www.desatech.com
111035-01F
1
INSTALLATION
Continued
INSTALLING DAMPER CLAMP
ACCESSORY FOR vENTED
OPERATION
Note:
When used as a vented heater, appliance
must be installed only in a solid-fuel burning
fireplace with a working flue and constructed of
noncombustible material.
For Massachusetts Residents Only:
In
-
stallation of this vented gas log set in the Com
-
monwealth of Massachusetts requires the damper
be permanently removed or welded in the fully
open position.
If your heater is a manually-controlled model, you
may use this heater as a vented product. There
are three reasons for operating your heater in the
vented mode.
1. The fireplace does not meet the clearance
to combustibles requirements for vent-free
operation.
2. State or local codes do not permit vent-free
operation.
3. You prefer vented operation.
If reasons number 1 or 2 above apply to you, you
must permanently open chimney flue damper. You
must install the damper clamp accessory (to order,
see
Accessories
, page 39). This will insure vented
operation (see Figure 10). The damper clamp will
keep damper open. Installation instructions are
included with clamp accessory.
See chart below for minimum permanent flue
opening you must provide. Attach damper clamp
so the minimum permanent flue opening will be
maintained at all times.
Area of various Standard
Round Flues
Diameter
Area
5"
0 sq. inches
6"
9 sq. inches
7"
39 sq. inches
8"
51 sq. inches
Chimney
Minimum Permanent
Height
Flue Opening
6' to 15'
39 sq. inches
15' to 30'
9 sq. inches
INSTALLING HEATER BASE
ASSEMBLY
WARNING: You must secure
this heater to fireplace floor. If
not, heater will move when you
adjust controls. Moving heater
may cause a gas leak or log
misplacement.
WARNING: If installing in a
sunken fireplace, special care
is needed. You must raise the
fireplace floor to allow access
to heater control panel. This
will insure adequate air flow
and guard against sooting and
controls being damaged. Raise
fireplace floor with noncombus
-
tible material. Make sure material
is secure.
CAUTION: Do not pick up
heater base assembly by burners.
This could damage heater. Only
handle base assembly by grates.
IMPORTANT:
Make sure the heater burners are
level. If heater is not level, heater will not work
properly.
Figure 10 - Attaching Damper Clamp
Damper
Clamp
Damper
Manufactured
Fireplace
Masonry Fireplace
Damper