Patriot Series Single Tank Product Manual

 

pg. 6 

 

5.

 

Connect the Valves to the Water Source 

A.

 

Pipe or tube a line from the Control Valve Drain (Figure 14) to the drain. Refer to section 9 for 
the proper sized drain line. 
 

DO NOT  

 

install a valve in this line 

 

use a pipe smaller than the valve sizes listed on section 9 

 

make a direct connection to the drain 

o

 

Provide an air gap at least four times the diameter of the drain pipe to 
conform to sanitation codes and be able to observe the drain flow. 

 

use an excessive amount of elbows in the plumbing 

 

B.

 

Connect the facility plumbing to the control valve inlet and outlet following all local codes.  
 

Note

: Make sure all piping is free of thread chips and other foreign matter. 

 

6.

 

Start up the system for the first time.  

A.

 

Add about three gallons of water to the brine tank.  

B.

 

Make sure the tanks are filled with water.  

a.

 

 Manually put the control valve into regeneration (Hold the regen button) 

b.

 

 A mixture of air and water will flow from the drain line.  

c.

 

 Slowly open the bypass valve’s inlet to allow water to slowly enter the tank.  

(shown in figure  

d.

 

 Once the tank is filled, only water will be coming out of the drain line. Put the system back 
into bypass operation.  Run each step of the regen cycle (Figure 21) for a few minutes.  

C.

 

Program the Valve. Most of the settings were pre-programed by Diamond H2O. The installer 
must enter the installer settings shown in part 8 section C of this manual.  
 

 

 

 
 
 
 
 
 
 
 
 
 

Figure 16: Finished System 

Control Valve Inlet 

Brine Line 

Drain Outlet 

Control Valve Outlet 

Bypass Valve 
 

Figure 15: Opening 

bypass valve’s inlet 

Summary of Contents for DCS6-120-125

Page 1: ...Patriot Series Single Tank Product Manual pg 0 Patriot Single Tank Product Manual...

Page 2: ...Figure 2 _____ 2 Brine Tank Figure 4 _____ 3 Brine Line Hose Figure 6 _____ 4 Softener Tank Figure 5 _____ 5 Correct Amount of Gravel from Model and Media Requirements Table on page 2 _____ 6 Correct...

Page 3: ...5 15 DCS6 60 xxx 2 25 DCS6 75 xxx 2 5 25 30 DCS6 90 xxx 3 30 35 DCS6 120 xxx 4 55 DCS6 150 xxx 5 80 DCS6 180 xxx 6 100 DCS6 210 xxx 7 100 DCS6 240 xxx 8 175 DCS6 270 xxx 9 175 DCS6 300 xxx 10 175 DCS...

Page 4: ...the side The correct distance between the two tanks can be determined by connecting the MAV to both valve outlets d Mark the front of each resin tank shown in Figure 7 with either a marker or tape Th...

Page 5: ...nd radials if it is not contact Diamond H2O Conditioning F SLOWLY pour the correct amount of resin into the tank Again try to keep the media level by carefully rocking the tank back and forth G Fill t...

Page 6: ...no air can get into the line or the softener will not regenerate properly C A red latch with a Polytube insert attached is placed under the brine inlet of each valve Place this insert in the brine lin...

Page 7: ...hips and other foreign matter 6 Start up the system for the first time A Add about three gallons of water to the brine tank B Make sure the tanks are filled with water a Manually put the control valve...

Page 8: ...resulting in four modes of operation Treated Water Exits Supply Water Enters Figure 17 Normal Operation Supply Water Enters Supply Water Exits Figure 18 Bypass Operation Supply Water Enters Supply Wa...

Page 9: ...drawn from Brine Tank through Brine Line Valve to Resin Bed Hardness ions are then replaced by sodium ions preparing Resin for another treatment cycle The Regenerate flows through resin at a specific...

Page 10: ...y Diamond H2O Press and Hold NEXT a Type of water treatment device Softening Filtering Softening This device is a water softener Filtering This device is a filter b Capacity of Resin in grains per gal...

Page 11: ...capacity automatically estimated Regeneration occurs at the next Regen Set Time when volume capacity fails below the reserve capacity or the specified number of days between regenerations is reached A...

Page 12: ...s setting is turned off if volume capacity is set directly b Day Override Off Regeneration is based solely on the number of gallons used Number of Days 1 28 Maximum number of days before regeneration...

Page 13: ...he day that the system will regenerate The system will then regenerate and the G Regeneration Mode Once the systems starts to regenerate the display will show which process in the regeneration cycle i...

Page 14: ...irst the display will flash between showing A 0 and the reserve capacity in gallons A means that the reserve capacity is automatically calculated and the number after A represents the day 0 today 1 ye...

Page 15: ...d Hold J Valve History Press and Hold 4s then Press and Hold 4s a Software Version The current version of the installed software b Maximum Flow Rate since last time the system was reset c Total Number...

Page 16: ...Patriot Series Single Tank Product Manual pg 15...

Page 17: ...Patriot Series Single Tank Product Manual pg 16...

Page 18: ...Patriot Series Single Tank Product Manual pg 17 9 System Specifications...

Page 19: ...Patriot Series Single Tank Product Manual pg 18...

Page 20: ...icate that water is flowing Refer to instructions for how the display indicates water is flowing pg 13 Bypass valve in bypass position Figure 23 Turn bypass handles to place bypass in service position...

Page 21: ...or foreign material Incorrect programming Check for programming error Meter cable wires are not installed securely into three pin connector Verify meter cable wires are installed securely into three...

Page 22: ...Restricted or kinked drain line Check drain line for restrictions or debris and or un kink drain line Plugged backwash flow controller Remove backwash flow controller and clean or replace Missing ref...

Page 23: ...n too short and was unable to find the next cycle position and stalled Foreign material is lodged in control valve Open up control valve and pull out piston assembly and seal stack assembly for inspec...

Page 24: ...nd REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect Err 1006 Err 106 Err 116 MAV SEPS NHBP AUX MAV v...

Page 25: ...ged in MAV NHBP valve Check motor connections Press NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then...