Implemented protocols in UNIGATE® CL with Universal Script
10 Implemented protocols in UNIGATE
®
CL with Universal
Script
UNIGATE
®
CL is supplied with the Script “Universal Script Deutschmann“. The configuration of
the protocols is carried out by means of the software WINGATE. See "Instructions UNIGATE
®
CL
- Configuration with WINGATE". The PDF can also be found on our website under Support/Sup-
port/Downloads/Manuals.
Attention:
If a Reset Device is carried out it is possible (depending on the firmware
version of the UNIGATE
®
) that the "Universal Script" will get lost and
must be played in again.
The Script can be found on the Deutschmann Support-DVD in the folder
\Software\ProtocolDeveloper\Example\Universal\.
10.1 Protocol: Transparent
The data is transferred bidirectional from the UNIGATE
®
.
10.1.1
Data structure
On the RS-entry side the timeout time of 2 ms is firmly set. If no more data is received within the
timeout period, then the data that has been received so far is transferred to the bus.
If less data is received through Rx then configured by the GSDML-file (I/O-length), then the rest
is complemented with ZERO.
Too much data received will be cut off.
10.2 Protocol: Universal 232
The protocol designation "Universal 232" and the relation to the
"RS232-interface" in the description have eveloped over the years. The
protocol also works with RS422 and RS485 though!