TROUBLESHOOTING

TROUBLESHOOTING

Note:

 Before troubleshooting the system, make sure the gas 

shutoff valve is ON.

The two most common causes of a malfunctioning gas appliance are:
1. Loose wiring connections
2. Construction debris clogging the pilot and/or gas control valve filter

OBSERVED PROBLEM

Ignitor will not spark or pilot will not light

Pilot will not stay lit

No gas to burner, although wall switch is 

set to the ON position

Frequent pilot outage

POSSIBLE CAUSE

1.  No gas supply or shutoff valve is OFF

2.  Air in gas line

3.  Construction debris clogging pilot orifice

4.  Low gas pressure

5.  Kinked pilot line

6.  Control valve is not opening 

7.  No power to unit or the ignition module 

or power transformer is bad

1.  Loose wiring on ignitor wire to ignition 

module and/or poor ground to ignition 

module

2.  Pilot flame too low to sense

1.  Wall  switch  wires  defective  or  too 

long

1.  Pilot  flame  may  be  too  low,  causing 

safety pilot to “drop out”

2.  Improper venting or excessive blockage

REMEDY

1.  Check to see if you have gas supply and 

that equipment shutoff valve is opened

2.  Repeat lighting procedure several times 

to purge all air out of lines. If after re-

peated attempts appliance does not light, 

call for qualified service and repair.

3.  Remove  debris  and  dirt,  inspect  and 

clean any other possible obstructions

4.  Contact  your  gas  supplier  to  check 

pressure

5.  Have a qualified technician replace pilot 

line

6.  Replace control valve (refer to 

Replace-

ment Parts

, page 28)

7.  Check that main power is on and that all 

wire connections are made correctly to 

the ignition model (see 

Wiring Diagram

page  23).  Check  for  24  VAC  at  the 

secondary side of the transformer. If 24 

VAC is present and the module does not 

operate, have the module replaced oth-

erwise have the transformer replaced

1.  Check wiring connection. Refer to wir-

ing diagram (see 

Wiring Diagram

, page 

23) and/or check ground wire to ignition 

module

2.  Clean and adjust pilot burner and check 

gas supply and inlet pressure to unit

Note:

 Have a qualified technician replace 

pilot assembly if broken or corroded

1.  Check electrical connections

1.  Clean and adjust pilot flame for maximum 

flame impingement on thermopile

2.  Have the vent system inspected, includ-

ing the termination cap. Remove any 

restriction or obstruction

  WARNING:  Turn  off  heater  and  let  cool  before 

servicing.  Only  a  qualified  service  person  should 

service and repair heater.

  CAUTION:  Never  use  a  wire,  needle  or  similar 

object to clean pilot. This can damage pilot unit.

Summary of Contents for KC36NE Series

Page 1: ...a quali ed installer service agency or the gas supplier This appliance may be installed in an aftermarket permanently located manufactured mo bile home where not prohibited by state or local codes Thi...

Page 2: ...nual carefully and completely before trying to assemble operateor service this replace Improper use of this replace can cause serious injury or death from burns re explosions electrical shock and carb...

Page 3: ...per or other objects 13 Do not use any solid fuels wood coal paper cardboard etc in this replace Use only the gas type indicated on replace nameplate 14 This appliance when installed must be electrica...

Page 4: ...pliance Due to high temperatures do not locate this replace in high traf c areas windy or drafty areas or near furniture or draperies Proper clearances must be maintained If your replace is to be inst...

Page 5: ...replace as a heat source FRAMING AND FINISHING Figure4showstypicalframingofthis replace Figure5showsfram ing for corner installation All minimum clearances must be met For available accessories for th...

Page 6: ...earance above paved side walk or a paved driveway located on public property 84 inches 213 3cm minimum M clearance under veranda porch deck 12 inches 30 5cm minimum N clearance above a roof shall exte...

Page 7: ...wall restops when penetrating walls and restops when penetrating ceilings or attic spaces Install horizontal venting with a 1 4 rise for every 12 of run toward the termination WARNING Read all instru...

Page 8: ...cking lugs indentations These lugs will slide straight into matching slots on the male ends of adjacent pipes Push pipe sections together and twist one section clockwise approxi mately one quarter tur...

Page 9: ...the center of the 10 3 4 square hole and attach to exterior wall with wood screws provided see Figure 11 The siding standoff must sit ush against the exterior fascia material 7 Combustible Exterior W...

Page 10: ...al minimum and maximum dimensions which MUST be met IMPORTANT Rememberthatahorizontalrunofventingmust have a 1 4 rise for every 12 of run toward the termination Figure 13 Typical Horizontal Terminatio...

Page 11: ...sement installation where one foot clearance from ground to termination is possible SNORKEL TERMINATION INSTALLATION Recommended Applications Installations requiring a vertical rise on building exteri...

Page 12: ...tion Planning Cont HORIZONTAL SYSTEM INSTALLATION USING TWO 90 ELBOWS The following con gurations show the minimum vertical rise re quirements for a horizontal system using two 90 elbows Venting with...

Page 13: ...ove framed hole 2 Assemble the desired lengths of pipe and elbows necessary to reach from the replace ue up through the restop Be sure all pipe and elbow connections are fully twist locked see Figure...

Page 14: ...Shown Venting with Two 90 Elbows Vertical V1 Horizontal H 5 min 6 max 6 min 12 max 7 min 18 max 8 min 20 max Note Vertical V1 Vertical V2 40 max Figure23 VerticalVentingCon gurationUsingTwo90 Elbows V...

Page 15: ...with your local gas company for proper ori ce size identi cation When installing this replace at an elevation above 4500 feet in Canada check with local authorities Consult your localgas companyto hel...

Page 16: ...Components FIREPLACE INSTALLATION Check Gas Type Installing Optional Blower Accessory PARTS LIST FOR VENTING KITS AND COMPONENTS DESA 5 8 Pipe Vent Kits Number Description P58 6 6 Section Double Wall...

Page 17: ...LACE INSTALLATION Continued Speed Control Control Shaft Locknut Control Knob Switch Bracket Blower Plug In Duplex Outlet Located underneath rebox oor against lower right outside wall Thermodisc Figure...

Page 18: ...lator with Vent Pointing Down Propane LP Only Propane LP Supply Tank External Regulator Vent Pointing Down 5 Mount the speed control box against the mounting plate provided in the lower replace cavity...

Page 19: ...s for turning on or shutting off the gas to the appliance Checkyourbuildingcodesforanyspecialrequirementsforlocating equipment shutoff valve to replaces Apply pipe joint sealant lightly to male NPT th...

Page 20: ...d on or near gas meter for natural gas replace 3 Make sure control knob of replace is in the OFF position 4 Check all joints from equipment shutoff valve to gas valve see Figure 34 for propane LP or F...

Page 21: ...leaning Glass Door See Cleaning and Maintenance on page 25 Lock Unlock Glass Frame Assembly Screw Hinge Latch INSTALLING LAVA ROCK AND GLOWING EMBERS It is very important to keep logs exactly as insta...

Page 22: ...39 Installing Rear Brick Panel Rear Brick Panel Left Side Brick Panel INSTALLING BRICK LINER MODELS BL36DA SA AND BL36DHA SA WARNING If replace has been running turn off and unplug replace Let cool b...

Page 23: ...he wall switch to the ON position 11 Visuallylocatethepilot Theignitorshouldbegintosparkand the main burner should ignite once ame appears at pilot If lighting the appliance for the rst time each seas...

Page 24: ...te control for the replace your replace and blower will not turn on and off at the same time The replacemayrunforseveralminutesbeforetheblower turns on After the heater modulates to the pilot position...

Page 25: ...rom glass If glass has been broken carefully remove glass door see Remov ing Replacing Glass Door page 20 Vacuum all glass pieces with a shop vac CAUTION Do not vacuum if pieces are hot Use only the t...

Page 26: ...all air out of lines If after re peated attempts appliance does not light call for quali ed service and repair 3 Remove debris and dirt inspect and clean any other possible obstructions 4 Contact your...

Page 27: ...just after burner is lit or shut off Slight smoke or odor during initial operation Gas odor even when control knob is in OFF position Gas odor during combustion Glass soots Dark residue on logs or ins...

Page 28: ...TS Note Use only original replacement parts This will protect your warranty coverage for parts replaced under warranty PARTS UNDER WARRANTY Contact authorized retailers of this product If they can not...

Page 29: ...let Supply Pressure 5 5 w c 11 0 w c Dimension Inches mm HxWxD Fireplace Actual size of rebox Measurements do not 36 x 41 x 21 1 8 36 x 41 x 21 1 8 include nailing anges or 914 x 1041 x 537 mm 914 x 1...

Page 30: ...h com 116238 01C ILLUSTRATED PARTS BREAKDOWN Models KC36NE VKC36NE KC36PE VKC36PE ILLUSTRATED PARTS BREAKDOWN MODELS KC36NE VKC36NE KC36PE AND VKC36PE 6 7 20 17 18 13 2 12 19 8 1 4 11 9 14 3 16 5 15 1...

Page 31: ...ctory Brick Panel 1 12 see below see below Rear Refractory Brick Panel 1 13 see below see below Right Refractory Brick Panel 1 14 108719 01 108719 01 Screen Rod 1 15 12105 12105 Screen 2 16 11418 1141...

Page 32: ...2 2 3 13 9 11 6 12 14 18 17 17 18 19 20 16 14 8 4 5 22 23 24 21 31 33 32 30 29 28 25 27 26 ILLUSTRATED PARTS BREAKDOWN Models KC36NE VKC36NE KC36PE VKC36PE ILLUSTRATED PARTS BREAKDOWN BURNER ASSEMBLY...

Page 33: ...l 1 108866 02 Elec Pilot Assembly Propane LP 1 11 14569 Elec Valve Assembly Natural 1 14570 Elec Valve Assembly Propane LP 1 12 11165 Screw 10 x 5 8 Zinc 1 13 111913 01 Burner Base Gasket 1 14 14396 B...

Page 34: ...L36DSA Standard Refractory Brick Liner Kit BL36DHA Textured Refractory Herringbone Brick Liner Kit BL36DHSA Standard Refractory Herringbone Brick Liner Kit Thisbricklineraddsatouchofstyletoyourdirect...

Page 35: ...te School 13 Age of Purchaser Under 20 20 29 30 39 40 49 50 59 60 or Over 14 Buyer s total annual household income Under 15 000 15 000 to 19 999 20 000 to 34 999 35 000 to 49 999 50 000 to 74 999 75 0...

Page 36: ...36 www desatech com 116238 01C 2701 Industrial Drive P O Box 90004 Bowling Green KY 42102 9004 Postage Required TAPE TAPE...

Page 37: ...______________________ ________________________________________________________________________________________________ ________________________________________________________________________________...

Page 38: ...and all such other costs related to repairing a defective heater will be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT...

Reviews: