OWNER’S MANUAL

For more information, visit www.desatech.com

CAST IRON STOVE
AND B-VENT
BURNER SYSTEM
ASSEMBLY

Continued

 WARNING: A qualified in-

staller or service person must
connect burner system to gas
supply. Follow all local codes.

INSTALLATION PRECAUTIONS

Consult local building codes before begin-
ning the installation. Only a qualified ser-
vice person should install venting system.
The installer must follow these safety rules:

• Wear gloves and safety glasses for

protection

• Use extreme caution when using ladders

or when on roof tops

• Be aware of electrical wiring locations

in walls and ceilings

VENTING
INSTALLATION

 WARNING: Read all instruc-

tions completely and thoroughly
before attempting installation. Fail-
ure to do so could result in serious
injury, property damage, or loss of
life. Operation of improperly in-
stalled and maintained venting sys-
tem could result in serious injury,
property damage, or loss of life.

NOTICE: Failure to follow these
instructions will void the warranty.

Continued

6.

Reattach bottom cover to rear cover
with 8 screws removed in step 2 on
page 8 (see Figure 18, page 7). Make
sure that you don’t pinch any wires
during reassembly.

Figure 23 - Typical B-Vent Installation

Round Top

Storm Collar

Flashing

Roof
Support

25mm (1")
Clearance to
Combustible
Material

Firestop
Spacer

Keep Electrical
Wires and Building
Insulation Away
from Gas Vent and
Out of the Required
Air Space

Enclosure
Wall

Gas Vent
Length

25mm (1")
Clearance to
Combustibles

Support
Plate

Adjustable
Length

• Venting instruction contained in this

manual may or may not apply to your
area. Consult your local authority for re-
quirement in your area.

• Where the gas vent extends through ac-

cessible spaces, it should be enclosed to
avoid personal contact and damage. En-
closure walls should have a fire rating
equal to or greater than the floors through
which the gas vent passes except in single
or two-family dwellings.

• Situate the gas vent in the structure so

that it can be installed without cutting
joists, sills, plates, or major load bearing
partitions or members. It is also impor-
tant to locate the base of the gas vent as
near as possible to the heating appliance.

• This heater must be properly connected to

a venting system. This heater is equipped
with a vent safety shutoff system.

• Use only vents labeled "FOR EXTE-

RIOR USE" above the roofline.

• Consult the authority having jurisdic-

tion to select the correct gas vent di-
ameter. Avoid using a larger than nec-
essary diameter.

The following actions will void the war-
ranty on your venting system:

• Installation of any damaged venting

component

• Unauthorized modification of the vent-

ing system

• Installation of any component part not

manufactured or approved by DESA
International

• Installation other than as instructed by

these instructions

Your burner system is approved for use with
any listed gas vent. A listed gas vent is a factory
made and listed system designed, and installed
exclusively for removing products of combus-
tion, excess air, and dilution air resulting from
burning fuel gas. Metal vents, the most com-
mon type of vent, employ double wall con-
struction enclosing an insulating air space.
This air space both helps keep flue gases warm
and reduce heat transferred to nearby combus-
tibles. This appliance is equipped with a safety
control system designed to protect against
improper venting of combustion products.

It is very important that the venting system
maintain its balance between the combus-
tion air intake and the flue gas exhaust.
Certain limitations apply to vent configura-
tions and must be strictly followed.

 WARNING: This gas stove with

burner system and vent assembly
must be vented directly to the out-
side. The venting system must
NEVER be attached to a chimney
serving a separate solid fuel burn-
ing appliance.

TYPE B-VENT INSTALLATION
(Listed B-0 or Greater)

Before beginning installation be sure that the
overall height and gas vent size conform to
building code requirements. Gas vents ex-
tending through pitched roofs can extend a
minimum height of at least 600 mm (2')
higher than any obstruction within 3m (10').
Gas vents extending through flat roofs are
required to extend at least 600 mm (2') above
the roof and at least 600 mm (2') higher than
any portion of the building or adjoining build-
ing within 3m (10') of the gas vent.

Summary of Contents for MSRBVN

Page 1: ...installationand operational procedures For as sistance or additional information consult a qualified installer ser vice agency or the gas supplier WARNING If the information in this manual is not foll...

Page 2: ...eated and sealed gas combustion products can spill into your home Carbon Monoxide Poisoning Early signs of carbon monoxide poisoning resemble the flu with headaches dizziness or nausea If you have the...

Page 3: ...gandventsvertically Heat is generated by both realistic flames and glowing embers When used without the blower accessory the stove with burner system requires no electricity making it ideal for emerge...

Page 4: ...d see Figures 3 and 4 4 This stove is a freestanding unit de signed to set directly on the floor If your stove is to be installed directly on carpeting vinyl tile or any combustible material other tha...

Page 5: ...e Figure 7 Rest stove on drop cloth orblankettoavoidscratchingstoveedges 7 Remove remaining pallet wood at tached to bottom of stove body see Figure 8 Use an adjustable wrench to remove bolts 8 Fasten...

Page 6: ...ly face down on a protected surface Remove the two screws that hold the front plate onto the front surround plate see Figure 14 Save these screws 15 Remove the seven screws and washers that hold the s...

Page 7: ...Body INSTALLING OPTIONAL BLOWER ACCESSORY 1 Remove4hexscrewssecuringrearcover to back of stove body see Figure 18 2 Separate bottom cover from rear cover by loosening the 8 mounting screws see Figure...

Page 8: ...re to the other side of the thermal switch see Figure 20 10 Connect the white wire to the other ter minal on the blower motor assembly see Figure 20 Make sure the thermal switch has been properly inst...

Page 9: ...major load bearing partitions or members It is also impor tant to locate the base of the gas vent as near as possible to the heating appliance This heater must be properly connected to a venting syst...

Page 10: ...NSTALLATION Continued CHECKING VENT CAPACITY Complete all gas piping electrical and vent connections After adjusting the fireplace andlightingthemainburners allowacouple of minutes for warm up Hold a...

Page 11: ...onsfrom0 4500feet When installing this stove and burner sys tem at an elevation above 2000 feet in the USA you may need to decrease the input rating by changing the existing burner ori fice to a small...

Page 12: ...tance to flow and may reduce draft enough to cause spillage The pitch of lateral runs can also be a problem lateral runs should be pitched 1 4 rise per foot of hori zontal run from the appliance to th...

Page 13: ...ed with the appliance or you can purchase it from your dealer CSA Design Certified Equipment Shutoff Valve with 1 8 NPT Tap 3 Minimum Propane LP From External Regulator 11 W C to 14 W C Pressure Appro...

Page 14: ...ee Figure 32 Connect flare union to flex ible gas line attached to gas regulator of fireplace see Figure 32 4 Check all gas connections for leaks See Checking Gas Connections CONNECTING STOVE AND BURN...

Page 15: ...Accessory INSTALLING OPTIONAL WALL MOUNTED SWITCH GWMS2 1 Connect one terminal of 25 ft wire for the wall switch to the TPTH terminal on the valve Connect remaining wire terminal to theTH terminal on...

Page 16: ...f the cover firmly and pull to separate from the base WARNING Do not connect this thermostat to a power source Electrical shock and or fire hazard will occur Figure37 BackViewofThermostatBase Feed wir...

Page 17: ...glass door to install logs lava rock and ember material To remove glass door you must first remove the front panel on stove body STOVE AND B VENT BURNER SYSTEM INSTALLATION Continued Figure 41 Instal...

Page 18: ...ury INSTALLING LOGS LAVA ROCK AND GLOWING EMBERS STOVE AND B VENT BURNER SYSTEM INSTALLATION Continued 1 2 3 4 Figure 45 Installing Log No 1 Figure 46 Installing Log No 2 Figure 47 Installing Log No 3...

Page 19: ...push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it call a qualified service technician Force or attempted repair may result in a f...

Page 20: ...will remain lit GHRCTA Series Operation 2b Press the AUTO ON OFF button on the hand held remote control see Figure 53 The lights to the left of the button will show AUTO ON or OFF Figure52 Settingthe...

Page 21: ...AL BLOWER ACCESSORY Blower controls are located on the left side of the rear cover of stove from front of stove The DA3610TA thermostatically con trolled blower has an ON setting and an OFF setting Th...

Page 22: ...WARNING Only parts sup pliedbythemanufacturershould be used when replacing broken ordamagedglassdoorpanel see ReplacementParts page26 This glass door panel is a complete unit No substitute materials m...

Page 23: ...ot fully open 4 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding piezo ignitor Nut is located...

Page 24: ...for a minute 2 Operate burner until air is removed from line Have gas line checked by local pro pane LP or natural gas company 3 Clean burner see Cleaning and Maintenance page 22 or replace burner or...

Page 25: ...per log placement 2 Air holes at burner inlet blocked 3 Burner flame holes blocked OBSERVED PROBLEM Burner system produces unwanted odors Burner system shuts off in use Gas odor even when control knob...

Page 26: ...elallwiresprior to disconnection when servicing controls Wiringerrorscancause improper and dangerous opera tion Verify proper operation af ter servicing Note Use only original replacement parts Thiswi...

Page 27: ...epartment at 1 877 SUNVAL1 for information You canalsowritetotheaddresslistedontheback page of this manual WALL MOUNTED THERMOSTAT CONTROL KIT GWMT1 Not Shown Allows easy wall access to the operation...

Page 28: ...6706 SUN VALLEY STOVE COMPANY For more information visit www desatech com ILLUSTRATED PARTS BREAKDOWN MSRBVN MSRBVP LO H I P I L O T OFF ON 4 4 17 18 19 21 23 1 23 4 23 2 23 3 16 4 22 10 5 11 8 1 9 25...

Page 29: ...43 Switch Screw 2 12 105468 01 Valve Bracket 1 13 105489 01 Valve Natural 1 105489 02 Valve Propane LP 1 14 105488 01 Pilot Assembly Natural 1 105488 02 Pilot Assembly Propane LP 1 15 102445 01 Ignito...

Page 30: ...106706 SUN VALLEY STOVE COMPANY For more information visit www desatech com ILLUSTRATED PARTS BREAKDOWN SUN VALLEY STOVE MC SERIES Indicates Color Suffix Designation 1R 1C 1L 5 8 8 7 4 6 5 5 7 1 7 2 5...

Page 31: ...lain Enamel Almond 4 Total Per Stove 1 104175 14 One Leg Porcelain Enamel Green 4 Total Per Stove 1 104175 15 One Leg Porcelain Enamel Red 4 Total Per Stove 1 6 104176 01 Leg Leveler bolt M8 x 1 25 55...

Page 32: ...be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES...

Reviews: