39
WORKING LIMITS
-
maximum working pressure
: 10 bar (140 p.s.i)
-
fluids accepted:
clean water and liquids that are chemically non-aggressive. If there are
impurities in the liquid, install a strainer upstream
-
fire / explosion:
inverters STEADYPRES
ARE NOT SUITABLE
for operation in environments
with risk of explosion.
-
Maximum ambient temperature:
40 °c; D
-
minimum ambient temperature
: 0 °C
-
max liquid temperature
: 55 °C
-
min liquid temperature
:: 0 °C
-
supply voltage tolerance
: + / - 10%
compared to the nameplate data
-
flow rates and pressure drops
:
in side
figure is represented the loss of load (in
mH2O) through the inverter, to vary the
flow rate
TECHNICAL DATA
main voltage
supply
230
+/- 10%
Vac single-phase (models M/M e M/T)
WARNING: IN CASE OF
LOW VOLTAGE
(NOMINAL VALUE -10% )
OVERCURRENTS CAN
OCCUR DURING
STARTING OR FULL
LOAD OPERATION.
400
+/- 10%
Vac three-phase
(models T/T)
output voltage
230 Vac single-phase
(models M/M)
230 Vac three-phase
(models M/T)
400 Vac three-phase
(models T/T)
frequency
50 – 60 Hz
enclosure
IP 65
working position
vertical, with the liquid inlet from the bottom and top exit.
Current and power table
Model
V in
V out
A out
Fuse (A)
P2 max (kW)
P2 max (HP)
M/M 8.5
1 ~ 230V
1 ~ 230V
8,5
20
1,1
1,5
M/M 11
1 ~ 230V
1 ~ 230V
11
25
1.5
2.0
M/M 16
1 ~ 230V
1 ~ 230V
16
25
2,2
3,0
M/T 7
1 ~ 230V
3 ~ 230V
7
20
1,1
1,5
M/T 12
1 ~ 230V
3 ~ 230V
12
25
2,2
3,0
T/T 6
3 ~ 400V
3 ~ 400V
6
no
2,2
3,0
T/T 8
3 ~ 400V
3 ~ 400V
8
no
3,0
4,0