EQ2200IDC/IDCGF/IDCSC
INITIATING DEVICE CIRCUIT
INPUT VOLTAGE—
24 vdc nominal, 18 to 30 vdc. 10% overvoltage will not
cause damage to the equipment.
INPUT POWER—
4.0 watts maximum.
INPUTS—
Two supervised non-incendive digital inputs (sealed or
unsealed switch or relay contacts). 10 kohm EOL
resistors are required.
OUTPUTS—
Digital communication, transformer isolated (78.5 kbps).
TEMPERATURE RANGE—
Operating:
–40°F to +167°F (–40°C to +75°C).
Storage:
–-67°F to +185°F (–55°C to +85°C).
HUMIDITY RANGE—
0 to 95% RH, non-condensing.
VIBRATION—
Meets MIL SPEC 810C, method 514.2, curve AW.
DIMENSIONS—
See Figure X-2.
EQ2200UV and EQ2200UVHT UV
FLAME DETECTORS
INPUT VOLTAGE—
24 vdc nominal, 18 to 30 vdc. 10% overvoltage will not
cause damage to the equipment.
INPUT POWER—
2.0 watts typical, 4.0 watts maximum during
oi
test.
TEMPERATURE RANGE—
EQ2200UV
Operating:
–40°F to +167°F (–40°C to +75°C).
Storage:
–67°F to +185°F (–55°C to +85°C).
EQ2200UVHT
Electronic Module: –40°F to +167°F (–40°C to +75°C).
UV Detector:
–40°F to +257°F (–40°C to +125°C).
Storage:
–67°F to +185°F (–55°C to +85°C).
HUMIDITY RANGE—
0 to 95% relative humidity, can withstand 100%
condensing humidity for short periods of time.
SPECTRAL SENSITIVITY RANGE—
UV radiation over the wavelength of 1850 to 2450
angstroms (solar blind).
CONE OF VISION—
The detector has a 90 degree cone of vision with the
highest sensitivity lying along its central axis. See
Figure X-3.
X-3
95-8470
0.32 (0.81) OVAL SLOT MOUNTING
(TYPICAL FOUR PLACES)
3.4
(8.6)
4.7
(11.8)
5.2
(13.2)
0.28
(0.71)
2.7
(6.8)
B2045
6.6
(16.8)
1.28
(3.25)
Figure X–2—Dimensions of Tall Cover Junction Box
in Inches (Centimeters)
0°
15°
30°
45°
15°
30°
45°
D573
100
90
80
70
60
50
40
30
20
10
DETECTION
DISTANCE
(PERCENT)
100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A GIVEN FIRE.
THE SENSITIVITY INCREASES AS THE ANGLE OF INCIDENCE DECREASES.
Figure X–3—Cone of Vision of UV Detector