DigitAx User Guide
Issue code: dgxu4
11-6
b3
Alarm reset
R–W
0 or 1
Def
.
val.
0
Res.
Set
b3
at 1 to accept and cancel any alarm or trip,
and reset the last alarm store
.
Display will show
rSt
during reset
.
Refer to
Pr98
.
Note
Set b2 at 0 or apply 0V to terminal B14 to
disable the Drive before resetting the
alarm.
b4
Drive enable status
RO
Def
.
val.
Res.
b4
= 0 indicates the Drive is disabled (by
b2
= 0, an
alarm, or the Drive enable signal being removed
from terminal B14).
b4
= 1 indicates the Drive is enabled.
b5
Recall default values from PROM
R–W
0 or 1
Def
.
val.
0
Res.
Recalls the default values of all parameters from
PROM
and enters them in
RAM
for immediate
application
. The d
isplay shows
dEf
while default
values are loaded. Related to
b1
and
b99
.
b6
Reference selector
R–W
0 or 1
Def
.
val.
0
Res.
Refer to
b8
.
When
b6
= 0, the reference is the speed loop
output.
When
b6
= 1, analog or digital current reference
selected.
Warning
Change the value of b6 only
when the Drive is disabled by
setting b2 at 0, and the
motor is stopped
b7
Enable accel/decel ramps
R–W
0 or 1
Def
.
val.
0
Res.
Change speed with or without ramps.
When
b7
= 0, ramps are disabled.
When
b7
= 1, ramps are enabled.
b8
Current reference mode
selector
R–W
0 or 1
Def
.
val.
0
Res.
When
b8
= 0, analog torque reference is selected.
When
b8
= 1, digital torque reference is selected
(see
Pr8
).
b9
Digital stop function status
RO
Def
.
val.
Res.
Indicates the logic level present on terminal B6.
When the input at terminal B6 is 0V selection is by
software only
.
Refer to
b18
.
When the input at terminal B6 is +24V, and
b53
= 1,
the stop function is to stop in position.
If the input at terminal B6 is +24V,
b53
= 0, and
b22
= 0,
b9
= 0, the stop function is to hold zero
speed without ramps.
When the input at terminal B6 is +24V,
b53
= 0, and
b22
= 1,
b9
= 1, the stop function is to hold zero
speed with ramps
.
Refer to
b18
.
b10
Digital enable state
RO
Def
.
val.
Res.
Indicates the logic input state at terminal B14.
When the logic state at B14 is 0,
b10
is 0 and the
Drive is not enabled.
When the logic state at B14 is 1,
b10
is 1 and the
Drive is enabled depending on the setting of
b2
.
b11
Current limit selector
R–W
0 or 1
Def
.
val.
0
Res.
Selects the current limit.
When
b11
is set at 0, the current limit is I
max
When
b11
is set at 1, the current limit is determined
by the signal applied to terminal B1.
b12
Analog Output Selector
R–W
Def
.
val.
0
Res.
Refer to
b13
.
Selects the analog signal output produced at
terminal B16.
When
b12
is set at 0, refer to
b13
.
When
b12
is set at 1, the output signal represents
the motor current
(16V pk-pk
≡
I
peak
).
Summary of Contents for DBE1100S
Page 3: ...User Guide DigitAx AC Servo Drive 1 4kW to 22kW Part Number 0415 0008 Issue Number 4...
Page 8: ...DigitAx User Guide Issue code dgxu4 iv...
Page 20: ...DigitAx User Guide Issue code dgxu4 3 8...
Page 28: ...DigitAx User Guide Issue code dgxu4 4 8...
Page 48: ...DigitAx User Guide Issue code dgxu4 5 20...
Page 50: ...DigitAx User Guide Issue code dgxu4 6 2...
Page 54: ...DigitAx User Guide Issue code dgxu4 8 2...
Page 56: ...DigitAx User Guide Issue code dgxu4 9 2...