Section VII
System Wiring
NOTE
Specific installation requirements may differ
depending on local installation practices and
compliance with third party certifications. For local
installation practices, consult the local authority
having jurisdiction. For compliance with third party
certifications, consult the appropriate appendix in
this manual for additional specific installation
requirements.
EQ2100PSM POWER SUPPLY
MONITOR USED WITH EQ2110PS,
EQ2130PS AND EQ2175PS POWER
SUPPLIES
WIRING
1.
Mount the power supply monitor in a Nationally
Recognized Test Laboratory (NRTL) labeled
enclosure. Refer to the “Specifications” section for
mounting dimensions.
NOTE
Power supplies require unrestricted air flow for
proper cooling.
2.
Securely mount the cabinet. The cabinet should be
electrically connected to earth ground.
3.
Connect the external wiring to the appropriate
points as described below. Refer to Figure VII-1 for
terminal block locations and Figures VII-2 and VII-3
for terminal identification.
95-8470
VII-1
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
J1: POWER AND LON WIRING
LON ADDRESS SWITCHES
J3: AC INPUT
TERMINAL NO. 1
YELLOW LED
RED LED
GREEN LED
TERMINAL NO. 1
TERMINAL "B"
TERMINAL "C"
J2: CURRENT TEST POINTS
TERMINAL NO. 1
SWITCH NO. 1
1
1
1
1
A1949
Figure VII-1—Location of Terminals, LEDs and Switches on the Power Supply Monitor