the heat pump, or should be in-
stalled in the immersion sleeve. The remaining empty space be-
tween the sensor and the immersion sleeve must be filled com-
pletely with heat transfer compound.

7.4 Electrical connection

The power supply and control voltage are supplied using stand-
ard cables (load: 3~ 5-core / 1~ 3-core; control 3-core).
For detailed instructions on how to connect the external compo-
nents and how the heat pump manager functions, please refer to
the device electrical documentation.
An  all-pole  disconnecting  device  with  a  contact  gap  of  at  least
3 mm (e.g. utility blocking contactor or power contactor) and an
all-pole circuit breaker with common tripping for all external con-
ductors must be installed in the power supply for the hydro tower
(tripping current in compliance with the device information). 
The (L/N/PE~230 V, 50 Hz) supply cable for the heat pump man-
ager must have a constant voltage. For this reason, it should be
tapped  upstream  from  the  utility  blocking  contactor  or  be  con-
nected  to  the  household  current,  as  important  protection  func-
tions could otherwise be lost during a utility block.
The  correct  control  voltage  must  be  ensured  according  to  the
general information leaflet.
The pipe heater (2nd heat generator) must only be connected by
authorised electricians according to the corresponding circuit di-
agram.  Regulations  of  the  utility  company  and  national  guide-
lines must be observed (VDE).
A cable duct is integrated into the polyurethane foam at the top
of  the  cylinder  (under  the  upper  covering  cap)  which  makes  it
possible to lay the electrical cables under the upper cover (from
the rear of the cylinder to the front/connection side).

NOTE

To use the HWK 230 Econ5S, two connecting cables (< 25 V / 230 V) must
be routed between the heat pump managr and the heat pump.

NOTE

Further information on the wiring of the heat pump manager is available
in the electrical documentation.

ATTENTION!

The communication cable is necessary for the function of air-to-water
heat pumps in outdoor installation. It must be shielded and laid
separately from the mains cables. It is connected to N1-J25.  For further
information, see electrical documentation

+RVHFOLS

6WUDSRQVHQVRU

7KHUPDOLQVXODWLRQ

Summary of Contents for HWK 230 Econ5S

Page 1: ...6 15 DE EN FR FD 9701 HWK 230 Econ5S Montage und Gebrauchsanweisung Installation and Operating Instruction Instruction d installation et d utilisation Hydro Tower mit WPM Hydro tower with HPM Tour hyd...

Page 2: ......

Page 3: ...E 5 6 1 Allgemein DE 5 6 2 Schall DE 5 7 Montage DE 5 7 1 Allgemein DE 5 7 2 Heizungsseitiger Anschluss DE 6 7 3 Temperaturf hler DE 6 7 4 Elektrischer Anschluss DE 7 8 Inbetriebnahme DE 8 8 1 Allgeme...

Page 4: ...R cklauftemperatur im W rmepum penmanager eingestellt werden Die Position des Temperatur f hlers ist hierbei zu beachten 1 2 Gesetzliche Vorschriften und Richtlinien Diese W rmepumpe ist gem Artikel 1...

Page 5: ...onenten Pufferspeicher 60 Liter Ungemischter Heizkreis mit berstr mventil Prim rkreis W rmeerzeugung incl Umw lzpumpe Absper rungen und Umschaltventil zur Brauchwasserbereitung 2 W rmeerzeuger elektri...

Page 6: ...Netzwerk eines Geb u deleitsystems angeschlossen werden F r den genauen An schluss und die Parametrierung der Schnittstelle muss die erg nzende Montageanweisung der Schnittstellenkarte beachtet werde...

Page 7: ...in einem Obergeschoss ist die Tragf higkeit der Decke zu pr fen und aus akustischen Gr nden die Schwingungsentkoppelung sehr sorgf ltig zu planen Eine Aufstellung auf einer Holzdecke ist abzulehnen 6...

Page 8: ...ef hrt werden Es ist m glich einen zweiten oder dritten Heizkreis anzuschlie en Zubeh rartikel Verteilerbalken VTB Die Installation der Heizkreise erfolgt dann bauseits au erhalb des HWK mit Heizungsu...

Page 9: ...dig ausgef llt sein 7 4 Elektrischer Anschluss Leistungsversorgung und Steuerspannung werden ber han dels bliche Leitungen zugef hrt Last 3 5 adrig 1 3 adrig Steuerung 3 adrig Genaue Anweisungen ber d...

Page 10: ...falls h ufiger gereinigt wer den muss mit einer 5 igen Ameisens ure durchzuf hren In beiden F llen sollte die Reinigungsfl ssigkeit Raumtempera tur haben Es ist empfehlenswert den W rmetauscher entgeg...

Page 11: ...Ger teabmessungen1 H x B x L mm 1 Beachten Sie dass der Platzbedarf f r Rohranschluss Bedienung und Wartung gr er ist 1920 x 740 x 950 4 2 Kippma mm 2000 4 3 Ger teanschl sse f r W rmeerzeuger Zoll 1...

Page 12: ...DE 10 452162 66 15 FD 9701 Deutsch HWK 230 Econ5S...

Page 13: ...EN 5 6 1 General EN 5 6 2 Sound EN 5 7 Assembly EN 5 7 1 General EN 5 7 2 Heating system connection EN 6 7 3 Temperature sensor EN 6 7 4 Electrical connection EN 7 8 Start up EN 8 8 1 General EN 8 8 2...

Page 14: ...system a sensible value for the maximum flow and return temperature should be set on the heat pump manager The position of the temperature sensor is important in this regard 1 2 Legal regulations and...

Page 15: ...ents Buffer tank 60 litres Unmixed heating circuit with overflow valve Primary circuit of heat generation including circulating pump shut offs and reversing valve for domestic water preparation 2nd he...

Page 16: ...network via supplementation of the relevant in terface plug in card The supplementary installation instructions of the interface card must be consulted regarding the exact con nection and parameterisa...

Page 17: ...should be checked On account of the acoustics measures for isolating possible vibrations should also be very carefully planned Installation on floors above wooden ceilings is not recommended 6 2 Soun...

Page 18: ...r VTB The heating circuits are then installed on site outside of the HWK with heat circulating pump M13 M15 NOTE If the pipes are more than 10 m long the free compression values stated in the device i...

Page 19: ...must be filled com pletely with heat transfer compound 7 4 Electrical connection The power supply and control voltage are supplied using stand ard cables load 3 5 core 1 3 core control 3 core For deta...

Page 20: ...purposes However if cleaning needs to be performed more frequently a 5 formic acid solu tion should be used In either case the cleaning fluid should be at room temperature We recommend flushing the he...

Page 21: ...s 1 H x W x L mm 1 Note that additional space is required for pipe connections operation and maintenance 1920 x 740 x 950 4 2 Tilting dimension mm 2000 4 3 Device connections for heat generator inches...

Page 22: ...EN 10 452162 66 15 FD 9701 English HWK 230 Econ5S...

Page 23: ...ation FR 5 6 1 G n ralit s FR 5 6 2 Bruit FR 5 7 Montage FR 5 7 1 G n ralit s FR 5 7 2 Raccordement c t chauffage FR 6 7 3 Sonde de temp rature FR 6 7 4 Branchements lectriques FR 8 8 Mise en service...

Page 24: ...raisonnable pour les circuits de d part et de retour Pour cela il faut respecter l emplacement de la sonde de temp rature 1 2 Dispositions l gales et directives Cette pompe chaleur est con ue pour un...

Page 25: ...it de chauffage non m lang avec soupape diff ren tielle Circuit primaire production de chaleur y compris circulateur dispositifs d arr t et vanne d inversion pour la production d eau non potable 2 me...

Page 26: ...syst me de contr le commande des b timents gr ce la carte d interface respective Pour le raccordement pr cis et le param trage de l interface respecter les instructions de mon tage suppl mentaires de...

Page 27: ...e au poids du plafond et le d couplage vi bratoire pour des raisons acoustiques Une installation sur un plancher en bois ne peut tre accept e 6 2 Bruit Afin d emp cher toute transmission des bruits de...

Page 28: ...ur circuit de chauffage avant l int gration dans la tour hydraulique combin e HWK Ce dispositif d arr t doit emp cher toute perte importante d eau de chauffage en cas de change ment ventuellement n ce...

Page 29: ...s d applique peuvent tre mont es sur les tuyauteries ou ins r es dans le doigt de gant du distributeur compact Montage sur les tuyauteries Nettoyer les tuyaux de chauffage des restes de peinture li mi...

Page 30: ...uis la face arri re du ballon la zone de raccordement l avant REMARQUE Deux c bles de raccordement 25 V 230 V doivent tre raccord s pour HWK 230 Econ5S entre le gestionnaire de pompe chaleur et la pom...

Page 31: ...suite soigneusement rincer les tuyauteries l aide de produits neutralisants ad quats afin d viter tous dommages pro voqu s par d ventuels restes de d tergents dans le syst me Les acides doivent tre ut...

Page 32: ...mm 2 Tenir compte de la place n cessaire plus importante pour le raccordement des tuyaux la commande et l entretien 1920 x 740 x 950 4 2 Hauteur appareil bascul mm 2000 4 3 Raccordements du g n rateur...

Page 33: ...einem Heizkreis Puffer und Warmwasserspeicher Mono energy heat pump heating system with one heating circuit buffer tank and hot water cylinder Installation de chauffage par pompe chaleur mono nerg tiq...

Page 34: ...A II 452162 66 15 FD 9701 Anhang Appendix Annexes HWK 230 Econ5S 1 Ma bilder Dimension Drawings Sch mas cot s 1 1 Ma bild Dimension Drawing Sch mas cot...

Page 35: ...nt lectrique 7 F ll und Entleerungshahn mit Schlaucht lle Filling and drain cock with hose nozzle Robinet de remplissage et de purge avec embout de flexible 8 Kaltwasser Zulauf R 1 AG Cold water suppl...

Page 36: ...es Courbes caract ristiques t W W 3XPSHQ HUlWHNHQQOLQLH HL NUHLV 3XPS GHYLFH FKDUDFWHULVWLF FXUYH KHDWLQJ FLUFXLW RXUEH FDUDFWpULVWLTXH GH OD SRPSH GH O DSSDUHLO FLUFXLW GH FKDXIIDJH UGHUK KH LQ P HOL...

Page 37: ...rauliques 3 1 Monoenergetische W rmepumpenheizungsanlage mit einem Heizkreis Puffer und Warmwasserspeicher Mono energy heat pump heating system with one heating circuit buffer tank and hot water cylin...

Page 38: ...pumpenheizungsanlage mit einem Heizkreis Puffer und Warmwasserspeicher Electical circuit diagram for a mono energy system with one heating circuits buffer tank and hot water cylinder Sch ma lectrique...

Page 39: ...rr t avec coulement Sicherheitsventilkombination Safety valve combination Groupe de valves de s curit W rmeverbraucher Heat consumer Consommateur de chaleur Temperaturf hler Temperature sensor Sonde d...

Page 40: ...sales service addres ses please refer to the Installation and Operating Instructions for Heat Pumps Pour les conditions de garantie et les adresses SAV se r f rer aux instructions de montage et d tili...

Reviews: