background image

 

 

7

If the heating and air-cooling speed are the same, the red 
wire and the blue wire can be connected on the same 
terminal on the motor. 

 

2.7 INSTALLATION 

OF 

ACCESSORIES

 

 

WARNING 

 

Electrical shock hazard. 

 

Turn OFF electrical power at the fuse box or service 
panel before making any electrical connections and 
ensure a proper ground connection is made before 
connecting line voltage. 

 

Failure to do so can result in death or bodily injury. 

 

 

 

2.7.1. Humidifier 

and 

electronic air cleaner 

 

 
This unit is equipped with a 120 VAC terminal for the 
connection of accessories up to a maximum of 2 amps.  A 
humidifier and an electronic air cleaner can be wired to 
terminals “1” and “2” of the unit.  Refer to the wiring 
diagrams in this manual.  A field supplied 120/24 VAC 
transformer can be installed for accessories using 24 VAC.  
A separate power source must be used if the accessories 
draw more then 2 amps. 
 
Certain accessories require control relays.  A location has 
been set aside in the unit for the installation of relays: a 24 
VAC (part number L01H009).  In addition, a 24 VAC relay 
can be wired between terminals “W1” and “C” to be activated 
during a call for heat.  Refer to the wiring diagrams for the 
location of the relay (RAcc) on the control panel. 
 

2.7.2. 

Use of a heat pump

 

 
When using a heat pump, a thermostat with dial fuel option 
or a fossil fuel kit is required that prevents the operation of 
the electric elements and the heat pump at the same time.  
Refer to the instructions provided with the thermostat or the 
“Fossil Fuel” kit for the proper wiring of the furnace and the 
heat pump. 
 
The simultaneous operation of the electric elements and the 
heat pump will cause overheating of either unit.  The safety 
controls of the appliances will shut down the elements or 
heat pump, since they are not designed to function in this 
fashion. 
 
 
 

3.0 OPERATION

 

 

3.1 START-UP

 

 
Before starting up the unit, be sure to check that the 
following items are in compliance: 
1.  The electrical installation and ventilation; 
2.  The blower access door is in place and the blower rail 

locking screws are well tightened; 

3.  The blower speed adjustments for heating and air 

conditioning are appropriate and according to the 
specifications in this manual; 

4.  The thermostat of the room is in the heating mode and 

is set higher than the ambient temperature.  

5.  The breakers on front panel are closed (green indicator) 
To start the unit, turn the main electrical switch on. 
 

3.2 

USE OF MANUAL FURNACE CONTROLS

 

 
When there is a demand for heat, the pilot light (“L-1”) 
comes on.  Refer to the wiring diagram. 
 
When the ”HI/LO” switch is put into the “LO” position, it will 
shut down approximately half the elements.  
 

However, it is important to put the switch back to the 
“HI” position during the winter months to ensure 
adequate heating. 

 
Also, this switch must remain in the “HI” position when a 2-
stage or outdoor thermostat is used to control the electric 
elements of the second stage.  Refer to the diagram in 
Section 2.5) above (Typical 24 VAC Wiring, Thermostat). 
 
The “ON/OFF  VENT/FAN” switch engages the blower in the 
continuous speed mode.  This will filter the air and provide 
for better air distribution in the building. 
 
The circuit breaker is there to protect the motor and control 
circuit conductors.  If the unit does not function, press the 
circuit breaker button to see if it may have disengaged due 
to a power surge.  If the breaker has to be pressed again, 
the unit must be checked by a qualified service technician. 
 

Figure 8 : Manual Furnace Controls 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

3.3 OPERATING 

SEQUENCE

 

 

3.3.1. Heating 

mode

 

 

1.  The thermostat closes the R-W1 circuit (24 VAC), 

thereby activating the first 22 VDC relay passing by a 
rectifier control. Without delay, the 1

st

 heating element is 

activated and the blower starts at low speed. On 15 kW 
unit power and more, a 2

nd

 relay is activated after 8 

seconds delay to start a 2

nd

 element. On 23 kW unit 

power and more, a 3

rd

 relay is activated after 8 second 

delay to start a 3

rd

 element.  

2.  The thermostat closes the R-W1 & W2 circuit (24 VAC), 

thereby activating others 22 VDC relays passing by a 
rectifier/timer with 8 seconds delay between each one. 
The heating elements of the second stage are activated 
in sequence after the 8 seconds delay between each. 

Summary of Contents for SUPREME SUP10-M2401A

Page 1: ...J1L 1V8 Caution Do not tamper with the unit or its controls Call a qualified service technician Printed in Canada Printed on 100 recycled paper MULTI POSITION INSTALLER SERVICE TECHNICIAN USE THE INF...

Page 2: ...8 4 1 AIR FILTER 8 4 2 MOTOR LUBRICATION 8 5 0 FURNACE INFORMATION 9 TABLES Table 1 Supply air adjustment on heating mode 6 Table 2 Supply air adjustment on air cooling mode 6 Table 3 Technical speci...

Page 3: ...tch or circuit breaker ii The air filter and how to change it check monthly and clean or replace if necessary f Before calling for service be sure to have the information of section 5 of your manual c...

Page 4: ...o clearance to combustible material regardless of the heating capacity 2 2 2 Supply air ducts Ducts for furnaces with a heating capacity up to and including 20 k W can be installed with a zero clearan...

Page 5: ...acement these must be copper wires only with same temperature rating as originals 2 5 INSTALLATION OF THE THERMOSTAT A thermostat must be installed to control the temperature of the area to be heated...

Page 6: ...no way hinder access to the furnace panels 2 6 SUPPLY AIR ADJUSTMENTS On units equipped with 4 speed blower motors the supply air must be adjusted based on heating air conditioning output and the stat...

Page 7: ...door is in place and the blower rail locking screws are well tightened 3 The blower speed adjustments for heating and air conditioning are appropriate and according to the specifications in this manu...

Page 8: ...certain that the unit does not operate above the temperatures specified in the Technical Specifications Table 2 This is particularly important if a cooling coil or a heat pump has been installed in th...

Page 9: ...ler name and address START UP RESULTS Voltage Total current consumed by the elements Supply air temperature Return air temperature Supply air duct static pressure Return air duct static pressure Total...

Page 10: ...nd size Shipping weight Maximum cooling capacity ELECTRICAL SYSTEM GENERAL INFORMATION BLOWER DATA factory adjusted to a staic pressure of 0 5 W C 1 20 x 20 3 tons SUPxx M2401B 19 x 19 12 x 10 2 Calcu...

Page 11: ...11 Figure 9 Furnace dimensions...

Page 12: ...12 Figure 10 Wiring diagram 3 wires 10 kW...

Page 13: ...13 Figure 11 Wiring diagram 3 wires 15 kW...

Page 14: ...14 Figure 12 Wiring diagram 3 wires 18 20 kW...

Page 15: ...15 Figure 13 Wiring diagram 3 wires 23 kW...

Page 16: ...16 Figure 14 Wiring diagram 3 wires 27 kW...

Page 17: ...17 Figure 15 PARTS LIST Supreme with 1 3 HP and 1 HP motor SUPxx M2401A or SUPxx M2401B B50130A dwg...

Page 18: ...L 22A B04125 ELECTRICAL KIT 10kw 22B B04124 ELECTRICAL KIT 15kw 22C B04123 ELECTRICAL KIT 18 20kw 22D B04122 ELECTRICAL KIT 23 25kw 22E B04121 ELECTRICAL KIT 27kw 23 B04091 MOUNTING PLATE FOR ELECTRIC...

Reviews: