background image

107304-01D

For more information, visit www.desatech.com

For more information, visit www.desatech.com

16

1.

Determine the route your vertical venting will take. If ceiling
joists, roof rafters, or other framing will obstruct the venting
system, consider an offset (see Figure 32) to avoid cutting load
bearing members. 

Note:

 Pay special attention to these installa-

tion instructions for required clearances (air space) to combus-
tibles when passing through ceilings, walls, roofs, enclosures,
attic rafters, etc. Do not pack air spaces with insulation. Also
note maximum vertical rise of the venting system and any maxi-
mum horizontal offset limitations. Offsets must fall within the
parameters shown in Figures 36 through 38, pages 17 and 18.

2.

Set the stove in desired location. Drop a plumb line down from
the ceiling to the position of the burner system exit flue. Mark
the center point where the vent will penetrate the ceiling. Drill
a small locating hole at this point.

Drop a plumb line from the inside of the roof to the locating
hole in the ceiling. Mark the center point where the vent will
penetrate the roof. Drill a small locating hole at this point.

Flat Ceiling Installation

1.

Cut a 10" (25.4cm) square hole in the ceiling using the locat-
ing hole as a center point. The opening should be framed to
10"x10" (25.4cm x 25.4cm) inside dimensions, as shown in
Figure 25 on page 14 using framing lumber the same size as
the ceiling joists. If the area above the ceiling is an insulated
ceiling or a room, nail firestop from the top side. This pre-
vents loose insulation from falling into the required clear-
ance space. Otherwise, install firestop below the framed hole.
The firestop should be installed with no less than three nails
per side (see Figure 33).

2.

Assemble the desired lengths of pipe and elbows necessary
to reach from the burner system flue up through the firestop.
All connections must be sealed with high temperature sili-
cone sealant as specified in the second warning statement on
page 12. Be sure all pipe and elbow connections are fully
twist-locked (see Figure 24, page 13).

3.

Cut a hole in the roof using the locating hole as a center point.
(Cover any exposed open vent pipes before cutting hole in roof.)
The 10"x10" (25.4cm x 25.4cm) hole must be measured on
the horizontal; actual length may be larger depending on the
pitch of the roof. There must be a 1" clearance from the vent
pipe to combustible materials. Frame the opening as shown in
Figure 25 on page 14.

4.

Connect a section of pipe and extend up through the hole.

Note:

 If an offset is needed to avoid obstructions, you must

support the vent pipe every 3 feet. Use wall straps for this
purpose (see Figure 32). Whenever possible, use 45° elbows
instead of 90° elbows. The 45° elbow offers less restriction
to the flow of the flue gases and intake air.

5.

Place the flashing over the pipe section(s) extending through
the roof. Secure the base of the flashing to the roof and fram-
ing with roofing nails. Be sure roofing material overlaps the
top edge of the flashing as shown in Figure 32. There must be
a 1" clearance from the vent pipe to combustible materials.

Figure 32 - Offset with Wall Strap and 45° Elbows

INSTALLATION FOR VERTICAL
TERMINATION

NOTICE: Use rigid pipe only. Flex venting is not to be
used with a vertical termination.

VENTING INSTALLATION

Continued

Figure 33 - Installing Firestop

If area above is not a
room, install firestop below
framed hole.

If area above is a room, install
firestop above framed hole.

45° Elbow

Wall Strap

Roof
Flashing

Ceiling Firestop

VENTING INSTALLATION

Installation for Vertical Termination

Summary of Contents for PSCIVFC Series

Page 1: ...ETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Installation and service must be performed by a qualified installer service agency...

Page 2: ...totheaboveteststandards Thisstove with burner system is a vented product This stove with burner system will not produce any gas leakage into your home if properly installed Thisstovewithburnersystemmu...

Page 3: ...on or around stove 12 Do not use this stove to cook food or burn paper or other objects 13 Never place anything on top of stove 14 Do not use any solid fuels wood coal paper cardboard etc in this stov...

Page 4: ...olor walls or cause odors LOCAL CODES Install and use stove and burner system with care Follow all local codes In the absence to local codes use the current National Fuel Gas Code ANSI Z223 1 NFPA 54...

