vENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un

-

confined space. When ventilating to an adjoining 

unconfined space, you must provide two perma

-

nent openings: one within 12" of the ceiling and 

one within 12" of the floor on the wall connecting 

the two spaces (see options 1 and 2, Figure 2). You 

can also remove door into adjoining room (see 

option 3, Figure 2). Follow the 

National Fuel Gas 

Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for 

Combustion and Ventilation

 for required size of 

ventilation grills or ducts.

Figure 3 - Ventilation Air from Outdoors

Figure 2 - Ventilation Air from Inside 

Building

AIR FoR CoMBUsTIoN 

ANd VeNTIlATIoN

Continued

INsTAllATIoN

NOTICE: This heater is intended 

for  use  as  supplemental  heat. 

Use this heater along with your 

primary heating system. Do not 

install  this  heater  as  your  pri

-

mary heat source. If you have a 

central heating system, you may 

run system’s circulating blower 

while using heater. This will help 

circulate the heat throughout the 

house. In the event of a power 

outage, you can use this heater 

as your primary heat source.

 WARNING: A qualified ser

-

vice person must install heater. 

Follow all local codes.

CHECK GAS TYPE

Use only the correct type of gas (natural or pro

-

pane/LP). If your gas supply is not the correct gas 

type, do not install heater. Call dealer where you 

bought heater for proper type heater.

This  appliance  is  only  for  use 

with the type of gas indicated on 

the rating plate. This appliance 

is  not  convertible  for  use  with 

other gases.

  WARNING:  This  appliance 

is equipped for (natural or pro

-

pane/LP) gas. Field conversion 

is not permitted.

Outlet

Air

Ventilated

Attic 

Outlet

Air

Inlet

Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

Or 

Remove 

Door into 

Adjoining 

Room, 

Option 3

Ventilation Grills 

Into Adjoining Room,

Option 2

12"

12"

Ventilation

Grills

into Adjoining

Room, 

Option 1

ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or 

ducts. You must provide two permanent openings: 

one within 12" of the ceiling and one within 12" 

of the floor. Connect these items directly to the 

outdoors or spaces open to the outdoors. These 

spaces include attics and crawl spaces. Follow the 

National Fuel Gas Code, ANSI Z223.1/NFPA 54, 

Section 5.3, Air for Combustion and Ventilation

 for 

required size of ventilation grills or ducts.

IMPORTANT:

 Do not provide openings for inlet 

or outlet air into attic if attic has a thermostat-

controlled power vent. Heated air entering the attic 

will activate the power vent.

Summary of Contents for VP20BTA

Page 1: ...appliance Do not touch any electrical switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your g...

Page 2: ...cause cancer or birth defects or other reproductive harm IMPORTANT Read this owner s manualcarefullyandcompletely before trying to assemble operate or service this heater Improper use of this heater c...

Page 3: ...ther gases 2 Do not place propane LP supply tank s in side any structure Locate propane LP supply tank s outdoors propane LP models only 3 If you smell gas shut off gas supply do not try to light any...

Page 4: ...purchaser a copy of 527 CMR 30 upon sale of the unit Vent free gas products are prohibited for bed room and bathroom installation in the Com monwealth of Massachusetts Unpacking 1 Remove heater from c...

Page 5: ...ir that leaks around doors and windows may provide enough fresh air for combustion and ventilation However in buildings of unusually tight construction you must provide additional fresh air Unusually...

Page 6: ...es Di rect vent draws combustion air from the outdoors and vents to the outdoors Example Gas water heater _______________Btu Hr Vent free heater ______________Btu Hr Total ______________Btu Hr 40 000...

Page 7: ...heater Follow all local codes CHECK GAS TYPE Use only the correct type of gas natural or pro pane LP If your gas supply is not the correct gas type do not install heater Call dealer where you bought...

Page 8: ...bedroom or bathroom in a recreational vehicle where curtains furniture clothing or other flammable objects are less than 36 from the front top or sides of the heater as a fireplace insert in high traf...

Page 9: ...on each end of mounting bracket to attach bracket to wall These two holes are 14 apart from their centers Attach mounting bracket to wall in one of two ways 1 Attaching to wall stud 2 Attaching to wal...

Page 10: ...r flush to wall 4 For thin walls 1 2 or less insert red key into wall anchor Push red key to pop open anchor wings see Figure 10 IMPORTANT Do not hammer key For thick walls over 1 2 thick or solid wal...

Page 11: ...er with base 3 For carpeted floors make a small cut with a sharp knife at marked locations prior to drill ing If mounting base to a wood floor drill 1 8 diameter hole 3 4 deep Do not use anchors in wo...

Page 12: ...inants This keeps them from going into heater controls If sediment trap is not installed or is installed wrong heater may not run properly Figure 14 External Regulator With Vent Pointing Down External...

Page 13: ...by either opening propane LP supply tank valve for propane LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air 3 Check all joints from gas meter for n...

Page 14: ...OR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not fol low these instructions exactly a fire or explosion may result causing property damage per sonal injury or loss of life A This appliance ha...

Page 15: ...t you determine your own comfort levels MANUAL LIGHTING PROCEDURE 1 Remove front panel see Figure 4 page 8 2 Follow steps 1 through 7 under Lighting Instructions page 14 3 With control knob pressed in...

Page 16: ...nd pilot assembly clean and free of dust and dirt To clean these parts we recommend using compressed air no greater than 30 PSI Your local computer store hardware store or home center may carry compre...

Page 17: ...in gas lines when in stalled 5 Depleted gas supply pro pane LP gas only 6 ODS pilot is clogged 7 Gas regulator setting is not correct OBSERVED PROBLEM When ignitor button is pressed there is no spark...

Page 18: ...ntrol knob is released Burner does not light after ODS pilot is lit Delayed ignition of burner Burner backfiring during combustion REMEDY 1 Press in control knob fully 2 AfterODS pilotlights keepcon t...

Page 19: ...s or furniture Heater produces a clicking tick ing noise just after burner is lit or shut off Heater shuts off in use ODS operates REMEDY 1 Check burner for dirt and debris If found clean burner see C...

Page 20: ...see Checking Gas Connec tions page 12 1 Locate and correct all leaks see Checking Gas Connec tions page 12 2 Replace control valve 1 Take apart gas tubing and remove foreign matter 2 Locate and corre...

Page 21: ...tion and operating instructions included Thermostatically controlled blower turns itself on and off as required Specifications VN20BTA 10 000 20 000 Btu hr Variable Natural Gas Electronic Ignition Pre...

Page 22: ...0 10 11 12 13 14 16 18 19 4 7 1 15 17 20 Illustrated Parts Breakdown Models VN20BTA VP20BTA VN30BTA VP30BTA AA Battery Positive UP AAA Battery Negative UP Install Battery According To This Illustratio...

Page 23: ...7894 14 Deflector Assembly 1 107894 15 Deflector Assembly 1 9 098271 11 Ignitor Cable 1 10 098249 01 Nut M5 2 11 110803 01 ODS Pilot Assembly 1 110803 02 ODS Pilot Assembly 1 12 103446 02 Burner 1 103...

Page 24: ...ginal condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects caused by improper installation Travel diagno...

Reviews: