background image

 

 

5

 

Figure 3:  Thermostat Wiring- Heating & Air Conditioning - 

With ECM Variable Speed Motor 

 

Figure 4:  Thermostat Wiring-Heating &Air 

Conditioning/HeatPump - With ECM Variable Speed Motor 

 

2.4 

INSTALLATION OF THE BURNER 

Also refer to the burner manufacturer’s instructions. 

1.  Position  the  mounting  gasket  between  the  mounting 

flange  and  the  burner  mounting  plate.  Align  the  holes  in 
the burner mounting plate with the studs on the mounting 
flange and bolt securely in place. 

2.  Remove  the  burner  drawer  assembly  or  the  air  tube 

assembly; 

3.  Install the nozzle (refer to Technical Specifications, p.13); 

4.  Check the electrode settings; 

5.  Make the electrical connections; 

6.  Complete oil line connections. 

2.4.1 

Nozzles 

The  burner  comes  equipped  with  an  appropriate  nozzle. 
However,  if  another  size  or  a  replacement nozzle is required, 
use the manufacturer’s recommended spray angle and type a 
shown in Table 1 and based on a pump pressure of 100 psi.

 

Always  select  nozzle  sizes  by  working  back  from  the  desired 
flow rate at operating pressure and not the nozzle marking. 

2.4.2 

Air and Turbulator Settings 

Before  starting  the  burner  for  the first time, adjust the air 
and  turbulator  settings  to  those  listed  in  this  manual. 
Once  the  burner  becomes  operational,  final  adjustments 
will be required. Refer to section 3 of this manual. 

2.4.3 

Post purge delay adjustment 

The post purge delay on the oil-fired burners is factory set 
to  zero  second.  This  delay  is  applicable  for  all 
installations  with  chimney  venting.  For  heating  units 
installed with side wall venting and burners equipped with 
this  feature,  the  post  purge  delay  must  be  set  to  15 
seconds. No delay is required for Riello burners. Refer to 
the  burner  control  instruction  manual  and  markings  for 
proper adjustment of the post purge delay. 

2.5 

VENTING 

WARNING

 

Poisonous carbon monoxide gas hazard. 

Never install a hand operated damper in the vent 

pipe. However, any Underwriters Laboratories listed, 

electrically operated automatic type vent damper may 

be installed if desired. Be sure to follow the 

instructions provided with vent damper. Also, read 

and follow all instructions in this section of the 

manual. 

Failure  to  properly  vent  this  furnace  or  other 
appliances  can  result  in  death,  bodily  injury  and/or 
property damage. 

To  ensure  the  safe  and  proper  functioning  of  an  oil 
furnace,  it  must  always  be  connected  to  a  flue  with 
sufficient  draft  or  to  an  approved  side-wall  venting 
system.  In  addition,  it  is  strongly  recommended  to 
perform  a  complete  inspection  of  all  the  existing  venting 
systems. 

2.5.1 

Masonry chimney 

This  furnace  can  be  vented  into  an  existing  masonry 
chimney.  However,  the  unit  must  not  be  vented  into  a 
chimney into which a solid fuel burning furnace is already 
being vented. 

Before  venting  this  furnace  into  a  chimney,  its  condition 
must  be  checked  and  repairs  made,  if  necessary.  Also, 
the chimney lining and dimensions must conform to local 
and national codes. 

2.5.2 

Factory Built Chimneys 

Oil  fired  furnaces  are  approved  for  use  with  “L”  type 
vents.  The  unit  may  also  be  used  with  an  approved 
chimney of proper dimensions and temperature ratings as 
specified  in  the  installation  code.  Refer  to  chimney 
manufacturer’s instructions for proper installation. 

2.5.3 

Draft Regulator 

This unit may be installed with or without a draft regulator. 
However,  it  is  recommended  that  a  draft  regulator  be 
installed in cases where the draft is either high or variable 
due  to  external  conditions.  Follow  the  instructions 
provided with the regulator. 

Summary of Contents for OLR154F20A

Page 1: ...RMATION IN THIS MANUAL FOR THE INSTALLATION SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE At...

Page 2: ...ly air Temperature Rise Test 10 3 3 8 Limit Control Check 10 3 3 9 Restart after burner failure 10 4 MAINTENANCE 10 4 1 CLEANING THE HEAT EXCHANGER 10 4 2 CLEANING THE BLOCKED VENT SHUT OFF DEVICE BVS...

Page 3: ...formation such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must conform...

Page 4: ...re the ambient and return air temperatures are above 15 C 60 F In addition the furnace should be installed as closely as possible to the vent so that the connections are direct and kept to a minimum T...

Page 5: ...ired for Riello burners Refer to the burner control instruction manual and markings for proper adjustment of the post purge delay 2 5 VENTING WARNING Poisonous carbon monoxide gas hazard Never install...

Page 6: ...adequate supply of combustion air It is common practice to assume that older homes have sufficient infiltration to accommodate the combustion air requirement for the furnace However home improvements...

Page 7: ...ated the return air must be sealed and also be directed to the space other than where the furnace is located 2 9 1 Air filter A properly sized air filter must be installed on the return air side of th...

Page 8: ...heating or air conditioning mode This signal can be used to activate an electronic air cleaner that is not equipped with an air flow switch If the cleaner is equipped with an air flow switch the S te...

Page 9: ...of the oil piping and pump Slowly close and tighten the bleed screw Once closed the flame will light up 3 3 2 Pressure adjustment The oil pressure must be adjusted according to the Technical Specifica...

Page 10: ...burner should restart after a few minutes The time required for the restart also depends on the adjustment of the blower OFF delay 3 3 9 Restart after burner failure 1 Set the thermostat lower than r...

Page 11: ...uction inside the heat transfer tube 7 Re mount lock and fasten the control box with the 2 screws removed in step 4 8 Re attach the assembly cover with the screws removed in step 2 9 Re establish powe...

Page 12: ...vice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Amb...

Page 13: ...n 87 5 86 2 87 5 86 2 Volts Hertz Phase Rated current Amps Minimum ampacity for wire sizing Amps Max fuse size Amps Control transformer VA External control power available Heating VA Cooling VA Heatin...

Page 14: ...Time ShortRun On Delay CFM Level Time Off Delay CFM Level Time A 1 OFF 2 OFF 0 90 13 45 sec 44 30 sec 38 3 min B 1 ON 2 OFF 1 10 13 30 sec 44 30 sec 38 3 min C 1 OFF 2 ON 1 10 13 30 sec 50 30 sec 38...

Page 15: ...WITH AIR FILTER Table 10 Minimum clearances from combustible material LOCATION APPLICATION CLEARANCES combustible materials RECOMMANDED ACCESS FOR SERVICE FURNACE 2 54 cm 1 0 6 m 24 SUPPLY PLENUM WIT...

Page 16: ...16 Figure 7 Furnace Dimensions...

Page 17: ...17 Figure 8 Wiring Diagram 4 Speed Motor PSC...

Page 18: ...18 Figure 9 Wiring Diagram Variable Speed Motor ECM...

Page 19: ...19 Figure 10 Parts List With 4 Speed motor PSC B50095B...

Page 20: ...TERIOR 33 F06F015 ZINC WASHER 1 7 16 34 Z99F061 SIGHT GLASS FOR HEAT EXCHANGER 35 Z06G001 BLOCKED VENT SHUT OFF BVSO 225 36 B03675 GASKET SMOKE OUTLET 37 B03765 CLEAN OUT ASSEMBLY Item 36 included 38...

Page 21: ...21 Figure 11 Parts List With variable speed motor ECM B50096C...

Page 22: ...ELECTRICAL BOX COVER Panel only 32 B03118 01 ELECTRICAL KIT BVSO EXTERIOR 33 F06F015 ZINC WASHER 1 7 16 34 Z99F061 SIGHT GLASS FOR HEAT EXCHANGER 35 Z06G001 BLOCKED VENT SHUT OFF BVSO 225 36 B03675 G...

Page 23: ...NICIEN UTILISER LES RENSEIGNEMENTS DANS CE MANUEL POUR L INSTALLATION ENTRETIEN DE L APPAREIL ET GARDER LE DOCUMENT PR S DE L UNIT POUR R F RENCES ULT RIEURES PROPRI TAIRE S V P GARDER CE MANUEL PR S...

Page 24: ...rture de ventilation dans la porte du placard 4 Figure 2 Branchement du thermostat Chauffage et climatisation Unit avec moteur 4 vitesses 5 Figure 3 Branchement du thermostat Chauffage et Climatisatio...

Page 25: ...onduit comment le changer une fois par ann e iv Le filtre air comment le changer v rifier mensuellement et nettoyer ou changer si n cessaire g Avant d appeler pour le service prendre en note les rense...

Page 26: ...s doit tre utilis e 2 1 EMPLACEMENT MISE EN GARDE Risque d incendie ou d explosion L appareil doit tre install au niveau Ne jamais installer avec une inclinaison vers l avant Ne pas ranger ou utiliser...

Page 27: ...ils d origine de l appareil de chauffage central utilisez seulement du fil de cuivre r sistant la m me temp rature que les fils d origine 2 3 INSTALLATION DU THERMOSTAT L installation d un thermostat...

Page 28: ...ajustement 2 5 VACUATION MISE EN GARDE Risque d empoisonnement par monoxyde de carbone Lire et suivre toutes les instructions contenues dans cette section Ne jamais installer un volet manuel sur le tu...

Page 29: ...usqu la fin du cycle de refroidissement Si le fonctionnement n est pas conforme APPELER UN TECHNICIEN QUALIFI 2 7 APPROVISIONNEMENT EN AIR DE COMBUSTION ET VENTILATION MISE EN GARDE Risque d empoisonn...

Page 30: ...oir avec une pompe appropri e une l vation de 2 4 m 8 et plus requi re une pompe deux stages et une l vation de plus de 4 9 m 16 une pompe auxiliaire Suivre les directives d installation de la pompe p...

Page 31: ...fonction de la puissance de chauffage et de climatisation Les d lais de d part et d arr t du ventilateur en mode chauffage doivent aussi tre ajust s en positionnant les interrupteurs DIP du contr le...

Page 32: ...ence Moteur vitesse variable ECM Si le moteur de soufflerie ECM s av re d fectueux et qu un rechange n est pas disponible imm diatement vous pouvez remplacer temporairement le moteur de la soufflerie...

Page 33: ...dans le tuyau de raccordement environ 18 pouces de la bride d vacuation de la fournaise Pour les installations avec une vacuation murale utiliser l orifice pr vu cet effet 2 Suite un d part froid lais...

Page 34: ...azout accumul des vapeurs de mazout ou que la chambre combustion est tr s chaude 4 ENTRETIEN MISE EN GARDE Risque de d charge lectrique Avant d effectuer des travaux d entretien FERMER l alimentation...

Page 35: ...rupteur thermique Un interrupteur thermique endommag doit tre remplac 6 Nettoyer et enlever toute accumulation de salet ou obstruction de l int rieur du tube de transfert de chaleur 7 Remonter verroui...

Page 36: ...dresse du technicien de service R SULTAT DU TEST DE MISE EN MARCHE Gicleur Pression lb po2 Ajustements du br leur Bande principale Bande secondaire Position de la t te CO2 Indice de fum e Bacharach Te...

Page 37: ...103 et des lois am ricaines 87 5 86 2 87 5 86 2 Volts Hertz Phase Consommation Amp Amp minimum pour grosseur du fil Amp Fusible max Amp Contr le du transformateur VA Courant disponible contr les exter...

Page 38: ...n Niveau PCM Temps D lai Off Niveau PCM Temps A 1 OFF 2 OFF 0 90 13 45 sec 44 30 sec 38 3 min B 1 ON 2 OFF 1 10 13 30 sec 44 30 sec 38 3 min C 1 OFF 2 ON 1 10 13 30 sec 50 30 sec 38 3 min D 1 ON 2 ON...

Page 39: ...XTERNE AVEC FILTRE AIR Table 10 D gagement minimum mat riaux combustibles EMPLACEMENT APPLICATION D GAGEMENTS mat riaux combustibles ACC S RECOMMAND POUR L ENTRETIEN FOURNAISE 2 54 cm 1 0 6 m 24 PL NU...

Page 40: ...18 Figure 7 Dimensions de la fournaise...

Page 41: ...____________________________________________________________________________________ 19 Figure 8 Diagramme lectrique Moteur 4 vitesses PSC...

Page 42: ...20 Figure 9 Diagramme lectrique Moteur vitesse variable ECM...

Page 43: ...____________________________________________________________________________________ 21 Figure 10 Liste de pi ces Avec moteur 4 vitesses PSC B50095B...

Page 44: ...DELLE ZINC 1 7 16 34 Z99F061 OEIL DE REGARD POUR CHANGEUR 35 Z06G001 DISPOSITIF D ARR T BVSO 225 36 B03675 GARNITURE SORTIE FUM E 37 B03765 ASS BRIDE DE NETTOYAGE Comprend item 36 38 B03762 ASS COUVER...

Page 45: ...____________________________________________________________________________________ 23 Figure 11 Liste de pi ces Avec moteur vitesse variable ECM B50096C...

Page 46: ...ITE LECTRIQUE Panneau seulement 32 B03118 01 KIT LECTRIQUE BVSO EXT RIEUR 33 F06F015 RONDELLE ZINC 1 7 16 34 Z99F061 OEIL DE REGARD POUR CHANGEUR 35 Z06G001 DISPOSITIF D ARR T BVSO 225 36 B03675 GARNI...

Reviews: