ALARMS 

OVER 

CURRENT % 

The current 

exceeded the allowable tolerance 

on the current set. 

The inverter stops the pump, the rearm is only manual. 

CURRENT 

LIMIT 

The current 

exceeded the module current capacity.

 

The inverter stops the pump, the rearm is only manual. 

 i DRY  
 

Occurs if, in the absence of flow, 

the pump cannot reach the SET pressure

, but 

can 

reach at least a pre-determined percentage

 of the SET pressure, defined through 

the parameter Pd. The inverter does not stop the pump, which continues to work with 

the message “i-DRY” on the display. 

DRY RUNNING 

 

Occurs if, in the absence of flow, 

the pump fails to reach the pressure 

of the set but 

does not even reach a predetermined percentage of the SET pressure

, expressed 

by the parameter Pd; the inverter stops the pump. 
The error is reset after the time TP and the inverter re-starts in automatic mode. 

LOW PRESS 

Occurs if the pump is running at maximum frequency (50/60 Hz), in the presence of 

flow, and 

the pressure doesn’t reach 0.3 bar

; the inverter stops the pump. 

The error is reset after the time TP and the inverter re-starts in automatic mode. 

LOW VOLTAGE 

voltage drop

 has occurred beyond minimum operating threshold. The inverter stops 

the pump. The error is reset after one minute, and the inverter re-starts in automatic 

mode. 

HIGH VOLTAGE 

voltage peak

 has occurred beyond maximum operating threshold. The inverter stops 

the pump. The error is reset after one minute, and the inverter re-starts in automatic 

mode. 

HIGH TEMP. 

BOX

 

(only T/T mod.)

 

The 

temperature inside the inverter

 has reached 65 ° C;  is automatically 

limited the 

maximum

 frequency of 5 Hz but 

the drive continues to run

, the error is reset below 

60 ° C 

OVER TEMP. 

BOX 

(only T/T mod.)

 

The 

temperature inside the inverter

 has reached 80 ° C, 

the inverter stops the 

pump,

 the error is reset below 60 ° C and the drive will restart automatically 

HIGH 

TEMPERATURE 

MOD 

The 

module temperature

 has reached the first alarm threshold; 

the maximum

 

working frequency 

is automatically limited,  but 

the drive continues to run

, the error 

is reset when the module temperature returns below 70 °C

 

OVER TEMP 

MOD 

The 

module

 

temperature 

has reached 

the second alarm threshold

the inverter stops 

the pump,

 the error is reset 

when the module temperature returns below 70 °C

 and the 

drive will restart automatically

 

INPUT ERROR 

There has been a 

reversal of the power connections

 / output to the motor. the 

inverter is locked, the error is reset by connecting the cables correctly in the terminal

 

COM ERROR 
 

communication has been interrupted

 between the control board and the power 

board; the causes could be the integrity of the cable and of the connection ports or an 

electronic board fault.

 

PHASE ERROR 
 

 (only for models with three-phase output) 

lack of a phase towards the motor

 during 

operation. The inverter stops the pump ; reset is manual only.

 

LOW LEVEL 

this occurs when the digital input EI is 

configured as “WATER LEVEL” (level signal) 

and there is no signal.

 When the signal returns, the message disappears and the 

inverter operates normally again.

 

EXT OFF 

this occurs when the digital input EI is 

configured as “EXT ENABLE” (control 

enabled from outside) and there is no signal

. When the signal returns (external 

enabling) the message disappears and the inverter operates normally again.

 

 

OFF 

It occurs when the supply voltage is disconnected; the capacitors are discharged, for 

security reasons, from the discharge resistors. The process takes about 10 sec 

Summary of Contents for STEADYPRES 2.0 M/M 11

Page 1: ...spare parts tampering or improper use make the product warranty null and void During first installation or when carrying out maintenance make sure that the electric power supply network is not live Th...

Page 2: ...ASTER and SLAVE 36 o Alarms 37 PART 2 OPERATOR S AND MAINTENANCE MANUAL o General remarks 38 o Working limits 39 o Technical data 39 o Dimensions and weight 40 o Product identification code 40 o Surge...

Page 3: ...the inverter in a place o protected from the elements o ventilated free from excessive humidity or excessive dust o as close as possible to the pump o make sure that does not receive harmful vibration...

Page 4: ...sinusoidal filter It aids smooth running of motors eliminating negative effect of voltage peaks GND L N GND V W U LINE MOTOR N L SINGLE PHASE IN line SINGLE PHASE OUT motor M M Pump supply voltage 23...

Page 5: ...ps 4 e 5 In applications with parallel inverters the wiring must be carried out on the MASTER RS485 SIGNAL CONNECTION 10 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1 Connect the termina...

Page 6: ...history etc TEST mode only in OFF mode TEST mode allows you to start and stop the pump in manual mode START STOP button and change the frequency in steps of 1 Hz It also allows to control the operatin...

Page 7: ...Y FOR POWER FACTOR only T T models TP RESTART INTERVAL FOR DRY RUNNING TF STOP DELAY FOR NO FLOW RF INVERTER REACTIVITY FS MODULE SWITCHING FREQ US NO GRIP STARTUPS EI INPUT SIGNAL EO OUTPUT SIGNAL AI...

Page 8: ...rent of the motor At low supply voltages the current set should leave a margin eg 15 to compensate for the low voltage m u Default Min Max Step M M 8 5 A 8 5 1 8 5 0 1 M M 11 A 11 1 11 0 1 M M 16 A 16...

Page 9: ...nning conditions CAUTION high values of the stop delay may damage the pump sec 10 1 100 1 PF 50 MINIMUM POWER FACTOR only T T models Sets the minimum value for the power factor below which the inverte...

Page 10: ...T there is at least one operating pump EO 3 recirculation activates the relay output time intervals defined by param AI AI 60 RECYCLE FUNCTION Sets the output activation interval clean contact type co...

Page 11: ...FI Shows the instantaneous value of the power factor only T T models Tm 50 POWER MODULE TEMPERATURE Displays the inverter s electronic module temperature C Ti 30 INVERTER BOX INTERNAL TEMP Displays th...

Page 12: ...he operating parameters by pressing the keys To stop the TEST press the A START STOP button PRIMING AND STARTING UP Do not run pumps dry Before starting the pump make the filling of all pumps In the p...

Page 13: ...rive continues to run the error is reset below 60 C OVER TEMP BOX only T T mod The temperature inside the inverter has reached 80 C the inverter stops the pump the error is reset below 60 C and the dr...

Page 14: ...s during starts and operation energy saving Allows the selection of the power supply and output voltage PART LIST 1 control system 2 removable electric connector 3 I O power cable bushing 4 power boar...

Page 15: ...nverter to vary the flow rate TECHNICAL DATA main voltage supply 230 10 Vac single phase models M M e M T WARNING IN CASE OF LOW VOLTAGE NOMINAL VALUE 10 OVERCURRENTS CAN OCCUR DURING STARTING OR FULL...

Page 16: ...under pressure to minimize the start up of the pumps it is essential in the presence of small system leakages absorbs overpressures from the system the minimum tank volume in liters for diaphragm mode...

Page 17: ...cable and the motor cable must be sized to curb any power voltage drop within 3 The power supply cable and the motor cable must be suitably shielded to comply with EMC standards In case of long cable...

Page 18: ...you can view the status parameters For visualization of the operating parameters see QUICK INSTALLATION GUIDE LIGHT SIGNALS keyboard ON OFF BLINKING POWER STATUS STEADYPRES does not detect power supp...

Page 19: ...rrect direction of rotation check the correct sizing of the wires CURRENT LIMIT Serious overcurrent absorption which inverter cannot cope with Make sure the motor pump is not blocked reduce the motor...

Page 20: ...connect the inverter main power supply and wait 2 minutes capacitors discharge Open the front cover and disassembly the pressure sensor and the control board as shown below Install the new control boa...

Page 21: ...ton SET TEST to confirm the zero pressure SP 5 0 Start the pump by pressing START button the pump starts at the minimum frequency SP 5 0 Increase the frequency of the pump by pressing the button until...

Page 22: ...KIT 4 KIT 3 KIT 5 6 7 7 8 10 N Description Q ty KIT 1 Cover Kit with keyboard 1 KIT 2 Pressure sensor Kit 1 KIT 3 Non return valve flow sensor Kit 1 KIT 4 Cable bushing cover Kit 1 KIT 5 Expansion bo...

Page 23: ...ce in the countries where the unit is used Do not disperse pollutant parts in the environment DECLARATION OF CONFORMITY We declare under our own responsibility that the product in question is in compl...

Reviews: