background image

www.desatech.com

119426-01A

7

AIR FOR COMbUSTION 

AND VENTILATION

Continued

Space: 

Includes the room in which you will install 

fireplace plus any adjoining rooms with doorless pas

-

sageways or ventilation grills between the rooms.

1.  Determine the volume of the space (length x 

width x height).

 

Length x Width x Height =__________cu. ft. 

(volume of space)

 

Example:

 Space size 20 ft. (length) x 16 ft. 

(width) x 8 ft. (ceiling height) = 2560 cu. ft. 

(volume of space)

 

If additional ventilation to adjoining room is 

supplied with grills or openings, add the volume 

of these rooms to the total volume of the space. 

2.  Multiply the space volume by 20 to determine 

the maximum Btu/Hr the space can support.

 

 __________ (volume of space) x 20 = (Maxi

-

mum Btu/Hr the space can support)

 

Example:

 2560 cu. ft. (volume of space) x 20 = 

51,200 (maximum Btu/Hr the space can support)

3.  Add the Btu/Hr of all fuel burning appliances in 

the space.

 

Vent-free fireplace 

 ___________ Btu/Hr

 

Gas water heater* 

 ___________ Btu/Hr

 

Gas furnace 

 ___________ Btu/Hr

 

Vented gas heater 

 ___________ Btu/Hr

 

Gas fireplace logs 

 ___________ Btu/Hr

 

Other gas appliances*  +

 __________ Btu/Hr

 

Total  

= __________ Btu/Hr

 

* Do not include direct-vent gas appliances. Di

-

rect-vent draws combustion air from the outdoors 

and vents to the outdoors.

 

Example:

 

 

Gas water heater 

 ___________ Btu/Hr

 

Vent-free fireplace 

+ __________ Btu/Hr

 

Total 

= __________ Btu/Hr

4.  Compare the maximum Btu/Hr the space can 

support with the actual amount of Btu/Hr used.

 

 __________ Btu/Hr (maximum the space can support) 

 

 __________Btu/Hr (actual amount of Btu/Hr used)

 

Example:

  51,200 Btu/Hr (maximum the space 

can support) 

 

 

73,000  Btu/Hr  (actual  amount  of 

Btu/Hr used)

The space in the above example is a confined space 

because the actual Btu/Hr used is more than the maxi

-

mum Btu/Hr the space can support. You must provide 

additional fresh air. Your options are as follows:

A.  Rework worksheet, adding the space of an adjoin

-

ing room. If the extra space provides an unconfined 

space, remove door to adjoining room or add 

ventilation grills between rooms. See 

Ventilation 

Air From Inside Building.

B.  Vent room directly to the outdoors. See 

Ventila-

tion Air From Outdoors, 

page 8.

C.  Install a lower Btu/Hr fireplace, if lower Btu/Hr 

size makes room unconfined. 

If the actual Btu/Hr used is less than the maximum 

Btu/Hr the space can support,

 

the space is an un

-

confined space. You will need no additional fresh 

air ventilation.

  WARNING:  If  the  area  in 

which the heater may be oper-

ated is smaller than that defined 

as an unconfined space or if the 

building  is  of  unusually  tight 

construction, provide adequate 

combustion and ventilation air 

by one of the methods described 

in the 

National Fuel Gas Code, 

ANSI Z223.1/NFPA 54 Section 5.3

 

or applicable local codes. 

VENTILATION AIR

Ventilation Air From Inside Building 

This fresh air would come from an adjoining un

-

confined space. When ventilating to an adjoining 

unconfined space, you must provide two perma

-

nent openings: one within 12" of the ceiling and 

one within 12" of the floor on the wall connecting 

the two spaces (see options 1 and 2, Figure 2). You 

can also remove door into adjoining room (see 

option 3, Figure 2). Follow the 

National Fuel Gas 

Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for 

Combustion and Ventilation

 for required size of 

ventilation grills or ducts.

  40,000

  33,000

  73,000

Figure 2 - Ventilation Air from Inside Building

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills 

Into Adjoining Room,

Option 2

Ventilation

Grills Into

Adjoining 

Room,

Option 1

12"

12"

Summary of Contents for VUL 18R, VUL24R, VUL30R, HR B3930, HR 3924R, CRB3624T, VUL 18T, VUL24T, VUL30T, HR B3624T

Page 1: ...atelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qual...

Page 2: ...e agency or the gas supplier WARNING This appliance is for installation only in a solid fuel burning mason ry or UL127 factory built fireplace or in alistedvent less firebox enclosure It is design cer...

Page 3: ...your guide to safe and proper operation of this fireplace WARNING Any change to this heater or its controls can be dangerous WARNING Do not use a blower insert heat exchanger insertorotheraccessoryno...

Page 4: ...burner box or on adjacent walls and furniture 10 This heater needs fresh outside air ventilation to run properly This heater has an Oxygen DepletionSensing ODS safetyshutoffsystem The ODS shuts down t...

Page 5: ...ater may also be operated as a vented decorative ANSI Z21 60 product by opening the flue damper Non Thermostat Models Only Safety Device This heater has a pilot with an Oxygen Deple tion Sensing ODS s...

Page 6: ...tion However in buildings of unusually tight construction you must provide additional fresh air Unusually tight construction is defined as construction where a walls and ceilings exposed to the out si...

Page 7: ...of Btu Hr used The space in the above example is a confined space because the actual Btu Hr used is more than the maxi mum Btu Hr the space can support You must provide additional fresh air Your optio...

Page 8: ...culatetheheatthroughoutthe house In the event of a power outage you can use this heater as your primary heat source WARNING A qualified ser vice person must install heater Follow all local codes NOTIC...

Page 9: ...ere you bought heater for proper type heater WARNING This appliance is equipped for natural or pro pane LP gas Field conversion is not permitted INSTALLATION AND CLEARANCES For Vent Free Operation WAR...

Page 10: ...f noncombustible material is more than 12 you may need the hood accessory to deflect heat away from your mantel shelf See Figure 5 and Figures 6 and 7 page 9 for minimum clearances IMPORTANT If you ca...

Page 11: ...el Clearances When Using Hood Minimum Non Combustible Material Minimum Non Combustible Material Height Distances to Underside of Mantel Top of Fireplace Opening Underside of Mantel Shelf 12 8 A 18 14...

Page 12: ...cluded with clamp accessory See chart below for minimum permanent flue opening you must provide Attach damper clamp so the minimum permanent flue opening will be maintained at all times Area of Variou...

Page 13: ...oved flexible gas hose to gas regulator of heater see Figure 11 For Remote Ready models connect approved flexible gas hose to inlet side of gas control see Figure 12 IMPOR TANT Hold gas regulator with...

Page 14: ...gas connector if allowed by local codes not provided ACSAdesign certified equipment shutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Purchase the optional CSA desi...

Page 15: ...sediment trap traps moisture and contaminants This keeps them from going into heater controls If sediment trap is not installed or is installed wrong heater may not run properly CAUTION Avoid damage t...

Page 16: ...k reconnected fittings for leaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa 1 Close equipment shutoff valve see Figure 17 2 Pressurize supply piping system by either opening propane LP supp...

Page 17: ...o unit 2 Carefully remove logs and set aside 3 Locate mounting screws on sides of heater base assembly and remove screws Set screws aside for reinstallation 4 Disconnect gas line from heater base as s...

Page 18: ...ote Make sure excess wire does not inter fere with burner or pilot 10 If heater was removed from fireplace before installation of remote accessory see Install ing Heater Base Assembly on page 12 to re...

Page 19: ...ottom log in center of the base assem bly as shown in Figure 27 2 Rest rear log in back corner sections of base as semblyasshowninFigure27 Make sure log is completely vertical and not leaning in towar...

Page 20: ...iance and to replace any part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS WARNING If fireplace has glass doors never operate this heater with glass doors...

Page 21: ...level The burners should light Set control knob to any heat level between HI and LO CAUTION Do not try to ad just heating levels by using the equipment shutoff valve Operating Heater Continued Figure...

Page 22: ...page 23 WARNING Burners will come onautomaticallywithinoneminute when the selector switch is in the ON position after the pilot is lit Remote Ready Models FOR YOUR SAFETY READ BEFORE LIGHTING WARNING...

Page 23: ...t steps 4 through 8 page 22 and above 9 Slightly push in and turn control knob coun terclockwise to the ON position 10 Wait one minute and switch selector switch to theONpositiontolightburners Note AU...

Page 24: ...burner turns on Hold the control button again until burner turns off see Figure 34 To Lock press both buttons on hand held remote control until light stops flashing Hand held remote control is now loc...

Page 25: ...e receiver continuously receives signals from the hand held remote to control the room temperature If the hand held remote is misplaced obstructed or for any reason cannot transmit to the receiver the...

Page 26: ...by a qualified service person Heater may need more frequent cleaning due to excessive lint fromcarpeting pethair bedding material etc WARNING Failure to keep the primary air opening s of theburner s...

Page 27: ...mpressed air is not available Cleaning and Maintenance Continued LOGS If you remove logs for cleaning refer to Install ing Logs page 18 to properly replace logs Replace log s if broken or chipped dime...

Page 28: ...n PILOT position 4 Air in gas lines when installed 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Reconnect ignitor cable 2 Free ignitor...

Page 29: ...terlock system to reset Repeat ignition operation 4 Fully open equipment shutoff valve 5 A Contact local natural or propane LP gas company B Clean ODS pilot see Cleaning and Maintenance page 26 or re...

Page 30: ...line checked by local natural or propane LP gas company 3 Observe minimum installa tion clearances see pages 9 through 11 4 Clean burners see Cleaning and Maintenance page 26 or replace burner orific...

Page 31: ...r between con trol valve and burner 2 Gas leak See Warning statement at top of page 1 Thermostat sensing bulb needs to be repositioned Thermo stat Controlled Models Only 2 Hand held remote control is...

Page 32: ...t sensing bulb IMPORTANT Do not force or bend the thermostat sensing bulb or capillary Capillary Screw Retaining Clamp Thermostat Sensing Bulb Figure 43 Location of Gas Valve Assembly and Thermostat S...

Page 33: ...s Pressure in of water Max 10 5 W C Min 5 W C VUL24PT VUL30Pt HRB3624PT Rating Variable 25 000 36 000 Btu Hr Type Gas Propane LP Ignition Electronic Manifold Pressure 7 9 W C Inlet Gas Pressure in of...

Page 34: ...Log 2 1 4 113621 04 113621 10 113621 16 Middle Left Log 2 1 5 113621 05 113621 11 113621 11 Bottom Log 3 Remote 1 113621 05 113621 19 113621 19 Bottom Log 3 T stat 6 113621 06 113621 12 113621 18 Rea...

Page 35: ...aceable parts used in your heater When ordering parts follow the instructions listed under Replacement Parts on page 42 of this manual 1 3 2 KEY NO PART NUMBER DESCRIPTION QTY CRB2618NR CRB2618PR HRB3...

Page 36: ...9426 01A 36 Illustrated Parts Breakdown Thermostat controlled Models VUL18NT VUL18PT VUL24NT VUL24PT VUL30NT VUL30PT HRB3624NT AND HRB3624PT LPG 11 10 4 1 8 3 12 8 2 5 6 7 24 25 21 2 23 22 15 13 16 9...

Page 37: ...rner Injector Propane LP 1 101004 15 1 12 101004 11 Front Burner Injector Natural 1 101004 10 Front Burner Injector Propane LP 1 101004 22 Front Burner Injector Natural 1 101004 06 Front Burner Inject...

Page 38: ...ch com 119426 01A 38 ILLUSTRATED PARTS BREAKDOWN Remote Ready Variable Control Models VUL18NR VUL18PR VUL24NR VUL24PR VUL30NR VUL30PR LPG 5 6 21 14 22 14 23 24 2 19 20 16 1 18 17 10 11 4 3 8 8 12 14 1...

Page 39: ...Injector Natural 1 101004 02 Rear Burner Injector Propane LP 1 12 101004 11 Front Burner Injector Natural 1 101004 10 Front Burner Injector Propane LP 1 101004 08 Front Burner Injector Natural 1 10100...

Page 40: ...40 ILLUSTRATED PARTS BREAKDOWN Remote Ready Variable Control Models CRB2618NR CRB2618PR CRB3624NR CRB3624PR CRB3630NR CRB3630PR HRB3624NR AND HRB3624PR LPG 5 6 21 14 22 14 23 24 2 19 20 16 1 18 17 10...

Page 41: ...Injector Propane LP 1 12 101004 11 Front Burner Injector Natural 1 101004 10 Front Burner Injector Propane LP 1 101004 08 Front Burner Injector Natural 1 101004 06 Front Burner Injector Propane LP 1...

Page 42: ...ts Technical Service Department at 1 866 672 6040 When calling DESA Heating Products have ready your name your address model and serial numbers of your heater how heater was malfunctioning type of gas...

Page 43: ...MATE FIREBOXES Not Shown Available in 32 36 and 42 models Circu lating fireboxes feature louvers and an optional blower Non circulating smooth face models are ideal for custom trim applications such a...

Page 44: ...talled by a qualified installer in accordance with all local codes and instructions furnished with the unit This warranty does not apply to parts that are not in original condition because of normal w...

Reviews: