c.  caulking  or  sealants  are  applied  to 

areas  such  as  joints  around  window 
and door frames, between sole plates 
and floors, between wall-ceiling joints, 
between  wall  panels,  at  penetrations 
for plumbing, electrical, and gas lines, 
and at other openings.

If your home meets all of these three cri-

teria,  you  must  provide  additional  fresh 
air.  See 

Ventilation  Air  From  Outdoors

page 8.

If your home does not meet all of the three 

criteria  above,  proceed  to 

Determining 

Fresh-Air  Flow  For  Fireplace  Location

below.

Confined and Unconfined Space

The 

National Fuel Gas Code, ANSI Z223.1/

NFPA 54

 defines a confined space as a space 

whose volume is less than 50 cubic feet per 
1,000 Btu per hour (4.8 m

3

 per kw) of the ag

-

gregate input rating of all appliances installed 

in that space and an unconfined space as a 
space whose volume is not less than 50 cubic 
feet per 1,000 Btu per hour (4.8 m

3

 per kw) 

of the aggregate input rating of all appliances 
installed in that space. Rooms communicating 

directly with the space in which the appliances 
are installed*, through openings not furnished 
with doors, are considered a part of the un

-

confined space.
* Adjoining rooms are communicating only if 
there are doorless passageways or ventilation 
grills between them.

DETERMINING FRESH-AIR FLOW 

FOR FIREPLACE LOCATION

Determining if You Have a Confined or 
Unconfined Space

Use this work sheet to determine if you have 
a confined or unconfined space.

Space:

  Includes  the  room  in  which  you  will 

install fireplace plus any adjoining rooms with 
doorless  passageways  or  ventilation  grills 
between the rooms.

1.  Determine the volume of the space (length 

x width x height).

 

Length x Width x Height =__________cu. ft. 
(volume of space)

 

Example:

 Space size 16 ft. (length) x 14 ft. 

(width) x 8 ft. (ceiling height) = 1792 cu. ft. 

(volume of space)

AIR FOR COMBUSTION AND VENTILATION

Continued

 

If  additional  ventilation  to  adjoining  room 
is supplied with grills or openings, add the 

volume of these rooms to the total volume 
of the space.

2.  Multiply the space volume by 20 to deter-

mine  the  maximum  Btu/Hr  the  space  can 
support.

 

  ________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)

 

Example:

 1792 cu. ft. (volume of space) x 20 

=  35,840  (maximum  Btu/Hr  the  space  can 

support)

3.  Add the Btu/Hr of all fuel burning appliances 

in the space.

 

Vent-free fireplace 

 ___________ Btu/Hr

 

Gas water heater* 

 ___________ Btu/Hr

 

Gas furnace 

 ___________ Btu/Hr

 

Vented gas heater   ___________ Btu/Hr

 

Gas fireplace logs 

 ___________ Btu/Hr

 

Other gas 

 

     appliances* 

+ __________ Btu/Hr

 

Total 

= __________ Btu/Hr

 

* Do not include direct-vent gas appliances. 

Direct-vent  draws  combustion  air  from  the 

outdoors and vents to the outdoors.

 

Example:

 

Gas water heater 

 ___________ Btu/Hr

 

Vent-free fireplace  +

 __________ Btu/Hr

 

Total 

= __________ Btu/Hr

4.  Compare  the  maximum  Btu/Hr  the  space 

can support with the actual amount of Btu/Hr 

used.

 

  _______ Btu/Hr  (maximum  the  space  can 
support)

 

  _______ Btu/Hr  (actual  amount  of  Btu/Hr 
used)

 

Example:

  35,840  Btu/Hr  (maximum  the 

space can support)

 

 

40,000 Btu/Hr (actual amount of 

Btu/Hr used)

The  space  in  the  example  on  the  previous 

page is a confined space because the actual 

Btu/Hr used is more than the maximum Btu/Hr 

the space can support. You must provide addi

-

tional fresh air. Your options are as follows:
A.  Rework  worksheet,  adding  the  space 

of an adjoining room. If the extra space 
provides  an  unconfined  space,  remove 
door to adjoining room or add ventilation 
grills between rooms. See 

Ventilation Air 

From Inside Building, 

page 8

30,000
10,000
40,000

Summary of Contents for Unvented (Vent-Free) Gas Compact Classic Hearth Fireplace VMH26NRB

Page 1: ...al switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire departmen...

