background image

 

 

6

 

 

 

2.5.4 

Side-wall venting 

The heating unit is approved for side-wall venting. This system 
includes  model  VTK-65  /  VTK-3  /  KLAVT0201DET  side-wall 
venter  and  a  5”  insulated  vent  pipe,  model  IFV5xx  / 
KLAFVxx01DET. Refer to the installation instructions provided 
with the venting system. 

2.6 

BLOCKED VENT SHUT-OFF DEVICE (BVSO) 
FOR CHIMNEY VENTING 

CAUTION 

It  is  imperative  that  this  device  be  installed  by  a  qualified 
service technician. 

A  positive  pressure  venting  system  (Sealed  Combustion 
System or Direct Vent) 

MUST NOT

 uses the BVSO. Follow the 

instructions supplied with the venting system. 

This device is designed to detect the insufficient evacuation of 
combustion  gases  in  the  event  of  a  vent  blockage.  In  such  a 
case  the  thermal  switch  will  shut  down  the  oil  burner.  The 
device will then need to be re-armed MANUALLY.

 

Refer to the detailed instructions and wiring diagrams supplied 
with the BVSO for the installation and wiring procedures.  The 
length  of  wires  supplied  with  the  unit  is  such  that  the  safety 
device  must  be  installed  between  the  flue  outlet  of  the 
appliance  and  the  draft  regulator,  as  indicated  in  the 
instructions. 

It is also essential that the BVSO be maintained annually. For 
more  details  refer  to  the  instructions  supplied  with  the  device 
itself, as well as Section 3 of this Manual. 

2.6.1 

BVSO Functional Test 

The  purpose  of  the  following  test  is  only  to  check  that  the 
electrical  outlet  on  the  furnace,  designated  to  the  BVSO,  is 
functional. 

1.  Start up the burner; 
2.  Remove the three-pole plug from the BVSO outlet on the 

furnace; 

3.  The  burner  must  shut-off  immediately,  while  the  blower 

continues to run to the end of the cool-down cycle. 

If  the  test  is  not  in  line  with  the  above,  call  a  QUALIFIED 
SERVICE TECHNICIAN. 

2.7 

COMBUSTION AIR SUPPLY 
AND VENTILATION 

WARNING

 

Poisonous carbon monoxide gas hazard. 

Comply  with  NFPA  31  (U.S.)  and  CSA  B139  (Canada) 
standards  for  the  installation  of  Oil  Burning  Equipment 
and  applicable  provisions  of  local  building  codes  to 
provide combustion and ventilation air. 

Failure  to  provide  adequate  combustion  and  ventilation 
air  can  result  in  death,  bodily  injury  and/or  property 
damage. 

Oil furnaces must have an adequate supply of combustion air. 
It  is  common  practice  to  assume  that  older  homes  have 
sufficient  infiltration  to  accommodate  the  combustion  air 
requirement  for  the  furnace.  However,  home  improvements 

such as new windows, doors, and weather stripping have 
drastically  reduced  the  volume  of  air  infiltration  into  the 
home.

 

 

Refer  to  oil  furnace  installation  codes  relative  to 
combustion  and  ventilation  air  requirements.  Consult 
Section  2.1  in  this  manual,  specifically  for  units  installed 
in an enclosed space.  

 

Home air exhausters are common. Bathroom and kitchen 
fans,  power  vented  clothes  dryers  and  water  heaters  all 
tend to create a negative pressure condition in the home. 
Should  this  occur  the  chimney  becomes  less  and  less 
effective  and  can  easily  downdraft.  In  certain  cases, 
mechanically supplied air, by way of a blower, interlocked 
with  the  unit,  is  necessary.  It  is  the  installer’s 
responsibility to check that. 

2.7.1 

Contaminated Combustion Air 

Installations  in  certain  areas  or  types  of  structures  will 
increase the exposure to chemicals or halogens that may 
harm  the  furnace.  These  conditions  will  require  that  only 
outside air be used for combustion. 

The following areas or types of structures may contain or 
be  exposed  to  certain  substances,  potentially  requiring 
outside air for combustion: 

 

a.  Commercial buildings; 
b.  Buildings with indoor pools; 
c. 

Furnaces installed near chemical storage areas. 

Exposure to the following substances: 

a.  Permanent wave chemicals for hair; 
b.  Chlorinated waxes and cleaners; 
c. 

Chlorine based swimming pool chemicals; 

d.  Water softening chemicals; 
e.  De-icing salts or chemicals; 
f. 

Carbon tetrachloride; 

g.  Halogen type refrigerants; 
h.  Cleaning solvents (such as perchloroethylene); 
i. 

Printing inks, paint removers, varnishes, etc. ; 

j. 

Hydrochloric acid; 

k. 

Solvent based glue; 

l. 

Antistatic fabric softeners for clothes dryers; 

m.  Acid based masonry cleaning materials. 

2.7.2 

Burner with Outdoor Combustion Air Kit 

Certain burners are designed to function with combustion 
air taken directly from the outside. Follow the instructions 
provided  with  the  burner,  the  fresh-air  supply  kit  or  the 
side-wall venting kit. 

2.8 

OIL TANK 

WARNING

 

Fire and explosion hazard. 

Use  only  approved  heating  type  oil  in  this 
furnace. DO NOT USE waste oil, used motor oil, 
gasoline or kerosene. 

Use  of  these  will  result  in  death,  bodily  injury 
and/or property damage. 

Summary of Contents for OLR154F20A

Page 1: ...RMATION IN THIS MANUAL FOR THE INSTALLATION SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE At...

Page 2: ...ly air Temperature Rise Test 10 3 3 8 Limit Control Check 10 3 3 9 Restart after burner failure 10 4 MAINTENANCE 10 4 1 CLEANING THE HEAT EXCHANGER 10 4 2 CLEANING THE BLOCKED VENT SHUT OFF DEVICE BVS...

Page 3: ...formation such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must conform...

Page 4: ...re the ambient and return air temperatures are above 15 C 60 F In addition the furnace should be installed as closely as possible to the vent so that the connections are direct and kept to a minimum T...

Page 5: ...ired for Riello burners Refer to the burner control instruction manual and markings for proper adjustment of the post purge delay 2 5 VENTING WARNING Poisonous carbon monoxide gas hazard Never install...

Page 6: ...adequate supply of combustion air It is common practice to assume that older homes have sufficient infiltration to accommodate the combustion air requirement for the furnace However home improvements...

Page 7: ...ated the return air must be sealed and also be directed to the space other than where the furnace is located 2 9 1 Air filter A properly sized air filter must be installed on the return air side of th...

Page 8: ...heating or air conditioning mode This signal can be used to activate an electronic air cleaner that is not equipped with an air flow switch If the cleaner is equipped with an air flow switch the S te...

Page 9: ...of the oil piping and pump Slowly close and tighten the bleed screw Once closed the flame will light up 3 3 2 Pressure adjustment The oil pressure must be adjusted according to the Technical Specifica...

Page 10: ...burner should restart after a few minutes The time required for the restart also depends on the adjustment of the blower OFF delay 3 3 9 Restart after burner failure 1 Set the thermostat lower than r...

Page 11: ...uction inside the heat transfer tube 7 Re mount lock and fasten the control box with the 2 screws removed in step 4 8 Re attach the assembly cover with the screws removed in step 2 9 Re establish powe...

Page 12: ...vice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Amb...

Page 13: ...n 87 5 86 2 87 5 86 2 Volts Hertz Phase Rated current Amps Minimum ampacity for wire sizing Amps Max fuse size Amps Control transformer VA External control power available Heating VA Cooling VA Heatin...

Page 14: ...Time ShortRun On Delay CFM Level Time Off Delay CFM Level Time A 1 OFF 2 OFF 0 90 13 45 sec 44 30 sec 38 3 min B 1 ON 2 OFF 1 10 13 30 sec 44 30 sec 38 3 min C 1 OFF 2 ON 1 10 13 30 sec 50 30 sec 38...

Page 15: ...WITH AIR FILTER Table 10 Minimum clearances from combustible material LOCATION APPLICATION CLEARANCES combustible materials RECOMMANDED ACCESS FOR SERVICE FURNACE 2 54 cm 1 0 6 m 24 SUPPLY PLENUM WIT...

Page 16: ...16 Figure 7 Furnace Dimensions...

Page 17: ...17 Figure 8 Wiring Diagram 4 Speed Motor PSC...

Page 18: ...18 Figure 9 Wiring Diagram Variable Speed Motor ECM...

Page 19: ...19 Figure 10 Parts List With 4 Speed motor PSC B50095B...

Page 20: ...TERIOR 33 F06F015 ZINC WASHER 1 7 16 34 Z99F061 SIGHT GLASS FOR HEAT EXCHANGER 35 Z06G001 BLOCKED VENT SHUT OFF BVSO 225 36 B03675 GASKET SMOKE OUTLET 37 B03765 CLEAN OUT ASSEMBLY Item 36 included 38...

Page 21: ...21 Figure 11 Parts List With variable speed motor ECM B50096C...

Page 22: ...ELECTRICAL BOX COVER Panel only 32 B03118 01 ELECTRICAL KIT BVSO EXTERIOR 33 F06F015 ZINC WASHER 1 7 16 34 Z99F061 SIGHT GLASS FOR HEAT EXCHANGER 35 Z06G001 BLOCKED VENT SHUT OFF BVSO 225 36 B03675 G...

Page 23: ...NICIEN UTILISER LES RENSEIGNEMENTS DANS CE MANUEL POUR L INSTALLATION ENTRETIEN DE L APPAREIL ET GARDER LE DOCUMENT PR S DE L UNIT POUR R F RENCES ULT RIEURES PROPRI TAIRE S V P GARDER CE MANUEL PR S...

Page 24: ...rture de ventilation dans la porte du placard 4 Figure 2 Branchement du thermostat Chauffage et climatisation Unit avec moteur 4 vitesses 5 Figure 3 Branchement du thermostat Chauffage et Climatisatio...

Page 25: ...onduit comment le changer une fois par ann e iv Le filtre air comment le changer v rifier mensuellement et nettoyer ou changer si n cessaire g Avant d appeler pour le service prendre en note les rense...

Page 26: ...s doit tre utilis e 2 1 EMPLACEMENT MISE EN GARDE Risque d incendie ou d explosion L appareil doit tre install au niveau Ne jamais installer avec une inclinaison vers l avant Ne pas ranger ou utiliser...

Page 27: ...ils d origine de l appareil de chauffage central utilisez seulement du fil de cuivre r sistant la m me temp rature que les fils d origine 2 3 INSTALLATION DU THERMOSTAT L installation d un thermostat...

Page 28: ...ajustement 2 5 VACUATION MISE EN GARDE Risque d empoisonnement par monoxyde de carbone Lire et suivre toutes les instructions contenues dans cette section Ne jamais installer un volet manuel sur le tu...

Page 29: ...usqu la fin du cycle de refroidissement Si le fonctionnement n est pas conforme APPELER UN TECHNICIEN QUALIFI 2 7 APPROVISIONNEMENT EN AIR DE COMBUSTION ET VENTILATION MISE EN GARDE Risque d empoisonn...

Page 30: ...oir avec une pompe appropri e une l vation de 2 4 m 8 et plus requi re une pompe deux stages et une l vation de plus de 4 9 m 16 une pompe auxiliaire Suivre les directives d installation de la pompe p...

Page 31: ...fonction de la puissance de chauffage et de climatisation Les d lais de d part et d arr t du ventilateur en mode chauffage doivent aussi tre ajust s en positionnant les interrupteurs DIP du contr le...

Page 32: ...ence Moteur vitesse variable ECM Si le moteur de soufflerie ECM s av re d fectueux et qu un rechange n est pas disponible imm diatement vous pouvez remplacer temporairement le moteur de la soufflerie...

Page 33: ...dans le tuyau de raccordement environ 18 pouces de la bride d vacuation de la fournaise Pour les installations avec une vacuation murale utiliser l orifice pr vu cet effet 2 Suite un d part froid lais...

Page 34: ...azout accumul des vapeurs de mazout ou que la chambre combustion est tr s chaude 4 ENTRETIEN MISE EN GARDE Risque de d charge lectrique Avant d effectuer des travaux d entretien FERMER l alimentation...

Page 35: ...rupteur thermique Un interrupteur thermique endommag doit tre remplac 6 Nettoyer et enlever toute accumulation de salet ou obstruction de l int rieur du tube de transfert de chaleur 7 Remonter verroui...

Page 36: ...dresse du technicien de service R SULTAT DU TEST DE MISE EN MARCHE Gicleur Pression lb po2 Ajustements du br leur Bande principale Bande secondaire Position de la t te CO2 Indice de fum e Bacharach Te...

Page 37: ...103 et des lois am ricaines 87 5 86 2 87 5 86 2 Volts Hertz Phase Consommation Amp Amp minimum pour grosseur du fil Amp Fusible max Amp Contr le du transformateur VA Courant disponible contr les exter...

Page 38: ...n Niveau PCM Temps D lai Off Niveau PCM Temps A 1 OFF 2 OFF 0 90 13 45 sec 44 30 sec 38 3 min B 1 ON 2 OFF 1 10 13 30 sec 44 30 sec 38 3 min C 1 OFF 2 ON 1 10 13 30 sec 50 30 sec 38 3 min D 1 ON 2 ON...

Page 39: ...XTERNE AVEC FILTRE AIR Table 10 D gagement minimum mat riaux combustibles EMPLACEMENT APPLICATION D GAGEMENTS mat riaux combustibles ACC S RECOMMAND POUR L ENTRETIEN FOURNAISE 2 54 cm 1 0 6 m 24 PL NU...

Page 40: ...18 Figure 7 Dimensions de la fournaise...

Page 41: ...____________________________________________________________________________________ 19 Figure 8 Diagramme lectrique Moteur 4 vitesses PSC...

Page 42: ...20 Figure 9 Diagramme lectrique Moteur vitesse variable ECM...

Page 43: ...____________________________________________________________________________________ 21 Figure 10 Liste de pi ces Avec moteur 4 vitesses PSC B50095B...

Page 44: ...DELLE ZINC 1 7 16 34 Z99F061 OEIL DE REGARD POUR CHANGEUR 35 Z06G001 DISPOSITIF D ARR T BVSO 225 36 B03675 GARNITURE SORTIE FUM E 37 B03765 ASS BRIDE DE NETTOYAGE Comprend item 36 38 B03762 ASS COUVER...

Page 45: ...____________________________________________________________________________________ 23 Figure 11 Liste de pi ces Avec moteur vitesse variable ECM B50096C...

Page 46: ...ITE LECTRIQUE Panneau seulement 32 B03118 01 KIT LECTRIQUE BVSO EXT RIEUR 33 F06F015 RONDELLE ZINC 1 7 16 34 Z99F061 OEIL DE REGARD POUR CHANGEUR 35 Z06G001 DISPOSITIF D ARR T BVSO 225 36 B03675 GARNI...

Reviews: