background image

10

V E N T - F R E E   G A S   H E A T E R   S E R V I C E   M A N U A L

REGULATOR INSTALLATION

GRH/PV 018

Propane Installations

CAUTION: Propane models require an

external regulator (not supplied with heater).
The external regulator must be connected be-
tween the heater and the propane supply tank.
This regulator must reduce the incoming supply
pressure to a maximum of 14" W.C. Under no
circumstances should this heater ever be con-
nected directly to a propane supply tank.

A typical propane installation is shown (below
right) in Figure 9. For details concerning tank or
cylinder location and installation, refer to NFPA
Pamphlet No. 58 and the laws in your locality.

External Regulators - Vents

External regulators should be installed with the
vent pointing down as shown in Figure 9. Some
regulators have a so-called “drip lip” surround-
ing the vents which acts as a shield for the
recessed vent opening. This lip makes it more
difficult for freezing rain or sleet to plug a vent
that has been installed pointing down. Older
style vents may not have the lip and are far less
resistant to freeze-up problems (see Figure 10).

A regulator with the drip lip design installed
outdoors does not require additional protection
if the vent is pointing down, unless subjected to
upward splatter from rain.

Older regulators with the non-drip lip vent con-
struction require additional protection, such as a
hood, cover, encasement, etc. The external
regulator should be installed high enough above
ground level (at least 18 inches) so that rain
splatter does not block or freeze the vent. Extra
protection for the vent may be needed in areas
where there is heavy snow fall.

Be sure the external regulator is installed in
accordance with NFPA No. 58 and any other
applicable local regulations, as well as the
manufacturer’s instructions.

DRIP LIP

GRH/P 026

Figure 9. Typical Propane Installation

Drip Lip

No Drip Lip

Figure 10. Regulator Vent Drip Lips

3 FT
MIN

3 FT

MIN

3 FT

MIN

CYLINDER LOCATION

GRH/PV 016

Supply
Tank

Regulator

!

WARNING ICON

G 001

Manual Shutoff Valve
With 1/8" NPT Tap

Summary of Contents for VP2600

Page 1: ...s supplier s instructions If you cannot reach your gas supplier call the fire department WARNING Improper installation ad justment alteration service or mainte nance can cause injury or property dam a...

Page 2: ...tion Gas Type 8 Location Safety Precautions 8 Gas Supply Installation 9 Propane Installation 10 External Regulators 10 Section 6 Test Procedures Testing Gas Supply Line Connections 11 Testing Heater G...

Page 3: ...ny phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department 5 Never insta...

Page 4: ...Fan Kit GA2100A The fan accessory pro vides better heat distribution in the room 2 Floor Mounting Stand GA4000 3 plaque models and GA4010 5 plaque models The floor stand allows the heater to be instal...

Page 5: ...e held down at least 10 seconds until the thermocouple is heated enough to hold the valve open Once the pilot flame is established the control knob can be released and turned to any of the operating p...

Page 6: ...mo couple provides a low level electric current to an electromagnetic plunger in the control valve This low level electric current keeps the plunger open allowing gas to flow to the pilot and the main...

Page 7: ...alling vent free gas heaters Source Information Controls Inc P O Box 52275 Raleigh North Carolina 1 800 334 5886 Item ESL 16 Approximate Cost 14 00 DESA International P O Box 90004 Bowling Green KY 42...

Page 8: ...bustible surfaces MUST NOT be less than shown in Figure 7 These are absolute minimum clearances Greater clearances should be allowed if possible The heater can also be mounted to an optional floor mou...

Page 9: ...ult in clogged valves IMPORTANT Pressure regulator must be held with wrench when connecting gas piping and or fittings to pressure regulator External Regulator For LP Heaters Only Drip Leg Trap Figure...

Page 10: ...cult for freezing rain or sleet to plug a vent that has been installed pointing down Older style vents may not have the lip and are far less resistant to freeze up problems see Figure 10 A regulator w...

Page 11: ...ely WARNING NEVER USE AN OPEN FLAME TO CHECK FOR A LEAK Apply a solution of liquid detergent and water to all connections The formation of bubbles indicate leaks that must be corrected Pressure Testin...

Page 12: ...tion 230 ma maximum Drop out current specification 80 ma minimum If the control valve operates correctly during the above test it is likely that the problem is the result of a bad thermocouple 7 Conne...

Page 13: ...put Maximum 16 000 16 000 26 000 26 000 Minimum 6 000 6 000 6 000 11 000 Fresh Air Opening Minimum 16 sq in 16 sq in 26 sq in 26 sq in MODELS VN1800 VN1800T VN3000 VN3000T VN1800A VN1800TA VN3000A VN3...

Page 14: ...e Causes 1 Ignitor cable 2 Ignitor electrode position and or cleanli ness 3 Ignitor electrode body cracked 4 Control knob not fully depressed 5 Control valve malfunction Procedures 1 Check the ignitor...

Page 15: ...re clip from the bi metal strip located on the pilot tube see Figure 14 Remove the brass cover and clean any dust or cob webs from the air gas mixing chamber Reassemble the brass cover with the wire c...

Page 16: ...at the room is properly ventilated See SPECIFICATIONS page 13 for the minimum fresh air openings required If necessary instructtheusertoslightlyopen a window for proper ventilation 4 Be sure that stro...

Page 17: ...fold pressure with a manometer to be sure that the regulator is not defective See SPECIFICATIONS on page 13 for the model you are servicing Third check the pilot assembly and pilot line to be sure tha...

Page 18: ...the outside of the tank The ice acts as an insulator and can reduce the evaporation rate and the pressure to your heater If an im proper tank size is causing a low supply pressure to the heater con t...

Page 19: ...r and gas supply connec tions for leaks See procedures under Testing Gas Supply Line Connections and Testing Heater Gas Connections on page 11 of this service manual 2 If all gas connections inside an...

Page 20: ...as malfunctioning type of gas used propane or natural gas purchase date In most cases we will ask you to return the defective part to the factory Parts Not Under Warranty Contact authorized dealers of...

Reviews: