System Installation
Digitize Inc.
8
700271-0001 Rev. G 05/13
8.
Apply 120 VAC power to the DET-16 step down transformer. Then connect the 12 VDC
battery for back up.
9.
Call the alarm receiving location and request a test of the box.
10.
Activate each input in the same manner that the fire system would. Be sure that the code
for the desired input is actually received at the alarm receiving location.
11.
When the testing is complete, close and lock the front door of the cabinet.
12.
Most locations like to know which zones activate which input. This can be accomplished
by listing them inside the front door.
DET-16 with Display Door Open