Page 2: ...s appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other gases Aftermarket Completion of sale not for purpose of resale from...

Page 3: ...the OFF position to prevent children from turning on burners with remote You must operate this fireplace withthefireplacescreeninplace Make sure fireplace screen is closed before running fireplace Ke...

Page 4: ...that can be purchased separately wall switch hand held ON OFF remote wall thermostat hand held thermostat remote See Accessories page 35 Local Codes Install and use fireplace with care Follow all loca...

Page 5: ...udes one hardware packet Assembly Local Codes Continued 4 Check fireplace for any shipping dam age If heater is damaged call DESA Heating LLC at 1 866 672 6040 for replacement parts before returning t...

Page 6: ...from the house to operate You must provide adequate fresh air for these appliances This will insure proper venting of vented fuel burning appliances PROVIDING ADEQUATE VENTILATION The following are e...

Page 7: ...th x Width x Height __________cu ft volume of space Example Space size 16 ft length x 14 ft width x 8 ft ceiling height 1792 cu ft volume of space AIR FOR COMBUSTION AND VENTILATION Continued If addit...

Page 8: ...adjoining room see option 3 Figure 4 Follow the National Fuel Gas Code ANSI Z223 1 NFPA 54 Air for Combustion and Ventilation for required size of ventilation grills or ducts AIR FOR COMBUSTION AND V...

Page 9: ...clearance installations Wall or framing ma terial can be placed directly against any exterior surfaceontherear sides ortopofyourfireplace except where standoff spacers are integrally at tached If stan...

Page 10: ...in Figure 6 Example The face of a mantel bookshelf etc is made of combustible material and protrudes 3 1 2 from the wall This com bustible material must be 4 from the side of the fireplace opening se...

Page 11: ...lve The flexible gas line must be the last item installed on the gas piping Nails or Wood Screws Nailing Flanges Figure 9 Attaching Fireplace to Wall Studs Wall Studs 4 If you have not assembled fireb...

Page 12: ...ollowing raise the mantel to an accept able height remove the mantel Figure 10 Minimum Mantel Clearances for Built In Installation OPTIONAL MANTEL Installation Refer to instructions provided with the...

Page 13: ...shoulder screws Align fireplace in mantel assembly so the trim overlaps mantel evenly on all three sides 12 Lower bottom louver door Use 3 wood screws provided with mantel accessory to attach fireplac...

Page 14: ...oles in the rear of the valve cover shieldandthroughtherectangularholeinthe front of shield see Figure 16 page 15 8 Reconnect red wire to switch position 3 Reconnect blue wire to switch position 1 Rec...

Page 15: ...tch Plate Blue Red Valve Cover Shield Snap Bushing Black Blower Mounting Holes Lower Louver Door Power Cord Figure 17 Wiring Diagram For Blower Accessory Standard Installation Red Red Fan Switch Auto...

Page 16: ...t In Installation WARNING A licensed elec trician must connect the wiring harness to electrical supply followingalllocalcodes Electri cianmustprovideaclamponthe box cover to secure the wiring Wiringsh...

Page 17: ...f you do not reduce incoming gas pressure fireplace regulator damage could occur Install external regula tor with the vent pointing down as shown in Figure 21 Pointing the vent down protects it from f...

Page 18: ...te sediment trap where it is within reach for cleaning Install in piping system between fuel supply and heater Locate sediment trap where trapped matter is not likely to freeze Asediment trap traps mo...

Page 19: ...flame to check for a leak Apply a noncorrosive leak detection fluid toalljoints Bubblesformingshow a leak Correct all leaks at once CAUTION Make sure exter nal regulator has been installed betweenprop...

