background image

EN-2

English

1

1 Please read 

immediately

1.1 Important information

ATTENTION!

The device is not suitable for operation with a frequency converter.

ATTENTION!

The hydraulic tower and transport pallet are only connected by the
packing film.

ATTENTION!

Never use cleaning agents containing sand, soda, acid or chloride as
these can damage the surfaces.

ATTENTION !

Before opening the device, ensure that all circuits are isolated from the
power supply.

ATTENTION!

Any work on the system may only be performed by authorised and
qualified after-sales service technicians.

The operational reliability of the safety valve should be checked
at regular intervals. We recommend having an annual service in-
spection carried out by a qualified specialist company.
The drainage of the safety valve should visibly flow into a waster
water drain.
The installer of the heating system is responsible for checking
whether an additional expansion vessel is required.
Smart operation provides significant energy savings. The heating
water temperature should be as low as required during heat
pump operation. The planner of the heating system is responsi-
ble for the definition of the system temperature.
When installing an underfloor heating system, a sensible value
for the max. flow and return temperature should be set in the heat
pump controller. The position of the temperature sensor is impor-
tant in this regard.

1.2 Legal Regulations and 

Directives

The construction and design of the hydraulic tower complies with
all relevant EU directives, DIN and VDE regulations (see CE de-
claration of conformity).
When connecting the hydraulic tower to the power supply, the
relevant VDE, EN and IEC standards are to be fulfilled. Any fur-
ther connection requirements stipulated by the network opera-
tors must also be observed.
When connecting the heating system, all applicable regulations
must also be adhered to.
Persons, especially children, who are not capable of operating
the device safely due to their physical, sensory or mental abilities
or their inexperience or lack of knowledge, must not operate this
device without supervision or instruction by the person in charge.
Children must be supervised to ensure that they do not play with
the device.

2 Intended use of the 

hydraulic tower

2.1 Application

The hydraulic tower constitutes the interface between a non-re-
versible air-to-water heat pump set up outside and the heating
system in the building. The HPK200S contains all hydraulic com-
ponents required between heat generation and heat distribution
with an unmixed heating circuit. A mixed heating circuit in time-
saving modular design can be subsequently integrated as an ex-
tension. A dual differential pressureless manifold with a buffer
tank yields an energetically optimal hydraulic integration of the
heat generator and the heat consumers. The required heat pump
manager is included. There is the option to combine the
HPK200S with a tank (identical design) to heat domestic hot wa-
ter.

ATTENTION!

The device is not suitable for operation with a frequency converter.

2.2 General properties

„

Low installation effort

„

Easy accessibility of all components

„

No lateral minimum distance required

„

Ready-to-connect, contains all essential components via
pumps, shut-offs, safety technology and heat pump control-
ler

„

Combination of panel heating and radiator heating possible
(special accessories required)

„

Integrated buffer storage reduces contact cycles of the heat
pump - this increases the efficiency of the system

„

The infinitely adjustable operation of the circulating pump in
the heating circuit permits demand-dependent output adjust-
ment.

2.3 Expansion options

„

Optional mixed heating circuit incl. controlled circulating
pump (infinitely adjustable or 3 stages), shut-offs and back-
pressure feature.

„

optional immersion heater up to 6 kW

„

Optional hot water charge circuit, shut-offs and pump
adapter included

The flow direction must be borne in
mind when installing the hot water
heat pump.
Circulation must take place from
bottom to top. The fitter is perso-
nally responsible for carrying out
the electrical connection and the
alignment of the motor block.
Ball valves must be opened after in-
stallation.

Summary of Contents for HPK 200S

Page 1: ...tower with HPM Tour hydraulique avec gestionnaire WPM Montage und Gebrauchsanweisung Deutsch English Fran ais Instructions d installation et d utilisation Installation and Operating Instructions Beste...

Page 2: ......

Page 3: ...t DE 3 3 2 Schaltkasten DE 3 3 3 W rmepumpenregler DE 3 4 Transport DE 3 5 Aufstellung DE 4 5 1 Allgemein DE 4 5 2 Schall DE 4 6 Montage DE 4 6 1 Allgemein DE 4 6 2 Heizungsseitiger Anschluss DE 4 6 3...

Page 4: ...sicher zu benutzen sollten dieses Ger t nicht ohne Aufsicht oder Anwei sung durch eine verantwortliche Person benutzen Kinder sollten beaufsichtigt werden um sicherzustellen dass sie nicht mit dem Ge...

Page 5: ...und kann durch L sen der beiden oben liegenden Befestigungsschrauben her ausgeklappt werden Im Schaltkasten befinden sich die Netzanschlussklemmen Hei zungssch tze Nabelschnuranschl sse Verbindungslei...

Page 6: ...schluss Die heizungsseitigen Anschl sse am Hydrauliktower sind mit 1 1 4 Au engewinde versehen Beim Anschluss muss an den berg ngen mit einem Schl ssel gegengehalten werden Bevor die heizwasserseitige...

Page 7: ...ler Die Einstellungen m ssen gem dessen An leitung vollzogen werden Die auf dem Typschild angegebenen Betriebs berdr cke d rfen nicht berschritten werden St rungen w hrend des Betriebes werden ebenfal...

Page 8: ...managers nach Wenn die St rung nicht selbst behoben werden kann verst ndigen Sie bitte den zust ndigen Kundendienst ACHTUNG Arbeiten an der Anlage d rfen nur vom autorisierten und sachkundigen Kunden...

Page 9: ...sprechdruck Sicherheitsventil bar 2 5 3 6 maximaler Betriebs berdruck bar 2 0 3 7 maximale Betriebstemperatur C 85 3 8 elektrische Rohrheizung kW 2 4 bzw 6 Tauchheizk rper kW bis 6 optional 3 9 Schall...

Page 10: ...DE 8 Deutsch 11...

Page 11: ...EN 3 3 2 Switch box EN 3 3 3 Heat pump controller EN 3 4 Transport EN 3 5 Set up EN 4 5 1 General EN 4 5 2 Sound EN 4 6 Installation EN 4 6 1 General EN 4 6 2 Heating System Connection EN 4 6 3 Electr...

Page 12: ...y or mental abilities or their inexperience or lack of knowledge must not operate this device without supervision or instruction by the person in charge Children must be supervised to ensure that they...

Page 13: ...osening the two top mounting screws it can be folded open The switch box contains the supply connection terminals heating contactors umbilical cable connections connecting line to the heat pump and th...

Page 14: ...start up must be carried out by a qualified specialist com pany The entire system including all factory assembled compo nents should be inspected to ensure that everything is working properly and that...

Page 15: ...als are used Residue from lubricants and sealants may also contaminate the heating water In the case of severe contamination leading to a reduction in the performance of the liquefier in the heat pump...

Page 16: ...ssure safety valve bar 2 5 3 6 max operating overpressure bar 2 0 3 7 max operating temperature C 85 3 8 electrical pipe heater kW 2 4 or 6 Immersion heater kW up to 6 optional 3 9 Sound power level d...

Page 17: ...FR 3 3 3 R gulateur de pompe chaleur FR 3 4 Transport FR 3 5 Installation FR 3 5 1 G n ralit s FR 3 5 2 Bruit FR 4 6 Montage FR 4 6 1 G n ralit s FR 4 6 2 Raccordement c t chauffage FR 4 6 3 Branchem...

Page 18: ...connaissances ne sont pas en mesure d utiliser l appareil en toute s curit ne devraient pas le faire en l absence ou sans instructions d une personne responsable Les enfants doivent tre surveill s pou...

Page 19: ...facile utiliser Il commande et surveille toute l installation de chauffage en fonction de la temp rature ext rieure ainsi que la production d eau chaude sanitaire et les dispositifs de s curit La son...

Page 20: ...ion diff rentielle Protection antigel Dans le cas de pompes chaleur expos es au gel il convient de pr voir ventuellement une vidange manuelle La fonction de protection antigel du r gulateur est activ...

Page 21: ...chauffage peut galement tre souill e par des r sidus de produits de lubrification et d tanch ification Si l encrassement est si fort que la puissance du condenseur de la pompe chaleur s en trouve r du...

Page 22: ...Surpression de service maximale bars 2 0 3 7 Temp rature de service maximale C 85 3 8 Chauffage tubes lectrique kW 2 4 ou 6 R sistance immerg e kW max 6 en option 3 9 Niveau de puissance sonore dB A 3...

Page 23: ...Anschlussplan Last Circuit diagram load Sch ma lectrique de charge A VII 3 5 Legende Legend L gende A VIII 4 Hydraulische Prinzipschemen Hydraulic Plumbing Diagrams Sch mas hydrauliques A X 4 1 Hydra...

Page 24: ...HU IORZ H WHUQDO WKUHDG RW ZDWHU UHWXUQ IORZ H WHUQDO WKUHDG OHFWULFDO FRQQHFWLRQ HDW UHWXUQ IORZ QSXW LQ 3 6 H WHUQDO WKUHDG HDW IORZ 2XWOHW IURP 3 6 H WHUQDO WKUHDG GGLWLRQDO FRQQHFWLRQ RI DQ H SDQV...

Page 25: ...HVW pTXLSp G XQH DGDSWDWLRQ pOHFWURQLTXH FRQWLQXH GX UHIRXOHPHQW UGHUK KH LQ P HOLYHU KHLJKW LQ P 5HIRXOHPHQW HQ P HL ZDVVHUGXUFKIOXVV LQ P K HDWLQJ ZDWHU IORZ UDWH LQ P K pELW G HDX GH FKDXIIDJH HQ P...

Page 26: ...pendix Annexes 3 3 Stromlaufpl ne Circuit Diagrams Sch mas lectriques 3 1 Steuerung Control Commande 7 9 9 12 12 12 5 7 5 7 1 1 95 9 WHUP 9 1 1 12 12 12 12 1 12 12 12 12 1 12 1 12 1 1 1 5 G 1 0 1 1 3...

Page 27: ...A V Anhang Appendix Annexes 3 2 3 2 Last Load Charge...

Page 28: ...rcuit diagram control Sch ma lectrique de commande 7 3 9 9 12 12 12 5 7 5 7 1 1 95 9 WHUP 9 1 1 12 12 12 12 1 12 12 12 12 1 12 1 12 1 1 1 5 G G 5 5 G G 5 7 7 1 0 0 0 0 1 5 G 1 3 1 3 9 7U 7U 0 1 7 7 1...

Page 29: ...A VII Anhang Appendix Annexes 3 4 3 4 Anschlussplan Last Circuit diagram load Sch ma lectrique de charge...

Page 30: ...50 Hz J2 Anschluss f r Warmwasser R cklauf und Aus senf hler Connection for hot water sensor return flow sensor and external sensor Connexion des sondes sur circuit d eau chaude sanitaire sur circuit...

Page 31: ...erheitstrenntransformator 230 24 VAC 28VA Safety isolating transformer 230 24 V AC 28 VA Transformateur sectionneur de s curit 230 24 V AC 28 VA W1 Steuerleitung 15polig Control line 15 pole Ligne de...

Page 32: ...4 Hydraulische Prinzipschemen Hydraulic Plumbing Diagrams Sch mas hydrauliques 4 1 Hydrauliktower monoenergetische Betriebsweise Hydraulic tower mono energy operating mode Tour hydraulique en mode mon...

Page 33: ...ng und gemischtem Heizkreis Hydraulic tower bivalent operating mode optionally with DHW preparation and mixed heating circuit Tour hydraulique en mode bivalent en option avec production d eau chaude s...