2.3.3.2.1 Reheat Settings (Figures 54 and 55)
Selecting the Reheat Settings from the Parameter Settings
Menu displays the Reheat Transition PID parameters shown
in Figure 54. The Transition parameters are used by the
control system every time the transition is made from Lights
On to Lights Off or Lights Off to Lights On. After the transition
time, typically 10 minutes, the Reheat Run PID parameters
are
used.
Press
the
DOWN
key for the Run parameters, see
Figure
55.
Figure
54
Figure
55
To return to the Service Menu, press the
Esc
key.
2.3.3.2.2 Aux Heat Settings (Figure 56 and 57)
Selecting the Aux Heat Settings from the Parameter Settings
Menu displays the Aux Heat Transition PID parameters shown
in Figure 56. The Transition parameters are used by the control
system every time the transition is made from Lights On to
Lights Off or Lights Off to Lights On. After the transition time,
typically 10 minutes, the Reheat Run PID parameters are used.
Press
the
DOWN
key for the Run parameters, see Figure 57.