Page 5: ...ating 2 Remove all screws fastening the wood frame enclosure Spread wood frame open and lift away from plastic bagged stove body The bottom pieces of pallet wood will remain bolted to the stove body 3...

Page 6: ...Tighten step bolt until snug Make sure door moves freely 11 Install door catch bolt M8 x 1 25 55mm with two M8 hex nuts into threaded hole on stove body see Figure 9 Use an adjust able wrench or a 12m...

Page 7: ...round plate Discard these screws wash ers and screen They are for vent free use only see Figure 14 16 Replace the two screws from step 14 to reassemble the front plate and the front surround plate Set...

Page 8: ...r and Bottom Cover from Stove Body Speed Control Blower Control Knob Locknut Blower Assembly Thermal Switch and Bracket Control Shaft TOP VIEW Stove Body Rear Cover Bottom Cover Hex Screws Mounting Sc...

Page 9: ...otor and thermal switch are securely attached and that the screw retaining the green ground wire is tight Green Ground Wire Wiring Diagram Decal Speed Control Black Wire White Wire Blue Wire Power Cor...

Page 10: ...decks or utility buildings within 24 from the front of the termination cap Do not locate termination cap where excessive snow or ice build up may occur Be sure to clear vent termination area after sno...

Page 11: ...supply inlet 72 inches 182 9cm minimum L clearance above paved side walk or a paved driveway located on public property 84 inches 213 3cm minimum M clearance under veranda porch deck 12 inches 30 5cm...

Page 12: ...m clearance of 2 from the top of the pipe and 1 minimum to the sides and bottom Vertical sections of this system require a minimum of 1 clear ance to combustible materials on all sides of the pipe INS...

Page 13: ...Figure 24 Note Horizontal runs of vent must be supported every three feet Use wall straps for this purpose VENTING INSTALLATION Continued WARNING Do not recess vent terminal into a wall or siding Fig...

Page 14: ...her types of siding Combustible ExteriorWall For vinyl siding stucco or wood exteriors a siding standoff must be installed between the vent cap and exterior wall The siding standoff prevents excessive...

Page 15: ...ncludes a chart with vertical minimum maximum and horizontal maximum dimensions which must be met Seal all connections with high temperature silicone sealant outer pipe only as specified in the second...

Page 16: ...ith no less than three nails per side see Figure 33 2 Assemble the desired lengths of pipe and elbows necessary to reach from the burner system flue up through the firestop All connections must be sea...

Page 17: ...emperature silicone seal ant as specified in the second warning statement on page 12 Note Iftheventpipepassesthroughanyoccupiedareasabovethefirst floor includingstoragespacesandclosets youmustenclosep...

Page 18: ...ngConfigurationUsingTwo90 Elbows VENTING INSTALLATION Continued Venting with Two 90 Elbows Vertical V Horizontal H1 Horizontal H2 5 min 2 max 6 min 4 max 7 min 6 max 8 min 8 max 20 max 8 max Figure37...

Page 19: ...ement Vent Kit Includes Horizontal Square Termination 90 Elbow 7 12 Adjustable Coaxial Pipe 6 Pipe Adaptor 4 Coaxial Pipe WallFirestop DecorativeTrimPlateand18Screws VKS 47 K Snorkel Vent Kit Includes...

Page 20: ...ust supply an external regulator The external regulator will reduce incoming gas pressure Youmustreduceincominggaspressuretobetween11and 14 inches of water If you do not reduce incoming gas pressure b...

Page 21: ...ng Gas Supply Piping System Test Pressures In Excess Of 1 2 PSIG 3 5 kPa 1 Disconnect appliance with its appliance main gas valve con trol valve and equipment shutoff valve from gas supply pip ing sys...

Page 22: ...Apply noncorrosive leak test solution to all gas joints Bubbles forming show a leak Correct all leaks at once Pressure Testing Burner System Gas Connections 1 Open equipment shutoff valve see Figure 4...

Page 23: ...om the back on each side of the base see Figure 47 WARNING Do not connect this thermostat to a power source Electrical shock and or fire hazard will occur Figure 47 Back View of Thermostat Base Feed w...

Page 24: ...nit Terminal Wires Battery Cover 9 Volt Battery Remote Control Unit Battery Housing TPTH TPTH TP TP TH TH Figure 50 Installing Remote Receiver Figure 52 Installing Battery in Hand Held Remote Control...

Page 25: ...sition the parts in accor dance with these diagrams or failure to use only parts specifically approved with this burner system may result in property damage or personal injury INSTALLING LOGS LAVA ROC...

Page 26: ...a fire or explosion D Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system...

Page 27: ...when ON is lit In the AUTO mode the thermostat in the hand held re mote unit controls the room temperature To increase the room temperature press the top arrow of the TEMP but ton To lower the room t...

Page 28: ...lly controlled blower has an ON setting and an OFF setting The blower will only run when the switch is in the ON position In the OFF position the blower will not operate If you are using CDA3620TB blo...

Page 29: ...ng refer to Installing Logs Lava Rock and Glowing Embers page 25 to properly replace logs Use a vacuum cleaner to remove any carbon buildup on logs Replace log s if broken See Replacement Parts on pag...

Page 30: ...B Dirty or partially clogged pilot 5 Thermocouple connection loose at con trol valve 6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by...

Page 31: ...ved from line Have gas line checked by local pro pane LP or natural gas company 3 Clean burner see Cleaning and Maintenance page 29 or replace burner orifice 1 Adjust the log set so that the flame doe...

Page 32: ...rol valve defective 1 Gas leak See Warning statement above 1 Improper log placement 2 Air holes at burner inlet blocked 3 Burner flame holes blocked 4 Improper vent configuration OBSERVED PROBLEM Burn...

Page 33: ...1 4 x 23 1 2 23 1 4 x 33 1 4 x 23 1 2 59 1 x 84 5 x 59 7cm 59 1 x 84 5 x 59 7cm Weight lbs kg Burner System 70 lbs 31 8 kg 70 lbs 31 8 kg Shipping 75 lbs 34 kg 75 lbs 34 kg When installed in a model S...

Page 34: ...formation visit www desatech com 34 TPTH TPTH TP TP TH TH 24 4 19 20 21 23 26 1 26 4 26 2 26 3 29 24 4 25 4 1 28 28 4 7 8 9 18 10 11 13 12 15 16 17 22 4 2 3 6 22 27 14 4 5 ILLUSTRATED PARTS BREAKDOWN...

Page 35: ...H5C4 20B Hex Head Cap Screw 2 13 NTC 4C Locknut 2 14 105468 02 Valve Bracket 1 15 14389 Valve Natural 1 14390 Valve Propane LP 1 16 14561 Pilot Assembly Natural 1 14562 Pilot Assembly Propane LP 1 17...

Page 36: ...For more information visit www desatech com 36 ILLUSTRATED PARTS BREAKDOWN AMITY STOVE CHASSIS SCIVFC SERIES PSCIVFC SERIES Indicates Color Suffix Designation 2 5 8 7 4 6 5 5 7 1 7 2 5 4 7 3 1R 1C 1L...

Page 37: ...ove 1 104175 05 One Leg Forest Green 4 Total Per Stove 1 104175 06 One Leg Metallic Charcoal 4 Total Per Stove 1 104175 07 One Leg Porcelain Enamel Red 4 Total Per Stove 1 104175 08 One Leg Porcelain...

Page 38: ...ws easy wall access to the operation of your burner system This will allow you thermostatic control with the convenience of a wall switch WALL MOUNTED ON OFF SWITCH GWMS2 Not Shown For all models Allo...

Page 39: ...Completed College Completed Graduate School 13 Age of Purchaser Under 20 20 29 30 39 40 49 50 59 60 or Over 14 Buyer s total annual household income Under 15 000 15 000 to 19 999 20 000 to 34 999 35...

Page 40: ...107304 01D For more information visit www desatech com For more information visit www desatech com 40 2701 Industrial Drive P O Box 90004 Bowling Green KY 42102 9004 Postage Required TAPE TAPE...

Page 41: ...___________________________________________________________ _______________________________________________________________________________________________ ____________________________________________...

Page 42: ...ective stove and burner system will be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY...

Reviews: