27
PARAMETER
SYMBOL SHORT DESCRIPTION
UNIT default min Max step
2.20 KP
KP
P.I.D control proportional coefficient
-
8
1
50
1
2.21 KI
KI
P.I.D control integrative coefficient
-
10
0
50
1
IMPORTANT: THE PARAMETERS KI and KP ARE CRITICAL BECAUSE THEY CHANGE THE BEHAVIOUR
OF THE INVERTER, AND WRONG SETTING CAN CAUSE SYSTEM MALFUNCTIONING
The parameters KP and KI constantly define the operating frequency of the inverter-controlled pump,
depending on the fluctuation of system pressure compared to the set pressure.
The more the system is elastic, the greater the proportionate parameter must be. The more rigid the
system is, the smaller the proportionate parameter must be. Limits vary from 1 to 50 with step 1.
The integrative parameter must be higher in the presence of fast changes in system pressure and
lower in the presence of pressure oscillations. Limits vary from 0 to 50 with step 1.
NOTE. The parameters KP and KI are automatically changed when any changes are made to the RF
parameter (see 2.7 RESPONSE FACTOR parameter); this operation is performed to adapt the speed of
response of the device.
PARAMETER
SYMBOL SHORT DESCRIPTION
UNIT default min Max step
2.22
RESTORE DEFAULT
-
Restore of BASE and ADV parameters
-
-
-
-
-
By means of this function, the parameters entered in the BASE SETUP and ADV SETUP menus are reset
to factory setting, while the HARDWARE SETUP parameters are not reset.
To reset all the parameters, including the HARDWARE SETUP parameters, the function in the EXTENDED
MENU must be used; use of the menu protected by password is restricted to after-sales centres or the
factory.
1.2.
HARDWARE CONFIGURATION
(HARDWARE SETUP)
This menu contains all the parameters needed to set up the signal inputs and outputs on the control board.
The control logics of the flow and pressure signal and type of connected sensors can also be set up.
PARAMETER
SYMBOL SHORT DESCRIPTION
UNIT default min max
step
3.1 PUMP 1 CONFIG
P1C
Pump 1 configuration
-
1
1
1
-
The parameter is fixed, pump 1 is connected by default to the inverter 1
PARAMETER
SYMBOL SHORT DESCRIPTION
UNIT default min max
step
3.2 PUMP 2 CONFIG
P2C
Pump 2 configuration
-
*
0
3
1
•
Default setting depends from the model. In case of DEFAULT RESTORE the parameter is = 0
The parameter makes it possible to set up the pump 2 connection
The functions that can be assigned are:
0
NO FUNCTION
Pump 2 is disabled (factory setting for models “MV”)
1
INTERNAL
CONTACTOR 1
Pump 2 is connected to internal connector 1 (factory setting for models
“MVF”) and works at fixed speed.
2
INVERTER 2
Pump 2 is connected to internal inverter 2 (factory setting for models “MW”)
and works at variable speed.
3
EXT. INV. 2
Pump 2 is connected to SLAVE 1 unit and works at variable speed.
PARAMETER
SYMBOL SHORT DESCRIPTION
UNIT default min max
step
3.3 PUMP 3 CONFIG
P3C
Pump 3 configuration
-
0
0
1
1
The parameter makes it possible to set up the pump 3 connection.
The assignable functions are:
0
NO FUNCTION
Pump 3 is disabled (factory setting)
1
EXT. INV. 3
Pump 3 is connected to the inverter SLAVE 2 and works at variable speed