background image

 

 

8

The 24 VAC relay of the heating speed is also activated 
and heating blower speed start.  

 

3.3.2. Cooling 

mode

 

 
1.  The thermostat closes the R-G circuit, thereby activating 

the 24 VAC R-1 relay.  The blower starts up to cooling 
speed.   

2.  The thermostat closes the R-Y contact, thereby 

activating the compressor relay of the air conditioner. 

 

3.3.3. Continuous 

Fan 

speed 

 

 
The blower will also start up to cooling speed by way of the 
“Fan” switch on the thermostat. 

 

3.4 AIRFLOW 

VERIFICATION

 

 
Verify the airflow by taking readings of the following points, 
while the elements are in the heating mode: 
a.  Total amperage of all the heating elements; 
b.  Voltage at the furnace; 
c.  Supply air temperature.  The point of the reading must 

not be affected by radiant heat from the elements; 

d.  Return air temperature. 

 

From these readings, one can arrive at an approximate 
calculation of the average airflow.  To do that, the following 
formula should be used: 
 
 
 
 

 

0.82 x amps. x volts 

Liter/s= ------------------------- 
   Diff. 

temperature 

˚

 
 

 

3.1 x amps. x volts 

CFM =  ------------------------ 
   Diff. 

temperature 

˚

 

3.4.1. 

Supply Air Temperature Rise Test

 

 
1.  Operate the unit at maximum power for at least 10 

minutes; 

2.  Measure the air temperature in the return air plenum; 
3.  Measuring the air temperature in the largest trunk 

coming off the supply air plenum, just outside the range 
of radiant heat from the heat exchanger.  0.3 m (12”) 
from the plenum of the main take-off is usually sufficient; 

4.  The temperature rise is calculated by subtracting the 

return air temperature from the supply air temperature. 

 
If the temperature rise exceeds the temperature specified in 
Table 3, change to the next higher blower speed tap, until 
the temperature rise falls to the target or below.  If the 
excessive temperature rise cannot be reduced by increasing 
fan speed, investigate for ductwork obstructions or dirty and 
improper air filter. 

 

CAUTION 

 

It is important to check the airflow and to ascertain that 
the unit does not operate above the temperatures 
specified in the Technical Specifications (Table 2).  This 
is particularly important if a cooling coil or a heat pump 
has been installed in the ducts. 

 

Hi-Limit thermal protectors should never need to engage 
during the normal functioning of the appliance.  They 
are strictly designed to engage during the improper 
functioning of the blower or when the filter was 
improperly maintained. 

 

 

3.4.2. High 

limit 

verification

 

 

After operating the furnace for at least 15 minutes, restrict 
the return air supply by blocking the filters or the return air 
register and allow the furnace to shut off on High Limit.  The 
electric heaters must deactivate themselves one by one 
before the warm air temperature exceeds 200

˚

F. 

Remove the obstruction and the elements should restart 
after a few minutes. 
 

4.0 MAINTENANCE 

 

WARNING 

 

Electrical shock hazard. 

 

Turn OFF power to the furnace before any disassembly 
or servicing. 

 

Failure to do so can result in death, bodily injury and/or 
property damage. 

 

 

Preventive maintenance is the best way to avoid 
unnecessary expense and inconvenience.  Have your 
heating system inspected by a qualified service technician at 
regular intervals.  Do not attempt to repair the furnace or its 
controls.  Call a qualified service technician. 
 
Before calling for repair service, check the following points: 
1.  Check fuses or the circuit breaker; 
2.  Check if the 15 A circuit breaker on the furnace is 

disengaged; 

3.  Set the thermostat higher than room temperature.  If the 

unit does not start up, cut the power and call la qualified 
service technician. 

 
When calling for service or ordering a replacement part, 
specify the model and serial number of your appliance. 
 

4.1 AIR 

FILTER

 

 
The filter supplied with the unit is the disposable type and 
should be replaced twice a year.  The presence of animal 
hair, dust, etc. may necessitate more frequent changes.  
Dirty filters have an adverse effect on the performance of the 
central heating system. 
 

4.2 MOTOR 

LUBRICATION

 

 
Do not lubricate the blower motor, since it is permanently 
lubricated. 

Summary of Contents for SUPREME SUP10-M2401A

Page 1: ...J1L 1V8 Caution Do not tamper with the unit or its controls Call a qualified service technician Printed in Canada Printed on 100 recycled paper MULTI POSITION INSTALLER SERVICE TECHNICIAN USE THE INF...

Page 2: ...8 4 1 AIR FILTER 8 4 2 MOTOR LUBRICATION 8 5 0 FURNACE INFORMATION 9 TABLES Table 1 Supply air adjustment on heating mode 6 Table 2 Supply air adjustment on air cooling mode 6 Table 3 Technical speci...

Page 3: ...tch or circuit breaker ii The air filter and how to change it check monthly and clean or replace if necessary f Before calling for service be sure to have the information of section 5 of your manual c...

Page 4: ...o clearance to combustible material regardless of the heating capacity 2 2 2 Supply air ducts Ducts for furnaces with a heating capacity up to and including 20 k W can be installed with a zero clearan...

Page 5: ...acement these must be copper wires only with same temperature rating as originals 2 5 INSTALLATION OF THE THERMOSTAT A thermostat must be installed to control the temperature of the area to be heated...

Page 6: ...no way hinder access to the furnace panels 2 6 SUPPLY AIR ADJUSTMENTS On units equipped with 4 speed blower motors the supply air must be adjusted based on heating air conditioning output and the stat...

Page 7: ...door is in place and the blower rail locking screws are well tightened 3 The blower speed adjustments for heating and air conditioning are appropriate and according to the specifications in this manu...

Page 8: ...certain that the unit does not operate above the temperatures specified in the Technical Specifications Table 2 This is particularly important if a cooling coil or a heat pump has been installed in th...

Page 9: ...ler name and address START UP RESULTS Voltage Total current consumed by the elements Supply air temperature Return air temperature Supply air duct static pressure Return air duct static pressure Total...

Page 10: ...nd size Shipping weight Maximum cooling capacity ELECTRICAL SYSTEM GENERAL INFORMATION BLOWER DATA factory adjusted to a staic pressure of 0 5 W C 1 20 x 20 3 tons SUPxx M2401B 19 x 19 12 x 10 2 Calcu...

Page 11: ...11 Figure 9 Furnace dimensions...

Page 12: ...12 Figure 10 Wiring diagram 3 wires 10 kW...

Page 13: ...13 Figure 11 Wiring diagram 3 wires 15 kW...

Page 14: ...14 Figure 12 Wiring diagram 3 wires 18 20 kW...

Page 15: ...15 Figure 13 Wiring diagram 3 wires 23 kW...

Page 16: ...16 Figure 14 Wiring diagram 3 wires 27 kW...

Page 17: ...17 Figure 15 PARTS LIST Supreme with 1 3 HP and 1 HP motor SUPxx M2401A or SUPxx M2401B B50130A dwg...

Page 18: ...L 22A B04125 ELECTRICAL KIT 10kw 22B B04124 ELECTRICAL KIT 15kw 22C B04123 ELECTRICAL KIT 18 20kw 22D B04122 ELECTRICAL KIT 23 25kw 22E B04121 ELECTRICAL KIT 27kw 23 B04091 MOUNTING PLATE FOR ELECTRIC...

Reviews: