  CAUTION:  Use  only  new, 

black  iron  or  steel  pipe.  Inter

-

nally-tinned copper tubing may 

be used in certain areas. Check 

your  local  codes.  Use  pipe  of 

1/2" diameter or greater to allow 

proper gas volume to fireplace. 

If pipe is too small, undue loss 

of volume will occur.

Installation must include an equipment shutoff 
valve, union and plugged 1/8" NPT tap. Locate 
NPT tap within reach for test gauge hook up. 
NPT  tap  must  be  upstream  from  fireplace 
(see Figure 31).

IMPORTANT

: Install main gas valve (equip-

ment shutoff valve) in an accessible location. 
The main gas valve is for turning on or shutting 
off the gas to the appliance.
Check  your  building  codes  for  any  special 
requirements for locating equipment shutoff 
valve to fireplaces.
Apply pipe joint sealant lightly to male NPT 
threads. This will prevent excess sealant from 
going into pipe. Excess sealant in pipe could 
result in clogged fireplace valves.

  WARNING:  Use  pipe  joint 

sealant that is resistant to liquid 

petroleum (LP) gas.

FIREPLACE 

INSTALLATION

Continued

We  recommend  that  you  install  a  sediment 
trap/drip leg in supply line as shown in Figure 
31. Locate sediment trap/drip leg where it is 
within reach for cleaning. Install in piping sys-
tem between fuel supply and fireplace. Locate 
sediment trap/drip leg where trapped matter 
is not likely to freeze. A sediment trap traps 
moisture and contaminants. This keeps them 
from going into fireplace gas controls. If sedi-
ment trap/drip leg is not installed or is installed 
wrong, fireplace may not run properly.

Figure 31 - Gas Connection

* The CSA design-certified equipment shutoff 
valve may be supplied with the appliance or 
you can purchase it from your retailer.

CONNECTING FIREpLACE TO GAS 
SUppLY

Installation Items Needed

•  5/16" hex socket wrench or nut-driver
•  sealant (resistant to propane/LP gas, not 

provided)

1.  Open lower louver door panel by gently 

pulling forward.

2.  Route  flexible  gas  line  (provided  by  in-

staller)  from  equipment  shutoff  valve  to 
fireplace.  Route  flexible  gas  supply  line 
through one of the access holes on side 
of fireplace.

3.  Attach flexible gas line from gas supply to 

control valve (see Figure 32, page 23).

4.  Check all gas connections for leaks. See 

Checking Gas Connections, 

page 23.

Figure 30 - External Regulator with Vent 

Pointing Down (Propane/LP Only)

Propane/LP 
Supply Tank

External 
Regulator 
With Vent 
Pointing 
Down

CSA Design-Certified 
Equipment Shutoff Valve 
with 1/8" NPT Tap*

3" Minimum

Approved Flexible 
Gas Line

Cap  Pipe 

Tee

 

Nipple  Joint

Sediment Trap/Drip Leg

Natural

 - From 

Gas Meter (5.5" 
W.C. to 10.5" W.C. 
Pressure)

Propane/LP

 From 

External Regulator 
(11" W.C. to 14" 
W.C. Pressure)

Summary of Contents for VVC42NE Series

Page 1: ...mable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your bu...

Page 2: ...IMPORTANT Read this owner s manualcarefullyandcompletely before trying to assemble op erate or service this log set Improper use of this log set can cause serious injury or death from burns fire expl...

Page 3: ...sory not approved for use with this fire place WARNING This appliance is only for use with the type of gasindicatedontheratingplate Thisapplianceisnotconvertible for use with other gases unless a cert...

Page 4: ...e gas valve and pilot light before cleaning fireplace 6 Have venting system inspected annually by a qualified service person If needed have venting system cleaned or repaired See Cleaning and Maintena...

Page 5: ...e installation instructions are followed Local Codes Install and use fireplace with care Follow all local codes In the absence to local codes use the current National Fuel Gas Code ANSI Z223 1 NFPA 54...

Page 6: ...age of venting system When using snow blowers do not direct snow towards vent termination area Pre Installation Preparation Continued Clearances Minimum clearances to combustibles for the fireplace ar...

Page 7: ...ent C B A D E F G Top of Louver Opening 3 2 1 4 5 6 7 Wall Figure 5 Framing Clearances for Corner Installation Figure 6 Clearances for Combustible Mantels 48 41 5 8 58 1 2 16 3 4 13 1 2 Pre Installati...

Page 8: ...00 and 50 000 12 30 cm in Canada if between 10 000 and 100 000 12 30 cm in US if greater than 50 000 36 91 cm in Canada if greater than 100 000 K clearance to a mechanical air supply inlet In Canada 6...

Page 9: ...on the out side of the structure and can not be attached to a chimney or flue system serving a separate solid fuel or gas burning appliance Adirect vent appliance must have its own venting system DO...

Page 10: ...ale ends of adjacent pipes Push pipe sections together and twist one section clockwise approximately one quarter turn until sections are fully locked see Figure 8 Note Horizontal runs of vent must be...

Page 11: ...screws provided see Figure 11 Siding standoff must sit flush against exterior fascia material 7 Connecting Vent Cap With Horizontal Vent Pipe Slide wall firestop over the vent pipe before connecting h...

Page 12: ...red NOTICE Donotsealtermination cap to vent pipe Cap must be removable for vent inspection and maintenance WARNING Never run vent downward as this may cause excessive temperatures which could cause a...

Page 13: ...commended Applications Installations requiring a vertical rise on building exterior Any installation using snorkel termination to achieve one foot above ground Snorkel terminations are available for i...

Page 14: ...or a horizontal system using two 90 elbows Figure 18 Horizontal Termination Configuration for Venting Using Two 90 Elbows with Termination at 90 with Fireplace 45 Elbow Venting with Two 90 Elbows Vert...

Page 15: ...bove ceiling is an insulated ceiling or an attic nail firestop from top side This prevents loose insula tion from falling into required clearance space If area above ceiling is a living space install...

Page 16: ...e 90 Elbow Vertical Round High Wind Termination Shown 45 Elbow poor draft or down drafting in high winds Increasing vent height may solve this problem 7 Twist lock vent cap onto last section of vent p...

Page 17: ...feet in the USA you may need to decrease the input rating by changing the existing burner orifice to a smaller size Re duce input 4 for each 1000 feet above sea level Check with your local gas compan...

Page 18: ...Roof Flashing 0 12 6 12 26 Screws VKC 58 Corner Vent Kit Galvanized Includes 45 Elbow 7 12 Adjustable Pipe Wall Firestop Horizontal Termination 6 Pipe 90 Elbow 18 Screws HHTK 58 High Wind Round Horiz...

Page 19: ...upward Blower will fit inside back opening and be held in position against back wall by magnets see Figure 25 4 Be certain that all wire terminals are securely attached to terminals on blower motor an...

Page 20: ...hite wire to other remaining blower motor terminal Note Power cord outer insulation sleeve may have to be stripped slightly to allow enough wire length to reach and make all connec tions DO NOT trim e...

Page 21: ...1 2 Black Installing Gas Piping to Fireplace Location WARNING A qualified service person must connect fireplace to gas supply Follow all local codes CAUTION For propane LP units neverconnectfireplace...

Page 22: ...ng sys tem between fuel supply and fireplace Locate sediment trap drip leg where trapped matter is not likely to freeze A sediment trap traps moisture and contaminants This keeps them from going into...

Page 23: ...es forming show a leak Correct all leaks at once 5 Reconnect fireplace and equipment shutoff valve to gas supply Check recon nected fittings for leaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5...

Page 24: ...If fireplace has been running turn off and un plugfireplace Letcoolbeforere moving glass door or louvers Fireplace Installation Continued Removing Louver Panels Remove top and bottom louver panels by...

Page 25: ...t block pilot ports with embers It is not necessary to use all of the ember material provided 2 Pour lava rock onto plenum but not onto flat burner It is not necessary to use all of the lava rock prov...

Page 26: ...f a wall switch allows you to activate gas control valve and turn fireplace on and off Wall switch is to be connected to incoming 120 volt regular household wiring that supplies electricity to firepla...

Page 27: ...www desatech com 116237 01H 27 EV2 EV1 ORANGE IGNITOR LEAD GREEN PILOT TRANSFORMER IS1070B SYNETEK CONTROLS INC 24V AC E4 E2 E3 E6 RED E8 E12 BLUE 120V AC GROUND BLACK WHITE Wiring Diagram...

Page 28: ...explosion may result causing property damage per sonal injury or loss of life A This appliance is equipped with an igni tion device which automatically lights the pilot Do not light pilot by hand B BE...

Page 29: ...age 28 see Troubleshooting page 31 Figure 45 Typical Flame Pattern located on the left side of switch bracket to the right just inside louver panel The BK manual blower and BKT thermostati cally contr...

Page 30: ...cleaner to remove any carbon buildup on logs Replace log s if broken See Replacement Parts on page 34 Replace ember material periodically as needed See Replacement Parts on page 34 WARNING Turn off f...

Page 31: ...le or similar object to clean pilot This can damage pilot unit Note All troubleshooting items are listed in order of operation POSSIBLE CAUSE 1 No gas supply or shutoff valve is OFF 2 Air in gas line...

Page 32: ...oded 1 Check electrical connec tions 1 Clean and adjust pilot flame for maximum flame im pingement on thermopile 2 Have vent system inspect ed including termination cap Remove any restriction or obstr...

Page 33: ...3 Improper venting or exces sive blockage 4 Excessive amounts of embers and pan material OBSERVED PROBLEM Gas odor even when control knob is in OFF position Gas odor during combustion Glass soots Dar...

Page 34: ...Gas Pressure Is Too Low pilot will not stay lit burners will have delayed ignition fireplace will not produce specified heat propane LP gas supply might be low pro pane LP units only You may feel you...

Page 35: ...hase these accessories from your local dealer If they can not supply these accessories call DESAHeating LLC at 1 866 672 6040 for information You can also write to the address listed on the back page...

Page 36: ...www desatech com 116237 01H 36 Parts Models VC42NE VVC42NE VC42PE and VVC42PE series 6 7 22 19 20 15 2 14 21 8 1 4 13 9 16 3 18 5 17 23 10 11 12 24 25 26...

Page 37: ...8331 01 Top Louver Assembly 1 5 108331 02 Bottom Louver Assembly 1 6 Fireplace Top 1 7 Fireplace Top Insulation 1 8 Fireplace Surround 1 9 109082 01 Heat Shield 1 10 116216 01 Log Set 1 11 116338 01 B...

Page 38: ...www desatech com 116237 01H 38 PARTS Burner assembly Models VC42NE VC42PE VVC42NE and VVC42PE 7 15 10 12 3 2 13 9 23 24 22 21 11 25 27 26 29 30 28 33 32 31 6 12 14 18 17 17 18 19 20 16 14 8 4 5 1 12...

Page 39: ...Electric Valve Assembly NG 1 14570 Electric Valve Assembly LP 1 12 11165 Screw 10 x 5 8 Zinc 1 13 Burner Base Gasket 1 14 14500 Brass Fitting 2 15 116345 01 Pilot Bracket 1 16 26827 Switch Bracket 1 1...

Page 40: ...s not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects cause...

Reviews: