X-4
FLAME SENSITIVITY—
The detector has four adjustable sensitivity settings plus
transient arc rejection capabilities.
RESPONSE TIME—
The detector is selectable for a 0 to 7 second time
delay.
OUTPUTS—
Digital communication, transformer isolated (78.5 kbps).
SEPARATION DISTANCE (EQ2200UVHT only)—
Maximum separation distance between the UV detector
and the electronic module is 165 feet (50 meters).
VIBRATION—
Meets MIL SPEC 810C, method 514.2, curve AW.
DIMENSIONS—
See Figures X-4A and X–4B for the standard UV
detector. For the high temperature UV detector, see
Figures X-5A and X-5B (UV detector) and Figure X-6
(electronic module).
5.25 (13.3)
2.5 (6.4)
MOUNTING BASE
1/2 INCH NUT USED TO ADJUST
ELBOW TO DESIRED ANGLE
1-3/8 INCH NUT USED TO ROTATE
SWIVEL/DETECTOR ASSEMBLY
TO DESIRED POSITION
3/4 INCH NUT USED TO SECURE
DETECTOR TO SWIVEL MOUNT
DETECTOR SCREWS ONTO
SWIVEL MOUNT HERE
A1886
2.5 (6.4) DIA.
0.25 (.64) (3)
120
°
±
2
°
(2)
2.0 (5.0) DIA.
Figure X–4A—Dimensions of Optional Swivel Assembly
in Inches (Centimeters)
Figure X–5A—Q9001B Swivel Mounting Bracket Dimensions
in Inches (Centimeters)
5/16-18 UNC
1 3/8 INCH GLAND NUT
USED TO ROTATE
SWIVEL/DETECTOR ASSEMBLY
TO DESIRED POSITION
MOUNTING BASE
DETECTOR LOCK NUT
120
°
±
2
°
(2)
2.0 (5.08) DIA.
2.5 (6.4) DIA.
0.25 (0.64) DIA. (3)
2.5
(6.4)
2.5
(6.4)
A1986
Figure X–5B—UV Detector Dimensions
in Inches (Centimeters)
4.75 (12.06)
2.5
(6.35)
1/2 INCH NPT
OR 20 MM
A1987