28
PARAMETER
SYMBOL SHORT DESCRIPTION
UNIT default min max
step
3.4 PUMP 4 CONFIG
P4C
Pump 4 configuration
-
0
0
1
1
The parameter makes it possible to set up the pump 4 connection.
The assignable functions are:
0
NO FUNCTION
Pump 4 is disabled (factory setting)
1
EXT. INV. 4
Pump 4 is connected to the inverter SLAVE 3 and works at variable speed
PARAMETER
SYMBOL SHORT DESCRIPTION
UNIT default min max
step
3.5 INPUT 1 CONFIG IN1
digital 1 input function set
-
0
0
5
1
3.6 INPUT 2 CONFIG IN2
digital 2 input function set
-
0
0
5
1
The parameters make it possible to
set up the function to be attributed to the digital inputs IN1 and IN2
on the control board. The functions that can be assigned to each input are:
0
NO
FUNCTION
No function; the input state is ignored
1
WATER
LEVEL
Level signal input; if the level sensor contact is open, the control remains stopped, in alarm
state, and the message “LOW LEVEL” appears on the screen. If the level sensor contact is
closed, the alarm disappears and the control starts to work normally again.
2
EXT
ENABLE
Start and disabling of control by means of external signal: if the signal is not enabled, the
control does not start and the message “EXT OFF” appears.
3
PRESS SET
2
Enabling input of the second pressure level P2 (see para. 4.3.1 - parameter 1.2 /
PRESSURE SET 2); the active signal enables the switch to the second operating pressure set
in the PRESSURE SET 2 parameter; the inactive signal switches back to the main PRESSURE
SET 1 pressure.
4
FLOW
SIGN
Auxiliary flow signal input; this input configuration can be used to connect a clean-contact
type flow signal connection, and with NO logic (when there is no flow, the signal is not
active. When there is flow, the signal is active).
5
SLAVE 1
Enabling input of the SLAVE 1 signal (ON/OFF)
PARAMETER
SYMBOL SHORT DESCRIPTION
UNIT default min
max step
3.7
OUTPUT 1 CONFIG
OU1
digital 1 output function set
-
0
0
4
1
3.8
OUTPUT 2 CONFIG
OU2
digital 2 output function set
-
0
0
4
1
The parameters make it possible to
set up the function to be attributed to the 2 output relays
on the
control board. The output signal is provided by relay with contacts C/NO/NC. The maximum load
connectable to the relay must not exceed 5 A and 250 Vac. The functions that can be assigned to each
output are:
0
NO FUNCTION
No function. The state of the output is never activated.
1
ALARM
Alarm output. The output starts to indicate the condition of stop due to fault.
2
RUN
Pump operating output. The output starts to indicate there is at least one
operating pump.
3
ANTI FREEZE
the output is active at programmed intervals; the output can be used to command
a solenoid valve, which starts the recirculation of the liquid under pressure and
thus starts the system pump, to prevent the pump and the hoses from freezing.
4
PRE - ALARM
Output signal of pump running in frequency limitation for excessive absorption or
temperature rise.