47
3.8 High Condensate Level
This is an Automatic Reset Alarm. The optional Condensate Level Switch is required to
activate this alarm. The High Condensate Level Alarm is activated when the condensate
drain is plugged for any reason. The unit will stop and not restart until this condition is
reset. The red Alarm LED on the display will stay lit until the alarm is reset.
3.9 Smoke Alarm
This is an Automatic Reset Alarm. The Smoke Alarm is activated if the alarm contact
wired to digital input ID8 is opened. In this state, the unit will stop and not restart until
the smoke alarm contact closes. The red Alarm LED on the display will stay lit until the
alarm is reset.
3.10 Low Air Flow Condition
This is an Automatic Reset Alarm. The Low Air Flow Condition is activated if the air
flow falls below the air flow proving value for the air flow time delay. In this state, the
blower will continue to run, the refrigeration circuits and heating will stop and not
restart until the air flow rises above the proving switch value. The red Alarm LED on
the display will stay lit until the alarm is reset.
3.11 Low Water Flow Condition
This is an Automatic Reset Alarm. The optional Water Flow Switch is required to
activate this alarm. The Low Water Flow Condition is activated if the water in the water
cooled condenser stops flowing. In this state, the blower will continue to run, the
refrigeration circuits will stop and not restart until the water flow switch closes. The red
Alarm LED on the display will stay lit until the alarm is reset.
3.12 Freeze ‘Stat Alarm
This is a Manual Reset Alarm. The optional Freeze ‘Stat is required to activate this
alarm. The Freeze ‘Stat Alarm is activated when the temperature across the water
coil drops. In this state, the unit will stop and not restart until the temperature rises to
close the switch contact. The red Alarm LED on the display will stay lit until the alarm
is
reset.
3.13 Condenser Fan OL
This is an Automatic Reset Alarm. The Condenser Fan OL is activated if any
condenser fan overload device opens. In this state, the unit will continue to run
normally while activating additional condenser fans. The red Alarm LED on the display
will stay lit until the alarm is reset.
3.14 Air Filter Service Required
This is an Automatic Reset Alarm. The optional Air Pressure Switch is required to
activate this alarm. The Air Filter Service Required is activated when the pressure
differential across the air filter exceeds the normal pressure. In this state, the unit will
continue to run. The red Alarm LED on the display will stay lit until the alarm is reset.
Desert Aire - CM3550 Manual
Summary of Contents for CM3550 Series
Page 2: ...2 ...
Page 5: ...5 Desert Aire CM3550 Manual Product Warning for the State of California ...
Page 6: ...6 Desert Aire CM3550 Manual ...
Page 34: ...34 Figure 47 Figure 48 Figure 49 Figure 50 Desert Aire CM3550 Manual ...
Page 44: ...44 Desert Aire CM3550 Manual ...
Page 57: ...57 Desert Aire CM3550 Manual ...