Dettson R02P029 Installation And Operating Instructions Manual Download Page 9

 

 

Select  humidifier  pad  maintenance  reminder

Scrolling  message  will  show 

HUMIDIFIER  PAD 

MAINTENANC

e”.  Default  is  OFF.  It  can  be 

changed  to  a  setting  from  25  to  1975  hours  in 
increments  of  25  hours  to  select  the  amount  of 
time  for  the  reminder.  Setting  of  100  hours  is 
typically 6 months of run time. 

Based on this setting, the scrolling message area 
will  show  “

CHANGE  HUMIDIFIER  PAD

”  to 

indicate maintenance is required. 

 

6- USING THE THERMOSTAT 

6.1-  SYSTEM OPERATION 

 

Touch  the 

SYSTEM

  key  to  select  the  thermostat 

operating mode desired. The setpoint temperature 
can be changed by touching the 

 or 

 keys. 

6.2-  AUXILIARY HEATING 

6.2.1- 

Heat Pump Disable 

This feature  is applicable  only  when a heatpump 
is  connected  on  the  communication  network. 
When this feature is selected, the thermostat  will 
switch to electric heat and shut off the compressor 
when the outside temperature falls below the HP 
balance point. In the Thermostat User Menu, use

 

 or 

  to select the temperature which can 

be between 5 to 50°F. 

6.2.2- 

Dual Fuel System Disable 

This feature  is applicable  only  when a heatpump 
is  connected  on  the  communication  network. 
When this feature is selected, the thermostat  will 
switch  to  fossil  fuel  heat  and  shut  off  the 
compressor  when  the  outside  temperature  falls 
below  the  DF  balance  point.  In  the  Thermostat 

User Menu, use 

 or 

  to 

select 

the 

temperature which can be between 5 to 50°F. 

6.2.3- 

Air Handler Lockout Temperature 

This feature  is  applicable only  when a heatpump 
is connected on the communication network  with 
electric  auxiliary  heat.  When  the  outdoor 
temperature  is  above  the  Air  Handler  Lockout 
Temperature  balance  point,  the  auxiliary  heat 
stage(s) will be inhibited so the thermostat setpoint 
will be maintained by only the heat pump. Factory 
default  is  OFF  which  disables  the  feature.  The 
Lockout  Setpoint  cannot  be  set  at  or  below  the 
Heat  Pump  Disable  (HP)  balance  point.  In  the 

Thermostat User Menu, use 

 or 

 to select the 

temperature which can be between the Heat Pump 
Disable setting value (HP) to 95°F. 

6.3-  PERMANENT TEMPERATURE 

HOLD 

The  Permanent  Temperature  Hold  feature 
bypasses the program and allows you to adjust the 
temperature 

manually 

as 

needed. 

The 

temperature  you  set  in  HOLD  will  be  maintained 
indefinitely. Touch 

Run Schedule

 to cancel HOLD 

and resume the programmed schedule. Touch 

 

or 

  keys  to  adjust  the  temperature.  The 

Hold

 

key will appear on the screen. Touch the 

Hold

 key 

to  maintain  the  new  setpoint  temperature.  ”

Hold 

At

”  will  display  to  the  left  of  the  temperature 

setpoint. To cancel the permanent hold setting at 
any  time  and  return  to  the  program,  touch 

Run 

Schedule

E

XAMPLE

:  If  you  turn  up  the  heat  during  the 

Morning  program  and  touch  the  Hold  key,  it  will 
remain at the new temperature until you touch 

Run 

Schedule

  or  you  manually  adjust  to  another 

temperature. 

6.4-  NORMAL MODE 

If Program days per week is set for 0 Days (Normal 
mode)  in  the  Thermostat  Options  Configuration 
Menu, the thermostat will not follow any program 
periods.  Time  of  day  and  day  of  week  will  not 
display. Touch the 

SYSTEM

 key to select Heat or 

Cool  and  use  the 

  or 

  buttons  to  adjust  the 

temperature to your desired setting. 

 

Summary of Contents for R02P029

Page 1: ...ATION AND OPERATING INSTRUCTIONS Communicating Touchscreen Thermostat Model R02P029 FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND OR PROPERTY DAMAGE ...

Page 2: ...Using the Thermostat 9 6 1 System Operation 9 6 2 Auxiliary Heating 9 6 2 1 Heat Pump Disable 9 6 2 2 Dual Fuel System Disable 9 6 2 3 Air Handler Lockout Temperature 9 6 3 Permanent Temperature Hold 9 6 4 Normal Mode 9 6 5 Auto Mode 10 6 6 Choose the Fan Setting Auto or On 10 6 7 Check System Status 10 6 8 Maintenance Reminder Message 10 7 Advanced Installer Configuration Menu10 7 1 Entering and ...

Page 3: ...nu 18 Tableau 16 Unit Info Air Handler User Menu 18 Tableau 17 Setup Air Handler User Menu 18 Tableau 18 Dipswitch Air Handler User Menu18 Tableau 19 Status Het Pump User Menu 19 Tableau 20 Fault History Heat Pump User Menu 19 Tableau 21 2 week History Heat Pump User Menu 19 Tableau 22 Life History Heat Pump User Menu 19 Tableau 23 Unit Info Heat Pump User Menu 20 Tableau 24 Cool Setup Heat Pump U...

Page 4: ...es clean up any spilled mercury and place in a sealed container For proper disposal of a product containing mercury or a sealed container of spilled mercury place it in a suitable shipping container Refer to www thermostat recycle org or www switchthestat ca for location to send product containing mercury 3 INSTALLATION This document provides information for installation of the touchscreen thermos...

Page 5: ...thermostat up with the base and snap into place NOTE Push excess wire into the wall to prevent any interference when attaching the thermostat to the base ensuring a good connection to the terminals 4 POWER UP Turn on AC power to the system The thermostat will automatically identify the communicating components installed 4 1 MESSAGE AT THERMOSTAT During power up the thermostat will scroll the word ...

Page 6: ...to adjust thermostat setting above room temperature The cooling system should stop operating 5 THERMOSTAT SETUP 5 1 SET CURRENT TIME AND DAY On Home Screen Display touch the menu key to display additional key choices Touch Set Time once to display hour and AM or PM designation in clock display Touch either the or key until you reach the correct hour and AM or PM designation Then touch Set Time aga...

Page 7: ...y additional key choices Touch and hold the Installer Config key for 3 seconds This displays the first menu item as shown in the next step Touch or to change a menu option Touch to advance to the next menu item or to return to the previous menu item Touch Run Schedule at any time to exit the menu and return to Home Screen Display Select continuous FAN speed Default is Medium It can be set to High ...

Page 8: ...per to indicate a touch key selection It can be changed to OFF Select air filter maintenance reminder Scrolling message will show AIR FILTER MAINTENANCE Default is OFF It can be changed to a setting from 25 to 1975 hours in increments of 25 hours to select the amount of time for the reminder Consult your installer for the hours and type of filter When the system has run for the selected length of ...

Page 9: ...pump is connected on the communication network with electric auxiliary heat When the outdoor temperature is above the Air Handler Lockout Temperature balance point the auxiliary heat stage s will be inhibited so the thermostat setpoint will be maintained by only the heat pump Factory default is OFF which disables the feature The Lockout Setpoint cannot be set at or below the Heat Pump Disable HP b...

Page 10: ...layed refer to the Advanced Installer Configuration Menu Fault status If the thermostat indicates Call for Service with CHECK SYSTEM the indoor unit is not detected or has failed to communicate 6 8 MAINTENANCE REMINDER MESSAGE A reminder will display in the scrolling message area when it is time for accessory maintenance if selected in the Thermostat Options Configuration Menu When a reminder appe...

Page 11: ...LTS or will show a description of the fault with an error code in the temperature display area Touch or keys to view the fault status of each piece of equipment connected To change the display to the Equipment User Menu touch or 7 3 EQUIPMENT USER MENUS The equipment found in the system will display in the scrolling message area Touch or to step through the list of equipment connected including th...

Page 12: ...ow WORKING then change to the first parameter on the equipment submenu Settings for the parameter will also appear on the display Touch or to step through the items of the equipment submenu and view settings If a setting can be adjusted the or keys will appear Change the setting as required Then touch or to step to the next item WORKING will appear and then the display will show Done to indicate t...

Page 13: ... HIST Displays information on the lifetime number of hours of unit mode operation and the number of cycles the unit has operated in Unit Info On new system installations displays the model number and serial number of the selected unit If a control has been replaced the equipment will be recognized but will only show the unit model number Setup Used to display or modify equipment settings Dipswitch...

Page 14: ...r handler with heat pump systems Disables electric heat above the selected outdoor temperature OFF defaults to 50 F equipment _ Test No Yes Steps the selected equipment through its sequential mode of operation Reset System No Yes This will reset ALL of the communicating system components to their factory set values 7 5 FURNACE USER MENUS X in the following tables indicate alpha or numeric characte...

Page 15: ...pply Temp NA If disabled XXXF FLT Displays Supply Air Temp if installed and enabled in setup HUM Output On Off Humidifier Output Relay Status EAC Output On Off Electronic Air Cleaner Output Relay Status Tableau 6 Fault History Furnace User Menu Fault History FAULT HIST Fault Code Fault Occurred Comments XXXXXXXXXXXXXXX Days XX Displays up to 6 Faults Days XX indicates how many days ago the fault o...

Page 16: ... Days Pwrd XXXX Total number of days control has been powered Lo HT Hrs XXXXXX Low Heat Hours of Operation Lo HT Cycles XXXXXX Low Heat Cycles Hi HT Hrs XXXXXX High Heat Hours of Operation Hi HT Cycles XXXXXX High Heat Cycles Y1 Hrs XXXXXX First Stage Cooling Heat Pump Hours of Operation Y1 Cycles XXXXXX First Stage Cooling Heat Pump Cycles Y2 Hrs XXXXXX Second Stage Cooling Heat Pump Hours of Ope...

Page 17: ...n the following tables indicate alpha or numeric character Tableau 12 Status Air Handler User Menu Status Parameter Indications Comments Auxiliary Heat On Off Auxiliary Heat Status Blower CFM CFMXXXX Air Handler Blower CFM Motor Mfgr Rgblt Emerson Blower Motor Manufacturer Motor RPM RPMXXXX Blower Motor RPM Maximum CFM CFMXXXX Maximum CFM of the Air Handler Temp Rise NA XXXF FLT Difference Between...

Page 18: ... Control Software Version Tableau 17 Setup Air Handler User Menu Setup Parameter Options Comments Return Air Sense Off On If Return Air Sensor is field installed turn On Factory Default is Off Supply Air Sense Off On If Supply Air Sensor is field installed turn On Factory Default is Off Stage Aux Heat Off On If W1 and W2 staging is desired W1 W2 jumper must be removed from heater kit then turn On ...

Page 19: ...ion 2wk Y1 Cycles XXXX 2 Week First Stage Cooling Cycles 2wk Y2 Hrs XXX 2 Week Second Stage Cooling Hours of Operation 2wk Y2 Cycles XXXX 2 Week Second Stage Cooling Cycles 2wk Lo HT Hrs XXX 2 Week First Stage Heat Pump Hours of Operation 2wk Lo HT Cycls XXXX 2 Week First Stage Heat Pump Cycles 2wk Hi HT Hrs XXX 2 Week Second Stage Heat Pump Hours of Operation 2wk Hi HT Cycls XXXX 2 Week Second St...

Page 20: ... See Heat Pump Installer Guide Heat Air Adj 10 0 10 Selectable Heat Pump Airflow Adjustments Dfrost Cmpr Dly 0 5 Selectable Compressor Delay during defrost Reset All Dflts No Yes Resets the Heat Pump to the Factory Default Configuration by selecting Yes HP Staging Multi Stage Units Only On Off For Multi Stage Heat Pumps Factory Default is On This allows Low High stages of capacities To only allow ...

Page 21: ...XXXXXX First Stage Cooling Hours of Operation Y1 Cycles XXXXXX First Stage Cooling Cycles Y2 Hrs XXXXXX Second Stage Cooling Hours of Operation Y2 Cycles XXXXXX Second Stage Cooling Cycles Tableau 30 Unit Info Air Conditioner User Menu Unit Info Parameter Indications Comments Model Number XXXX XXXXXXXXXXXXXXXX Unit Model Number Serial Number XXXXXXXXXXXXXXXXXXX Unit Serial Number not available if ...

Page 22: ...ressure switch closed inducer off 45 Low pressure switch open inducer on high speed 46 Low pressure switch open inducer on low speed 55 High pressure switch closed inducer off 57 High pressure switch open inducer on high speed 60 Blower Fault Run 61 Blower Fault No Run 66 RPM out of range over 1200 RPM 68 No Blower Communication 77 Servo circuit open 78 Servo control fault 79 No Gas Valve Feedback...

Reviews: