21
Heating Stage 2 Off Threshold
Set the delta from the setpoint where stage two heating stops.
Stage two turns off at setpoint plus stage 2 delta. Range
is 0 ° to 6 °. Default is
0
°.
Aux Heat On Threshold
Set the delta from the setpoint where stage three heating
starts. Range is 3 ° to 8 °. Default is
3
°.
Aux Heat Off Threshold
Set the delta from the setpoint where stage three heating
stops. Stage three turns off at setpoint plus stage 3 delta.
Range is 0 ° to 7 °. Default is
0
°.
Cooling Stage 1 On Threshold
Set the delta from the setpoint where stage one cooling starts.
Range is 1 ° to 7 °. Default is
1
°.
Cooling Stage 1 Off Threshold
Set the delta from the setpoint where stage one cooling stops.
Stage one turns off at setpoint minus stage 1 delta. Range
is 0 ° to 6 °. Default is
0
°.
HEATING STAGE 2
OFF THRESHOLD
AUX HEAT
ON THRESHOLD
AUX HEAT
OFF THRESHOLD
COOLING STAGE 1
ON THRESHOLD
COOLING STAGE 1
OFF THRESHOLD