background image

 

 

5

 

2.3.3. 

Horizontal installation

 

 

The return duct may be installed to the back, on the left side, 
on the right side or under the unit. 
When the furnace is installed in the horizontal position, either 
suspended or on a combustible floor with a choice of right or 
left discharge, the clearances from combustible material 
must be adhered to.  Refer to Figure 3 for additional details. 
 

Figure 3: Horizontal installation 

 
 
 
 
 
 
 

  

2.4 ELECTRICAL 

SYSTEM

 

 

The 

SUPREME

 furnace is completely pre-wired and all field 

wiring must be connected to the terminal blocks on the unit.  
It requires a 120/240 volt, 3-wire power supply. 

 

WARNING 

 

Risk of fire. 

 

The conductor sizing must conform to the last edition of 
the local or national codes. 

 

Failure to follow this rule can result in death, bodily 
injury and/or property damage. 

 

 

Power supply to the unit can be done using copper or 
aluminum wires. The wire size must be decided in 
accordance to unit power consumption, the over current 
protection type and capacity, the wire type and length, and 
the environment where the unit is installed. If an aluminum 
wire is used, other precautions must be taken to insure the 
conformity of the installation. In all cases, all the factors 
affecting the wire gauge must be considered and the 
installation codes followed. 
 
The exterior of the unit must have an uninterrupted ground to 
minimize the risk of bodily harm.  A ground terminal is 
supplied with the control box for that purpose. A connector is 
supplied on the ground terminal to ground an added 
accessory. 
 
 
In the event that wires inside the unit require replacement, 
these must be copper wires only with same temperature 
rating as originals.

 

 

2.5 

INSTALLATION OF THE THERMOSTAT

 

 
A thermostat must be installed to control the temperature of 
the area to be heated.  Follow the instructions supplied with 
the thermostat.  Some thermostat need to connect the C 
terminal on the furnace and thermostat.  Install the 
thermostat on an interior wall in a location where it will not be 
subject to direct sun light, lamps, air diffusers, fireplaces, etc.  
Seal openings in walls to avoid air currents that may 
influence the operation of the thermostat.  Also refer to the 

wiring diagrams provided with the heating/air conditioning 
unit.  The connections must be made as indicated on 
Figures 4 to 8 diagrams and on electrical diagrams (Figures 
10 to 14). 

 

2.5.1. 

Anticipator adjustment (if required) on 
thermostat equipped with heat anticipator 
adjustment 

 

Certain thermostats are equipped with a heat anticipator that 
must be adjusted according to the instructions supplied.  
This is to ensure that the heating mode is comfortable and 
economical. 

 

Generally speaking, on a single stage thermostat, a reading 
of the current must be taken with an ammeter as follows: 
1.  Move the anticipator to its highest setting, rendering it 

ineffective. 

2.  Remove the wire from the “W1” terminal and connect an 

ammeter between the terminal and the wire. 

3.  Call for heat by raising the set point on the thermostat 

and allow the furnace to run for 3 to 4 minutes to reach 
its peak output. 

4.  Once the current has stabilized, a reading should be 

taken and the anticipator adjusted to that value.  If 
longer heating cycles are desired, the anticipator can be 
set to a higher value 

 

Figure 4: 1-stage thermostat, electric heating only 

 
 
 
 
 
 
 
 
 
 

 

Figure 5: 2-stage thermostat, electric heating only 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Summary of Contents for SUPREME SUP10-M2401A

Page 1: ...J1L 1V8 Caution Do not tamper with the unit or its controls Call a qualified service technician Printed in Canada Printed on 100 recycled paper MULTI POSITION INSTALLER SERVICE TECHNICIAN USE THE INF...

Page 2: ...8 4 1 AIR FILTER 8 4 2 MOTOR LUBRICATION 8 5 0 FURNACE INFORMATION 9 TABLES Table 1 Supply air adjustment on heating mode 6 Table 2 Supply air adjustment on air cooling mode 6 Table 3 Technical speci...

Page 3: ...tch or circuit breaker ii The air filter and how to change it check monthly and clean or replace if necessary f Before calling for service be sure to have the information of section 5 of your manual c...

Page 4: ...o clearance to combustible material regardless of the heating capacity 2 2 2 Supply air ducts Ducts for furnaces with a heating capacity up to and including 20 k W can be installed with a zero clearan...

Page 5: ...acement these must be copper wires only with same temperature rating as originals 2 5 INSTALLATION OF THE THERMOSTAT A thermostat must be installed to control the temperature of the area to be heated...

Page 6: ...no way hinder access to the furnace panels 2 6 SUPPLY AIR ADJUSTMENTS On units equipped with 4 speed blower motors the supply air must be adjusted based on heating air conditioning output and the stat...

Page 7: ...door is in place and the blower rail locking screws are well tightened 3 The blower speed adjustments for heating and air conditioning are appropriate and according to the specifications in this manu...

Page 8: ...certain that the unit does not operate above the temperatures specified in the Technical Specifications Table 2 This is particularly important if a cooling coil or a heat pump has been installed in th...

Page 9: ...ler name and address START UP RESULTS Voltage Total current consumed by the elements Supply air temperature Return air temperature Supply air duct static pressure Return air duct static pressure Total...

Page 10: ...nd size Shipping weight Maximum cooling capacity ELECTRICAL SYSTEM GENERAL INFORMATION BLOWER DATA factory adjusted to a staic pressure of 0 5 W C 1 20 x 20 3 tons SUPxx M2401B 19 x 19 12 x 10 2 Calcu...

Page 11: ...11 Figure 9 Furnace dimensions...

Page 12: ...12 Figure 10 Wiring diagram 3 wires 10 kW...

Page 13: ...13 Figure 11 Wiring diagram 3 wires 15 kW...

Page 14: ...14 Figure 12 Wiring diagram 3 wires 18 20 kW...

Page 15: ...15 Figure 13 Wiring diagram 3 wires 23 kW...

Page 16: ...16 Figure 14 Wiring diagram 3 wires 27 kW...

Page 17: ...17 Figure 15 PARTS LIST Supreme with 1 3 HP and 1 HP motor SUPxx M2401A or SUPxx M2401B B50130A dwg...

Page 18: ...L 22A B04125 ELECTRICAL KIT 10kw 22B B04124 ELECTRICAL KIT 15kw 22C B04123 ELECTRICAL KIT 18 20kw 22D B04122 ELECTRICAL KIT 23 25kw 22E B04121 ELECTRICAL KIT 27kw 23 B04091 MOUNTING PLATE FOR ELECTRIC...

Reviews: