Setting the Profibus-ID at LOCON and ROTARNOCK
Deutschmann Automation GmbH & Co. KG
26
Instruction manual LOCON 100 / 200 and ROTARNOCK 80 / 100 with fieldbus connection V. 1.0
22.1.08
9.1.3
Example for WINLOC32-Upload
The device has to be connected with the PC via the RS232-connection. If WINLOC32 is started
then only an „Upload“ has to be carried out afterwards. The desired Profibus-ID can be entered
into the „Configuration“ now.
A „Donwload“ has to be performed in order to take over the change. The device carries out a
restart and with it the new ID is set.
9.1.4
External setting of the Profibus-ID
The devices LOCON 100 & LOCON 200 can be adjusted to the corresponding address through
the rotary coding switches (hexadecimal) located at the bottom side.
At ROTARNOCK 100 it is also possible to select the Profibus-ID externally. For further informa-
tion please have a look at the manual „ROTARNOCK 100“.