15.8.14
UNIGATE
®
fieldbus gateway UNIGATE
®
CL PROFINET 2Port V. 1.6
38
Deutschmann Automation GmbH & Co. KG
Technical data
17 Technical data
17.1 Device data
The technical data of the module is given in the table below.
No. Parameter
Data
Explanations
1
Location
Switch cabinet
DIN-rail mounting
2
Enclosure
IP20
Protection against foreign
bodies and water to IEC 529
(DIN 40050)
4
Service life
10 years
5
Housing size
23 x 115 x 111 mm
(screw-plug-connector included)
23 x 1115 x 100 mm
(screw-plug connector not included)
W x D x H
6
Installation position
Any
7
Weight
150 g
8
Operating temperature
-25ºC ... +85ºC
9
Storage/transport
temperature
-40 ºC ... +85 ºC
10
Atmospheric pressure
during operation
during transport
795 hPa ... 1080 hPa
660 hPa ... 1080 hPa
11
Installation altitude
2000 m
4000 m
Unrestricted
Restricted -
Ambient temperature
40ºC
12
Relative humidity
Max. 80 %
No condensation,
no corrosive atmosphere
14
External
power supply
10...33 V DC
Standard power supply unit to
DIN 19240
15
Current consumption at 24
VDC
Typ. 120 mA
max 150 mA
17
Reverse voltage protection Yes
But does not function!
18
Short-circuit protection
Yes
19
Overload protection
Poly-switch
Thermal fuse
20
Undervoltage detection
(USP)
9 V DC
21
Emergency power supply
5 ms
Device fully operable
Table: Technical data of the module