background image

7.1

9

95-8242

SYSTEM SENSITIVITY CONSIDERATIONS

Figure 8 shows the approximate relation between counts 

per second (cps) and distance.  From this curve it can 

be seen, for example, that a 4 ft2 (0.37 m2) gasoline fire 

at 60 feet (18 meters) will normally cause the detector to 

generate 20 cps.  The same fire at 40 feet (12 meters) will 

generate about 50 cps.  If a 2 ft2 (0.18 m2) fire at 20 feet 

(6 meters) will generate about 100 cps, the same fire at 

70 feet (21 meters) will generate about 8 cps.  Because 

of  the  complexity  of  the  combustion  process,  the  UV 

tube count rate generated by different size fires viewed 

from the same distance is difficult to predict with a high 

degree of precision.  In general, however, if a fire doubles 

in size, the tube count rate is increased by approximately 

60 percent.

NOTE

The  count  rate  of  any  given  detector  will  depend 
upon  the  sensitivity  of  the  sensor  tube,  the  type 
and  amount  of  fuel,    the  distance  between  the 
detector  and  the  fire,  as  well  as  various  other 
factors.    Figure  8  illustrates  the  relative  response 
of a “typical” C7050 to various size gasoline fires 
based on minimum sensitivity standards for DE1888 
UV  sensor  modules.  Sensor  modules  with  higher 
sensitivity are available.  Consult the Field Support 
Group at Det-Tronics for information or assistance 
concerning  a  specific  detector  tube  type  or  a 
specific combustible material.

Selection  of  controller  sensitivity  and  time  delay  to  be 

used in a given application is dependent on the level of 

hazard  present  and  the  action  to  be  taken  in  the  event 

of fire.  The adjustable sensitivity and time delay of the 

R7404 allows it to meet the requirements of virtually any 

application. 

The system can be adjusted to various sensitivity levels 

by  programming  the  controller  to  respond  at  a  pre-

determined detector tube count rate.  This count rate is 

dependent  upon  the  intensity  of  the  ultraviolet  radiation 

reaching the detector, which is a function of fuel, flame 

size, distance from the detector, and the amount of UV 

absorbing vapors that may be present.

Programming  the  controller  to  respond  to  a  low  count 

rate  results  in  high  system  sensitivity.    Conversely, 

programming the controller to require a high count rate 

results  in  low  system  sensitivity.    The  presence  of  UV 

absorbing  vapors  must  be  examined  closely.    Some 

chemical and petrochemical vapors have very strong UV 

absorption characteristics.  See Table 2.

Referring  to  Figure  8  and  considering  the  conditions 

described above, the criteria for selecting a correct system 

sensitivity adjustment can be established.  For example, 

assume that the hazard to be protected is at a distance 

of 23 feet (7 meters) from the detector.  Assume that the 

hazard  is  gasoline  and  that  it  is  desired  to  produce  an 

alarm signal when a fire with a surface area of 1 square 

foot  (0.09  m2)  develops.    Reading  on  the  horizontal 

“Distance”  axis  of  Figure  8,  locate  the  vertical  line  at 

approximately 23 feet (7 meters).  Follow this line until it 

intersects the “1 square foot” curve.  Note that this occurs 

at the horizontal line of about 50 counts per second on 

the vertical “Detector Output” axis.  This means that the 

controller  should  be  adjusted  to  48  cps  sensitivity  in 

order to detect this size fire from 23 feet (7 meters).  If the 

detectors were located 30 feet from the hazard, it can be 

seen that it would be necessary to use a more sensitive 

(lower cps) setting.

The  following  38  substances  exhibit  significant  UV 
absorption  characteristics.  These  are  also  generally 
hazardous  vapors.  While  generally  of  little  consequence 
in  small  amounts,  these  gases  can  restrict  UV  detection 
if  they  are  in  the  atmosphere  in  heavy  concentrations.  It 
should also be determined whether or not large amounts of 
these gases may be released as a result of a fire-causing 
occurrence.

Acetaldehyde 

Methyl Methacrylate

Acetone 

Alpha-Methylstyrene

Acrylonitrile 

Naphthalene

Ethyl Acrylate 

Nitroethane

Methyl Acrylate 

Nitrobenzene

Ethanol 

Nitromethane

Ammonia 

1-Nitropropane

Aniline 

2-Nitropropane

Benzene 

2-Pentanone

1,3 Butadiene 

Phenol

2—Butanone 

Phenyl Clycide Ether

Butylamine 

Pyridine

Chlorobenzene 

Hydrogen Sulfide

1-Chloro-1-Nitropropane 

Styrene

Chloroprene 

Tetrachloroethylene

Cumene 

Toluene

Cyclopentadiene 

Trichloroethylene

O-Dichlorobenzene 

Vinyl Toluene

P-Dichlorobenzene 

xylene

If UV-absorbing gases may be a factor in a given application, 
precautionary  measures  should  be  taken.  Detectors  can 
be  placed  closer  to  the  potential  hazard  area,  and/or 
the  sensitivity  of  the  detection  system  can  be  increased. 
Contact the factory for further details.

Substances such as methane, propane, butane, hexane, 
camphor and octane are not UV absorbing.

Table 2—UV Absorbing Gases and Vapors

Summary of Contents for C7050

Page 1: ...Instructions 95 8242 Ultraviolet Flame Detection System R7404 Controller C7050 Detector 7 1 Rev 11 10 95 8242 ...

Page 2: ...ERATIONS 9 INSTALLATION 10 Wiring Requirements 10 Detector Positioning and Density 11 Mounting the Detector 11 Controller 13 TYPICAL SYSTEM APPLICATIONS 17 STARTUP PROCEDURE 18 CHECKOUT PROCEDURE 20 Manual oi Check 20 Detector Count Test 20 Manual Check in Normal Mode 21 MAINTENANCE 21 TROUBLESHOOTING 22 DEVICE REPAIR AND RETURN 22 ORDERING INFORMATION 24 Options 24 Recommended Spare Parts 24 ...

Page 3: ... in outdoor applications because it is not affected by wind or rain and is insensitive to solar radiation In addition the detector does not respond to normal artificial light Typical applications for Det Tronics UV detection systems are Wherever highly combustible materials are involved Where there is a need for instantaneous response to flame Wherever unsupervised areas require automated fire pro...

Page 4: ...n Considering the above it can be seen that there are fire detection applications where only ultraviolet sensors are suitable However success in using an ultraviolet detector is dependent not only on knowing its advantages but also its limitations It is important to note that electric arc welding is a source of intense ultraviolet radiation and care must be taken to ensure that arc welding is not ...

Page 5: ... external reflective oi ring faults caused by corrosion or contamination of the ring are eliminated A fault will be indicated only if the viewing window is actually dirty It is important to note that the internal reflection system is effective only with oily substances that wet the surface of the window It does not detect dry contaminants and therefore is not practical for powder coating booths or...

Page 6: ...eater than the preset time delay the following actions take place 1 The appropriate solid state zone output s is energized One zone output is available for each of the eight zones 2 The solid state alarm output is energized The alarm output is activated when any zone detects a fire 3 The ZONE display identifies the first responding zone The DETECTOR display is blank 4 The SYSTEM STATUS display sho...

Page 7: ... and INHIBIT LEDs will turn on and all Zone Fire Logic and Alarm outputs will be disabled Programming Switches The circuit board on the left side of the R7404 Controller contains switches for selection of 1 Detectors connected to the controller 2 System sensitivity 3 Time delay 4 Fire logic and latching non latching options See Switch Setting Procedure in the Installation section for a detailed de...

Page 8: ...dwires As with any field device shielded cable on all wires provides maximum protection from RFI EMI sources SHIPPING WEIGHT Approximate Pounds Kilograms Controller 2 5 1 12 Detector aluminum 1 25 0 56 stainless steel or brass 2 25 1 0 DIMENSIONS Refer to Figure 3 for dimensions of the controller and Figure 4 for the detector and swivel mounting brackets Figure 5 shows the dimensions of the Q4004 ...

Page 9: ... HT DIM A DIM B DIM C DIM D DIM E WEIGHT FIRE GAS INCH MM INCH MM INCH MM INCH MM INCH MM LB KG 4U 001 8 16 4U 19 00 482 6 18 30 464 8 17 36 440 9 4 00 101 6 6 97 177 1 9 3 4 2 4U 002 6 12 4U 15 06 382 6 14 36 364 7 13 42 340 9 7 6 3 5 4U 003 4 8 4U 11 13 282 6 10 43 264 9 9 49 241 1 5 9 2 7 4U 004 3 6 4U 9 16 232 7 8 46 214 9 7 52 191 0 5 1 2 3 4U 005 2 4 4U 7 19 182 7 6 49 164 9 5 55 141 0 4 2 1...

Page 10: ... detection system when sources of high level radiation are being used in the immediate area Caution must be exercised if the detection system is turned off since the hazardous area will not be protected If the application requires continuous supervision by the detection system a Nuclear Surveillance system is needed Refer to form number 95 8256 or contact Det Tronics for complete information NOTE ...

Page 11: ...presence of UV absorbing vapors must be examined closely Some chemical and petrochemical vapors have very strong UV absorption characteristics See Table 2 Referring to Figure 8 and considering the conditions described above the criteria for selecting a correct system sensitivity adjustment can be established For example assume that the hazard to be protected is at a distance of 23 feet 7 meters fr...

Page 12: ...re an explosion proof installation an additional seal is also required at any point where the conduit enters a non hazardous area When pouring a seal the use of a fiberdam is required to assure proper formation of the seal The seals should never be poured in temperatures that are below freezing since the water in the sealing compound will freeze and the compound will not dry properly Contamination...

Page 13: ...me as in an electrical fire do not use UV detectors alone Mounting the Detector The following procedure should be used for mounting and wiring the detectors 1 Detectors should be located for the best unobstructed view of the area to be protected Detectors must be accessible for cleaning the viewing window and reflector rings Care must be taken so that dirt or other foreign material will not accumu...

Page 14: ...f the wires from individual detectors are connected to the R7404 Controller using a multiple conductor cable with a single outer shield and without twisted pairs careful placement of the individual detector leads is necessary to prevent cross talk between zones The individual B leads should be arranged around the outside of the cable with a ground lead between The inner layer of conductors should ...

Page 15: ...eight rockers which are opened or closed to select zone and detector combinations controller sensitivity fire logic output latching and time delay Figure 13 illustrates the left side of the R7404 and contains a short explanation of rocker switch usage SWITCH 3 FIRE LOGIC SETTING OP OPEN CL CLOSED DC DON T CARE A B A AND B SENSITIVITY SELECTION ROCKER 3 4 CLOSED 64 CPS ROCKER 3 3 CLOSED 32 CPS ROCK...

Page 16: ...ents 3 1 closed 8 cps 3 2 closed 16 cps 3 3 closed 32 cps 3 4 closed 64 cps The values of the closed rockers are added together The rockers can be set in any combination to give the sensitivity setting selected for the application up to 120 cps NOTE If no rockers are closed or if only rocker 3 1 is closed the controller responds to an 8 cps signal from the detector Refer to Figure 15 for an exampl...

Page 17: ...ns All electrical connections are made to the field wiring connector that is furnished with the controller Figure 20 shows the terminal configuration for the controller 8 7 6 5 4 3 2 OPEN NOTE THE VALUE OF ROCKERS SET IN THE CLOSED POSITION ARE ADDITIVE A0282 8 SECOND TIME DELAY 4 SECOND TIME DELAY 2 SECOND TIME DELAY 1 SECOND TIME DELAY 0 5 SECOND TIME DELAY NOT USED ROCKER 5 CLOSED 4 SECONDS ROC...

Page 18: ...KER OPEN CLOSED 8 7 6 5 SWITCH 3 SENSITIVITY ROCKER OPEN CLOSED 4 3 2 1 THE POSITION OF ROCKER NO 8 DIVIDES THE SYSTEM INTO TWO GROUPS OF FOUR OR ONE GROUP OF EIGHT SENSITIVITY COUNT SELECTED WHEN ROCKER IS IN CLOSED POSITION NOT USED SWITCHES CLOSED ARE ADDITIVE LATCHING OPEN NON LATCHING CLOSED R7404 SIDE VIEW Figure 19 System Layout Chart 100K R7484 OPEN COLLECTOR OUTPUT 1N4004 TYPICAL 60 VDC M...

Page 19: ...ld be considered an alternate method for use only where codes allow The system illustrated in Figure 24 furnishes solid state output signals from zones 1 through 8 Fire Logic A and B and the Alarm output External Accept and External Inhibit are shown connected for use in locations remote from the controller Other connections are not used in this configuration 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16...

Page 20: ...rs to be operating normally remove mechanical blocking devices and restore power to the extinguishing loads 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 A 290 VDC B INPUT 1 B INPUT 2 B INPUT 3 B INPUT 4 B INPUT 5 B INPUT 6 B INPUT 7 B INPUT 8 D1 1 oi DRIVER D1 2 oi DRIVER D1 3 oi DRIVER D1 4 oi DRIVER D1 5 oi DRIVER D1 6 oi DRIVER D1 7 oi DRIVER D1 8 oi DR...

Page 21: ...C A B C D C7050 ZONE 2 A B C D C7050 ZONE 7 A B C D C7050 ZONE 8 A B C D A B C D C7050 ZONE 1 A B C D C7050 ZONE 3 A B C D C7050 ZONE 4 A B C D C7050 ZONE 5 A B C D C7050 ZONE 6 A B C D C7050 ZONE 2 A B C D C7050 ZONE 7 A B C D C7050 ZONE 8 A B C D J1 3 J1 5 J1 2 J1 13 A B C D J1 3 J1 4 J1 2 J1 20 A B C D J1 3 J1 5 J1 2 J1 21 A B C D J1 3 J1 6 J1 2 J1 14 A B C D J1 3 J1 6 J1 2 J1 22 A B C D J1 3 J...

Page 22: ...utomatic oi system continuously monitors the operation of the R7404 but does not monitor external relays or equipment that may be operated from the fire signal output the alarm signal output or the fault signal output It is important that the system be manually checked using the NORMAL mode checkout procedure on a regular basis The whole system including external equipment should be checked period...

Page 23: ...vation 1 Place the keylock switch in the NORMAL position 2 Shine the UV test light into a detector viewing window The corresponding ZONE LED turns on and flashes indicating the zone in which the detector is located The upper display shows the first zone activated The lower display shows a 6 The appropriate FIRE LOGIC LED s turns on if voting requirements are met 3 Turn off the UV source FIRE LOGIC...

Page 24: ...yCPIEngineering Silicone based lubricants should never be used if catalytic type combustible gas sensors are being used in conjunction with the UV detectors since inadvertent use of a silicone lubricant on or near the combustible gas sensor will cause irreversible damage to the sensing element A test form is supplied at the rear of this manual for recording maintenance performed on the system TROU...

Page 25: ...ault output remains ener gized 0 0 4 Low 290 vdc caused by a shorted A lead or controller malfunction 0 0 5 High 290 vdc caused by a failure in the regulating network in the controller Blank 1 8 6 Fire Output signal blinking ZONE OUTPUT LED indicates fire location Steady ZONE OUTPUT LED indicates that the detectors in that zone have responded to a UV signal but are no longer responding 7 Not used ...

Page 26: ...3 Air Shield provides a continuous flow of clean air across the viewing window of the detector to reduce the accumulation of certain types of airborne contaminants Q9001 Swivel Mounting Assembly for mounting the C7050 Detector Use the Q9001B for C7050 Detectors with aluminum housings and the Q9001H for C7050 Detectors with nickel brass and stainless steel housings R6006 Relay Output Module is used...

Page 27: ...7 1 25 95 8242 Fault Record Sheet Date Time Detector System Status Operator Comments Affected ...

Page 28: ...7 1 26 95 8242 Recommended Test Form Detector Detector Date Date Date Number Location Installed Checked Calibrated Remarks ...

Page 29: ...ainless steel enclosure and 1 2 inch or 3 4 inch NPT conduit entries M20 M25 or Pg 16 conduit entries can be used in non North American applications For 18 to 32 vdc operation through an approved control panel that provides separate circuits for power and alarm initiation Explosion proof for Class I Division 1 Groups B C and D Hazardous Classified Locations per FM 3615 Dust ignition proof for Clas...

Page 30: ...clipse are registered trademarks or trademarks of Detector Electronics Corporation in the United States other countries or both Other company product or service names may be trademarks or service marks of others Copyright Detector Electronics Corporation 2010 All rights reserved X3301 Multispectrum IR Flame Detector PointWatch Eclipse IR Combustible Gas Detector Eagle Quantum Premier Safety System...

Reviews: