DLEV1
Operating Instructions
- 18 -
5.3.5 CP Error
“E” Simulation
With the CP Error
“E” button pressed and held, a CP Error can be
simulated (in accordance with the standard IEC/EN 6185-1).
•
PP State switch will need to be set to any current position other
than NC.
•
CP State switch will need to be set to position C or D.
•
When CP error
“E” is pressed and held, a short circuit between
CP and PE through the internal diode is made. As a result, the
pending charging process is aborted indicated by the
immediate voltage drop.
5.3.6 PE Error (Earth Fault) Simulator
When pressing the PE Error button, an interruption of the PE conductor
is simulated.
•
As a result, the pending charging process is aborted.
5.3.7 Phase Indicator
The phase indicator consists of three LED lamps, one for each phase.
•
When the test adaptor is connected to the charging station and
phase voltages are present at the charging connector, the LED
indicators will illuminate.
Please Note:
In the case neutral (N) conductor is not present, or it is interrupted, the
LED indicators will not indicate possible voltage presence at L1, L2 and
L3 conductors.
The LED indicators cannot be used for phase sequence testing.
If the charging station has only a single-phase output, only one LED will
illuminate.