Page 20: ...e Figure 28 Discard switch plate after removing Save the screws 4 Locate battery clip mounted on back of receiver see Figure 29 5 Slide 9 volt battery not included through the clip 6 Attach terminal w...

Page 21: ...side of base see Figure 33 WARNING Do not con nect the thermostat to a power source Electrical shock and or a fire hazard will occur 6 Connect one bare wire end to each terminal W and R of the thermos...

Page 22: ...see Figure 32 page 21 2 Connect remaining wire terminal to TH terminal on control valve Make sure that wire terminals are in the positions on your unit as pictured in Figure 32 page 21 If wires are n...

Page 23: ...this fireplace with the fireplace screen in place Make sure fire place screen is installed before running fireplace Figure 36 Control Knob and Ignitor Button Location Shown as Supplied No Control Opt...

Page 24: ...e the selector switch is in the OFF positionwhenyouareawayfrom home for long periods of time Fireplacewillcomeonautomati cally with selector switch in the ON position TO TURN OFF GAS TO APPLIANCE Shut...

Page 25: ...rol 2 Press MANU button to turn on fireplace 3 Press POWER and LOCK buttons to gether to turn off fireplace Auto Thermostatic Mode 1 Press POWER and LOCK buttons together to turn on hand held remote c...

Page 26: ...red setting Thermostat has been electronically calibrated at the factory and requires no adjustment or leveling Upon installation thermostat must be allowed to stabilize at room temperature for a mini...

Page 27: ...liance page 24 see Troubleshooting page 30 Note The pilot flame on natural gas units will have a slight curve but flame should be blue and have no yellow or orange color BURNER FLAME PATTERN Figure 45...

Page 28: ...re hardware store or home center may carry compressed air in a can If using compressed air in a can please follow the directions on the can If you don t follow directions on the can you could dam age...

Page 29: ...remove one piece log set for clean ing refer to Installing Log Set and Screen page 22 for placement instructions Replace log set if broken or chipped dime sized or larger CABINET Air Passageways Use...

Page 30: ...in PILOT position 4 Air in gas lines when in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Reconnect ignitor cable 2 Free ignit...

Page 31: ...trol knob pressed in 30 seconds 3 Wait one minute for safety interlock system to reset Repeat ignition operation 4 Fully open equipment shut off valve 5 A Contact local natural or propane LP gas compa...

Page 32: ...ne checked by local natural gas company 3 Observe minimum instal lation clearances see page 10 4 Clean burner see Cleaning and Maintenance page 28 or replace burner orifice 1 Turn fireplace off when u...

Page 33: ...each your gas supplier call the fire department IMPORTANT Operating fireplace where impurities in air exist may create odors Cleaning supplies paint paint remover cigarette smoke cements and glues new...

Page 34: ...t s call DESA Heating LLC at 1 866 672 6040 When calling DESA Heating LLC have ready your name your address model and serial numbers of your heater how heater was malfunctioning purchase date Usually...

Page 35: ...Unfinished Traditional Design W26TO Oak Finished Traditional Design W26GO Oak Finished Georgian Design Mantel features clean classic lines Available in a stained oak or unfinished hardwood ready to s...

Page 36: ...atech com 113110 01H 36 Parts MODELS VMH26PRB and VMH26NRB 39 37 38 4 22 40 32 11 28 30 12 7 35 25 10 9 7 23 1 2 20 20 8 14 8 24 33 34 13 41 21 26 18 15 27 20 3 20 29 16 18 3 17 42 36 6 4 20 19 31 31...

Page 37: ...01 Injector 1 20 M11084 26 Screw Hex Head 10 x 3 8 25 21 098249 01 Nut M5 6 22 103781 01 Gas Valve 1 103781 02 Gas Valve 1 23 102639 01 Baffle 1 24 101628 01 Flexible Connector 1 25 104305 01 Control...

Page 38: ..._____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____...

Page 39: ..._____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____...

Page 40: ...proved by DESA Heating LLC Warranty parts must be obtained through authorized dealers of this prod uct and or DESA Heating LLC who will provide original factory replacement parts Failure to use origin...

Reviews: