17
Tableau 11: Dipswitch Furnace User Menu
Dipswitch*
Dip Switch
Indications
Comments
Cool Airflow
XXXXCFM
Airflow Dipswitch Settings
Heat Rise
Nom, Nom+10
Heat Rise Airflow Settings
Hi Heat Adj
-15%, -7%, 0%, 7%, 15%
High Heat Airflow Settings
Lo Heat Adj
-15%, -7%, 0%, 7%, 15%
Low Heat Airflow Settings
Fan Spd Select
Lo, Hi
Fan Speed Settings
AC-HP Adj
-10%, 0%, 10%
Heat Pump AC Airflow Settings
On-Demand Dehum
On, Off
Dehumidification Settings
Test Mode
Off, 40% (70%), 100%
Test Mode Settings
AC HP Stg Mult
NA, 50%, 75%
Heat Pump AC Stage Multiplier
* Dipswitch status is not required when the system is set up for 4-wire communications. It is only displayed
when a conventional 24V thermostat input is active.
7.6- AIR HANDLER USER MENUS
“X” in the following tables indicate alpha or numeric character.
Tableau 12: Status Air Handler User Menu
Status
Parameter
Indications
Comments
Auxiliary Heat
On, Off
Auxiliary Heat Status
Blower CFM
CFMXXXX
Air Handler Blower CFM
Motor Mfgr
Rgblt, Emerson
Blower Motor Manufacturer
Motor RPM
RPMXXXX
Blower Motor RPM
Maximum CFM
CFMXXXX
Maximum CFM of the Air Handler
Temp Rise
NA, XXXF, FLT
Difference Between the Supply and
Return Air Temperature (NA if either sensor
is disabled)
Return Temp
NA (if disabled),
XXXF, FLT
Displays Return Air Temperature
(if installed and enabled in Setup)
Supply Temp
NA (if disabled),
XXXF, FLT
Displays Supply Air Temperature
(if installed and enabled in Setup)
Tableau 13: Fault History Air handler User Menu
Fault History (FAULT HIST)
Fault Code
Fault Occurred
Comments
XXXXXXXXXXXXXXX
Days XX
Displays up to 6 Faults; Days (XX)
indicates how many days ago the fault
occurred
Clear Faults
No, Yes